Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
MODEL : ARUM36TLAV
Hi (SP mode00)
Hi (SP mode01)
Hi (SP mode02)
Hi (SP mode03)
Hi (SP mode07)
Hi (SP mode06)
Hi (SP mode05)
Hi (SP mode08)
Hi (SP mode09)
Hi (Normal SP)
0.24 (60)
0.40 (100)
0.16 (40)
0.32 (80)
0.08 (20)
0 (0)
0.48 (120)
0.56 (140)
0.64 (160)
Air Flow [CFM (m
3
/h)]
External Static Pressure [in.WG (Pa)]
(1000)(900)(700) (800) (1100) (1200) (1300) (1400) (1600)(1500) (1700) (1800) (2000)(1900) (2100) (2200)
589530412 471 647 706 765 824 942883 1001 1059 11771118 1236 1295
SP mode9
upper limit
Normal SP
upper limit
Normal SP
lower limit
SP mode00
upper limit
SP mode9
lower limit
Hi (SP mode9)
Hi (Normal SP)
Hi (SP mode00)
Lo (Normal SP)
Lo (SP mode00)
Lo (SP mode9)
0.24 (60)
0.40 (100)
0.16 (40)
0.32 (80)
0.08 (20)
0 (0)
0.48 (120)
0.56 (140)
0.64 (160)
External Static Pressure [in.WG (Pa)]
(1000)(900)(700) (800) (1100) (1200) (1300) (1400) (1600)(1500) (1700) (1800) (2000)(1900) (2100) (2200)
589530412 471 647 706 765 824 942883 1001 1059 11771118 1236 1295
Air Flow [CFM (m
3
/h)]
- (04-175) -
INDOOR
UNITS
INDOOR
UNITS