ADDITIONAL CHARGE CALCULATION6.
MODEL
: AOU9RLFF, AOU12RLFF
Refrigerant charge
z
MODEL
: AOU15RLFF
Refrigerant charge
z
Refrigerant type R410A
Refrigerant amount
lbs. oz. 2lbs.10oz.
g 1200
Pipe length
ft. 49 or less 66 (MAX)
0.22oz./ft.
(20g/m)
m 15 or less 20 (MAX)
Additional charge
oz. 0 +3.5
g 0 +100
Refrigerant type R410A
Refrigerant amount
lbs. oz. 2lbs.12oz.
g 1250
Pipe length
ft. 49 or less 66 (MAX)
0.22oz./ft.
(20g/m)
m 15 or less 20 (MAX)
Additional charge
oz.
0
+3.5
g 0 +100