Design and Technical Manual

- (01 - 27) -
FLOOR TYPE
AGU9-15RLF
FLOOR TYPE
AGU9-15RLF
FUNCTION DETAILS
Functions
1) Filter sign
2) Vertical airow direction range control
3) Room temperature control for indoor unit sensor
4) Auto restart
5) Room temperature sensor switching
6) Remote controller custom code
7) External input control
8) Room temperature sensor switching (Aux.)
9) Indoor unit fan control for energy saving for cooling
10) Room temperature control for wired remote controller sensor
11) Heat Insulation condition (building insulation)
1) Filter sign
Select appropriate intervals for displaying the lter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
... Factory setting)
Function number Setting value Setting description
11
00 Standard (400 hours)
01 Long interval (1000 hours)
02 Short interval (200 hours)
03 No indication
2) Vertical airow direction range control
In a concealed installation, change the setting to "Fixed" (02) to restrict the movement of the
upper air outlet so that the airow is only towards the horizontal direction.
(
... Factory setting)
Function number Setting value Setting description
23
00 Standard
01 (Setting prohibited)
02 Fixed (Concealed)