Submittal Sheet

Submittal Data:ASU9RLS2 9,000 BTU Wall Mount Type
Inverter Driven Heat Pump
Job Name:______________________________ Date:_______________________________
Location:_______________________________ Approval:____________________________
Engineer:_______________________________ Construction:_________________________
Submitted to:____________________________ Unit #:______________________________
Submitted by:___________________________ Drawing #:___________________________
Reference:______________________________
Model Information
Evaporator…………………………….……..…………...………….… ASU9RLS2
Condenser compatibility………………………….… AOU9RLS2, AOU18RLXFZ
AOU24RLXFZ, AOU36RLXFZ, AOU48RLXFZ
Electrical ……………………………………….…........ 208/230V AC 1ph-60Hz
Available Voltage Range……………………..……..….……....… 208/230 +/- 10%
Minimum Circuit Ampacity……………...…………………........…......…... 0.19 A
Full Load Amps………………………………………………………..……. 0.15 A
Input Power ……………………………………….……....…………….……. 16 W
Running Current………………………………………………………..…… 0.14 A
Capacity
Nominal Cooling………………….…………...…..…………………... 9,000 Btu/h
Fan Motor
Type: DC ……………………………..……………………………... Cross flow x1
Motor Output………………………………………………………….…...…. 36 W
Fan Motor Protection……………………………...… off: 320 ± 45°F (160 ± 25°C)
Airflow Rate on: 230 ± 45°F (110 ± 25°C)
Cooling (High / Medium / Low / Quiet)
353 CFM (600 m3/h) / 324 CFM (550 m3/h) / 277 CFM (470 m3/h) / 194 CFM (330 m3/h)
Heating (High / Medium / Low / Quiet)
353 CFM (600 m3/h) / 324 CFM (550 m3/h) / 277 CFM (470 m3/h) / 194 CFM (330 m3/h)
Heat Exchanger
Dimensions
(H x W x D) in. (mm)………...……..……. 12-5/8 x 27-3/16 x 13/16 (320x690x20)
Fin Pitch……………………………………...…...…..… Main 23 FPI / Sub 18 FPI
Rows x Stages………………………………………………. Main 2 x20 / Sub 1 x4
Pipe Type (Material)………....………………...………………………....… Copper
Type (Material)……………………..…………...……............................. Aluminum
Note: Specifications are based on the following conditions.
Cooling: Indoor temperature of 80°F (26.7°C) DB/67°F (19.44°C) WB, and outdoor temperature of 95°F (35°C) DB/75°F (23.9°C) WB.
Heating: Indoor temperature of 70°F (21.11°C) DB/59°F (15.°C) WB, and outdoor temperature of 47°F (8.33°C) DB/43°F (6.11°C) WB.
Pipe length: 24ft. 7in. (7.5m), Height difference: 0ft. (0m) (Outdoor unit indoor unit)
Refrigerant Type R410A.
Wired and wireless remote controllers
Auto changeover
Weekly timer
Removable open panel
Super quiet operation
Temperature Setting Range
Cooling…………...………….…………….……..…… 64°F - 90°F (18°C 32 °C)
Heating………………………………………….……… 60°F - 88°F (16°C - 30°C)
Enclosure
Material………………………………………...……...……Galvanized Steel Sheet
Sound Pressure Level
Cooling
High/Medium/Low/Quiet….........36 dB (A) / 32 dB (A) / 28 dB (A) / 21 dB (A)
Heating
High/Medium/Low/Quiet…………. 36 dB (A) / 32 dB (A) / 28 dB (A) / 21 dB (A)
Dimensions
H x W x D
in. (mm)..................................................... 11-1/8 x 34-1/4 x 7-5/16 (282x870x185)
Connection Pipe
Liquid……………………...………..……………..…..……...… 1/4” in. (6.35 mm)
Gas………………………..….....……………….………….…... 3/8” in. (9.52 mm)
Method (Liquid/Gas)………………...…..........………..…...……………....… Flare
Drain hose
Material…………………….…………………………………….…… PP + LLDPE
Size……….…. Ø9/16 (I.D.), Ø5/8 to Ø11/16 [Ø13.8 (I.D.), Ø15.8 to Ø16.7 O.D.)]
Weight
Net……………………...………………………...………………… 21 lbs. (9.5 kg)
Gross…………………........…………………………….……...…… 27 lbs. (12 kg)
Accessories
Wired Remote Controller…………………………………...……… UTY-RNNUM
Backlit Display……………….............…………………………….. UTY-RVNUM
Simple Remote Controller…………………….................…………. UTY-RSNUM
Dry Contact Wire Kit……………………………………...………. UTY-XWZXZ5
Interface Kit……………………………………………………...… UTY-TWBXF1
Intertek©ETL Number
ASU9RLS2………..………………………………...………….……………. 91986
Fujitsu General America, Inc.
353 Route 46 West
Fairfield, NJ 07004
Toll Free: 1-888-888-3424
Fax: (973) 836-0447
www.fujitsugeneral.com
General Features
Removable air filter
Energy Saving Program
Program timer
5 years standard parts warranty
Eligible for 10 year or 12 year parts
warranty. See warranty statement
for details.
1 of 2