Design and Technical Manual

- (01 - 30) -
FLOOR TYPE
AGU9-15RLF
FLOOR TYPE
AGU9-15RLF
10) Room temperature control for wired remote controller sensor
Refer to Function 95, before performing this setting.
Depending on the installed environment, correction of the wired remote controller temperature
sensor may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both "01".
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
(
. . .Factory setting)
Function number Setting value Setting description
92
(For cooling)
93
(For heating)
00 No correction 0.0°F 0.0°C
01 No correction 0.0°F 0.0°C
02 -1°F (-0.5°C)
More cooling
Less heating
03 -2°F (-1.0°C)
04 -3°F (-1.5°C)
05 -4°F (-2.0°C)
06 -5°F (-2.5°C)
07 -6°F (-3.0°C)
08 -7°F (-3.5°C)
09 -F (-4.0°C)
10 +1°F (+0.5°C)
Less cooling
More heating
11 +F (+1.0°C)
12 +3°F (+1.5°C)
13 +4°F (+2.0°C)
14 +5°F (+2.5°C)
15 +6°F (+3.0°C)
16 +7°F (+3.5°C)
17 +8°F (+4.0°C)
11) Heat Insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment.
Standard insulation "00" allows system to rapidly respond to the cooling or heating load
changes. High insulation "01" is when the heat insulation structure of the building is high and
does not require system to rapidly respond to cooling or heating load changes.
When High insulation "01" is selected;
• Overheating (overcooling) is prevented at the start-up.
• All room temp. control settings (Function 30, 31, 92, 93) will reset to No correction [0.0°F
(0.0°C)].
(
. . .Factory setting)
Function number Setting value Setting description
95
00 Standard insulation
01 High insulation
NOTE:
When changing Function 95, perform this setting before other Room temp. control settings
(Function 30, 31, 92, 93). IF Function 95 is not set rst, Room temperature control settings
(Function 30, 31, 92, 93) will be reset and you must re-do them again.