Design Technical Manual

Table Of Contents
IN THE CASE OF ONE OUTDOOR UNIT CONNECTED
b
a
H
1
H
2
H
5
*4
Limitation:
ft. (m)
Diagram
Allowable pipe
length (actual
pipe length)
Between master outdoor unit and the farthest indoor unit 541 (165) or less a + b
Between the rst separation tube and the farthest indoor unit 197 (60) or less a
Total pipe length 2296 (700) or less *1 Total
Allowable height
di󰀨erence
Between outdoor
unit and indoor unit
Outdoor unit is higher than indoor unit 164 (50) or less
H1
Outdoor unit is
lower than indoor
unit
*2
O.T. ≥ 23°F (-5°C) 131 (40) or less
*2
O.T. < 23°F (-5°C) 16 (5) or less
Between indoor unit 49 (15) or less H2
Between RB unit and indoor unit 16 (5) or less H5
¾
1 : Total pipe length is limited by the condition that total refrigerant amount should not exceed 77lbs. (35kg).
¾
2: O.T. = Outdoor Temperature.
¾
4 : Although "b" does not have limitation. Set to be 541’ (165m) or less in total pipe length of "a+b".
¾
5 : The pipe length is 25’ (7.5m) or more, between master outdoor unit and the nearest indoor unit.
- (06 - 36) -
SYSTEM
DESIGN
SYSTEM
DESIGN