Design Technical Manual

Table Of Contents
CONNECTABLE UNIT WITHIN 1 RB UNIT
RB unit
Maximum number of
connectable indoor units
per branch
Connectable cooling capacity range
of indoor unit
Single type
UTP-RU01AH 3 27,000 Btu/h or less
UTP-RU01BH 8 60,000 Btu/h or less
UTP-RU01CH 8 96,000 Btu/h or less
Multi type UTP-RU04BH 8
60,000 Btu/h or less
for 1 branch
191,000 Btu/h or less
(Sum total of 4 branches)
z
Caution (Multi type)
When there is a branch which is not used, install less than 1 branch per one set of Multi
type, and less than 2 branches per 1 refrigerant system.
However, be sure to connect indoor unit about the furthest branch from outdoor unit side.
Only "Multi type RB unit" is connectable with the side opposite to piping connected the
outdoor unit side and maximum connectable number is "two".
In case of two RB units connected in series ( total 8-branches ), maximum capacity of
connectable indoor units is up to 191,000 Btu/h.
OUTDOOR UNIT COMBINATION
Combinations other than the followings are prohibited.
Ton
Nominal coling
capacity
(Btu/h)
Set model name
Combination
*1
Outdoor unit 1
(Master)
Outdoor unit 2
(Slave 1)
Outdoor unit 3
(Slave 2)
6 72,000 AOUA72TLBV AOUA72TLBV - -
8 96,000 AOUA96TLBV AOUA96TLBV - -
10 120,000 AOUA120TLBV AOUA120TLBV - -
12 144,000 AOUA144TLBVG AOUA72TLBV AOUA72TLBV -
14 168,000 AOUA168TLBVG AOUA96TLBV AOUA72TLBV -
16 192,000 AOUA192TLBVG AOUA120TLBV AOUA72TLBV -
18 216,000 AOUA216TLBVG AOUA120TLBV AOUA96TLBV -
20 240,000 AOUA240TLBVG AOUA120TLBV AOUA120TLBV -
22 264,000 AOUA264TLBVG AOUA96TLBV AOUA96TLBV AOUA72TLBV
24 288,000 AOUA288TLBVG AOUA96TLBV AOUA96TLBV AOUA96TLBV
*1
:
Selecting outdoor unit capacity in order of
Outdoor unit 1 ≥ Outdoor unit 2 ≥ Outdoor unit 3
(Master) (Slave 1) (Slave 2)
- (06 - 02) -