AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASUG09LMAS ASUG12LMAS OUTDOOR AOUG09LMAS1 AOUG12LMAS1 DR_AS115EF_01 2019.12.
Notices: • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks FGLair™ is trademark of Fujitsu General Limited in the United States, other countries or both. Google Play™ is trademark of Google Inc. App Store® is a service mark of Apple Inc., registered in the U.S. and other countries. Copyright © 2019 Fujitsu General Limited. All rights reserved.
CONTENTS Part 1. INDOOR UNIT...........................................................................1 1. Specifications................................................................................................2 2. Dimensions....................................................................................................4 2-1. Models: ASUG09LMAS and ASUG12LMAS....................................................................4 2-2. Installation space requirement .................................
CONTENTS (continued) Part 2. OUTDOOR UNIT.....................................................................47 1. Specifications..............................................................................................48 2. Dimensions..................................................................................................49 2-1. Models: AOUG09LMAS1 and AOUG12LMAS1.............................................................49 3. Installation space ............................................
Part 1.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS 1. Specifications Wall mounted Type Inverter heat pump Model name ASUG09LMAS Power supply Power supply intake Available voltage range Rated Cooling Min.—Max. Rated Capacity Heating Min.—Max. Heating (17 °F)*1 Cooling Heating Input power Heating (17 °F)*1 Cooling Heating Current EER Cooling COP Heating SEER HSPF Cooling Heating Cooling Heating Power factor Rated Max. Rated Min.—Max. Rated Min.—Max. Rated Max.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS Wall mounted Type Inverter heat pump Model name ASUG09LMAS ASUG12LMAS NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80 °F (26.67 °CDB) /67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB). – Heating: Indoor temperature of 70 °FDB (21.11 °CDB) /60 °FWB (15.56 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) /43 °FWB (6.11 °CWB).
WALL MOUNTED ASUG09-12LMAS 2-1. Models: ASUG09LMAS and ASUG12LMAS Unit: in (mm) 8-3/4 (222) 10-5/8 (270) 32-13/16 (834) 1/8 (3.0) 12-7/8 (327) 10-3/4 (273) 2-1/8 (54) 1-11/16 (43) (10-5/8 [270]) 3/8 (9.5) (32-13/16 [834]) Outline of indoor unit 10-3/4 (273) 8-11/16 (220) 1-11/16 (43) WALL MOUNTED ASUG09-12LMAS 2. Dimensions 2-1/2 (63) 1-7/8 (48) 7-3/16 (182) 13-5/8 (346) 7-3/16 (182) 14 (356) for pipe inlet Ø 2-9/16 (65) 2-1.
Unit: in (mm) 3 (67) or more 3 (70) or more 2 (40) or more Wall hook bracket 5 (107) or more Outline of the indoor unit 8 (183) or more 71 (1,800) or more 60 (1,500) or more 2-2. Installation space requirement -5- 2. Dimensions WALL MOUNTED ASUG09-12LMAS Provide sufficient installation space for product safety. 2 (50) or more WALL MOUNTED ASUG09-12LMAS 2-2.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS 3. Wiring diagrams 3-1. Models: ASUG09LMAS and ASUG12LMAS 3-1. Models: ASUG09LMAS and ASUG12LMAS -6- 3.
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1. Cooling capacity ¢ Model: ASUG09LMAS AFR CFM 453 Indoor temperature °FDB °FWB Outdoor temperature °FDB 14 23 32 41 50 59 67 77 87 95 104 115 64 54 TC SHC kBtu 8.34 5.55 7.95 5.29 7.57 5.04 7.18 4.78 6.80 4.52 6.41 4.85 8.53 5.29 8.02 5.29 7.54 5.12 7.10 4.98 5.90 4.64 4.20 3.28 IP kW 0.21 0.23 0.23 0.23 0.21 0.21 0.43 0.49 0.55 0.61 0.49 0.
WALL MOUNTED ASUG09-12LMAS AFR CFM 453 Indoor temperature °FDB °FWB Outdoor temperature °FDB 14 23 32 41 50 59 67 77 87 95 104 115 64 54 TC SHC kBtu 11.25 7.76 10.66 7.36 10.07 6.95 9.47 6.54 8.88 6.13 8.29 6.35 11.43 7.47 10.82 7.13 10.10 6.99 9.49 6.69 8.05 6.35 5.66 5.15 IP kW 0.33 0.37 0.40 0.40 0.39 0.40 0.65 0.75 0.85 0.93 0.87 0.69 70 60 TC SHC kBtu 12.53 8.65 11.87 8.19 11.21 7.74 10.56 7.29 9.90 6.84 9.25 6.38 12.73 7.51 12.04 7.17 11.26 7.03 10.58 6.72 8.97 6.38 6.28 5.19 IP kW 0.33 0.
WALL MOUNTED ASUG09-12LMAS NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: ASUG09LMAS AFR CFM 453 Outdoor temperature °FDB °FDB °FWB 5 14 23 32 41 47 50 59 68 75 3 12 19 28 37 43 47 50 59 64 60 TC kBtu 8.87 9.87 11.61 13.19 14.60 15.84 15.92 16.09 15.18 15.68 IP kW 1.18 1.25 1.33 1.43 1.52 1.54 1.56 1.47 1.14 1.20 TC kBtu 8.64 9.61 11.31 12.84 14.22 15.43 15.51 15.67 14.78 15.27 IP kW 1.20 1.28 1.35 1.46 1.55 1.57 1.59 1.49 1.17 1.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS 5. Fan performance 5-1. Air velocity distributions ¢ Models: ASUG09LMAS and ASUG12LMAS Fan speed HIGH Measuring conditions Operation mode FAN (ft)(m) Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 10 3 7 2 3 1 0 0 3 1 7 2 10 3 Unit: ft/s (m/s) 7 (2) 3 (1) 2 (0.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS 5-2. Airflow ¢ Model: ASUG09LMAS Cooling Fan speed Airflow HIGH m3/h l/s CFM MED m3/h l/s CFM LOW m3/h l/s CFM QUIET m3/h l/s CFM 770 214 453 600 167 353 450 125 265 250 69 147 Heating Fan speed 5-2. Airflow Airflow HIGH m3/h l/s CFM MED m3/h l/s CFM LOW m3/h l/s CFM QUIET m3/h l/s CFM - 11 - 770 214 453 640 178 377 520 144 306 310 86 182 5.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS ¢ Model: ASUG12LMAS Cooling Fan speed Airflow m3/h HIGH 770 214 453 600 167 353 450 125 265 250 69 147 l/s CFM MED m3/h l/s CFM LOW m3/h l/s CFM QUIET m3/h l/s CFM Heating Fan speed 5-2. Airflow Airflow HIGH m3/h l/s CFM MED m3/h l/s CFM LOW m3/h l/s CFM QUIET m3/h l/s CFM - 12 - 770 214 453 640 178 377 520 144 306 310 86 182 5.
WALL MOUNTED ASUG09-12LMAS 6-1. Noise level curve ¢ Models: ASUG09LMAS and ASUG12LMAS Cooling Heating 80 Octave band sound pressure level, dB: (0 dB=0.0002 µbar) 80 Octave band sound pressure level, dB: (0 dB=0.
Type of protection Model Protection form Circuit protection Current fuse (PCB*) Fan motor protection Power IC thermal shutdown protection ASUG09LMAS and ASUG12LMAS Activate Reset 250 V, 3.15 A 257±18°F (125±10°C) Fan motor stop 212±18°F (100±10°C) Fan motor restart *PCB: Printed Circuit Board - 14 - 7. Safety devices WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS 7.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS 8.
With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m). • The wire connection should be separate from the power cable line. ¢ External input and output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB.
Use an external output cable with appropriate external dimension, depending on the number of cables to be installed. ¢ External input and output PCB • • • • A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m). Output voltage: High DC 12 V±2 V, Low 0 V. Permissible current: 50 mA For details, refer to "Combination of external input and output" on page 18.
By combining the function setting of the rotary switch setting of the External input and output PCB, you can select various combinations of functions.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS 8-4.
Function setting Rotary SW on External input and output PCB 46-02 1 External input External input and output PCB Input signal Command Off → On On → Off Forced stop Normal CN313 On CN313 Off Forced stop Normal Indoor unit Operation Stop On Remote controller On On – In the case of “Pulse” input: Function setting Rotary SW on External input and output PCB 46-02 1 External input External input and output PCB Input signal Command Pulse Pulse Forced stop Normal CN313 CN314 On CN313 Off
Function setting Rotary SW on External input and output PCB 46-03 1 External input External input and output PCB CN313 Input signal Command Off → On Operation Stop (R.C. disabled) On → Off On CN313 Off Operation Indoor unit Stop (R.C. disabled) On Remote contoller Off On – In the case of “Pulse” input: Function setting Rotary SW on External input and output PCB 46-03 1 External input External input and output PCB Input signal Command CN313 Pulse CN314 Pulse Operation Stop (R.C.
Rotary SW on External input and output PCB 2 B C External input External input and output PCB CN313 Input signal Command Off → On Thermostat off On → Off Normal operation On Off Input Compressor On Off Room temp. Set temp. 8-4. Details of function - 22 - 8.
• Operation/Stop status Rotary SW on External input and output PCB External output 1 B C D External input and output PCB CN310 Output signal Command Off → On Operation On → Off Stop Output signal Command Off → On On → Off Off → On On → Off Error Normal Error Normal The output is low when the unit is stopped.
Rotary SW on External input and output PCB 2 B C 8-4. Details of function External output External input and output PCB - 24 - CN312 Output signal Command Off → On Heater on On → Off Heater off 8.
Function setting Control Auxiliary heater control 1 Auxiliary heater control 2 Heat pump prohibition control Auxiliary heater control by outdoor temperature 1 Auxiliary heater control by outdoor temperature 2 Primary heater Auxiliary heater Indoor unit Wired R. C. Control switching external heaters No.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS Auxiliary heater control 1 Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode • Error occurred • Forced thermostat off • Fan stop protection • Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature switching of external heaters).
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS Heat pump prohibition control Perform heating by external heater only. Indoor unit is continuous thermostat off. Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature.
This control selects heat pump or external heater according to the outdoor temperature. When outdoor temperature is high, the heating is performed by using heat pump only. Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS • Operation status 46.4°F (8°C) Outdoor temperature (Factory setting) 42.8°F (6°C) -0.4°F (-18°C) -4°F (-20°C) Heat pump prohibition zone Outdoor temperature zone * Combination zone Heat pump only zone On Comp. On/Off Off 12 V Heater Fan 0V On Off * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Heater on Heater off Condition Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS • Operation status 46.4°F (8°C) Outdoor temperature (Factory setting) 42.8°F (6°C) -0.4°F (-18°C) -4°F (-20°C) Heat pump prohibition zone Outdoor temperature zone * Combination zone On Comp. On/Off Off 12 V Heater Fan 0V On Off * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
NOTE: Group control cannot be used together with Wireless LAN adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available. 1. Connect up to 16 indoor units in a system. I.U. I.U. B I.U. C D I.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS 10. Remote controller 10-1. Wireless remote controller ¢ Overview Signal transmitter MODE button FAN button MIN. HEAT button TEMP. button SWING button ECONOMY button SET button POWERFUL button Start/Stop button TIMER SETTING button SELECT button RESET button SLEEP button CANCEL button TEST RUN button CLOCK ADJUST button NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation manual.
Unit: in (mm) 8-1/16 (205) Top view 11/16 (17) 2-3/8 (61) Front view Size (H × W × D) Weight Side view in (mm) oz (g) 8-1/16 × 2-3/8 × 11/16 (205 × 61 × 17) 4.4 (124) (without batteries) Holder Unit: in (mm) 1-15/16 (48.5) 3/16 (5.5) 1/8 (3.5) R 21/4 (6.5) 5-7/8 (150) Ø 1/8 (Ø3.5) (Hole) Hole 1-1/16 (26.2) 2-3/4 (69.3) Front View Size (H × W × D) Weight 10-1. Wireless remote controller Side View in (mm) oz (g) Bottom View 5-7/8 × 2-3/4 × 1-1/16 (150 × 69.3 × 26.
To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 11-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting procedure and the content of each function setting, select appropriate functions for your installation environment.
• The air conditioner custom code is set to prior to shipment. • If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you find the code that operates the air conditioner. 11-1. Function settings by using remote controller - 36 - 11.
Each function setting listed in this section is adjustable in accordance with the installation environment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Function no.
Function number Setting value Setting description Factory setting 11 00 01 02 03 Standard (400 hours) Long interval (1,000 hours) Short interval (200 hours) No indication ♦ 3) Room temperature control for indoor unit sensor NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment.
NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen. *When Function 95-01 (High insulation) is set, the Standard setting "00" will be the same as "No correction 0.0 °C" (01).
Function number Setting value Setting description Factory setting A B C D ♦ 44 00 01 02 03 8) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description Factory setting Operation/Stop mode 1 (R.C. enabled) (Setting prohibited) Forced stop mode Operation/Stop mode 2 (R.C. disabled) ♦ 46 00 01 02 03 9) Room temperature sensor switching (Aux.
Function number Setting value Setting description Factory setting 61 00 01 02 03 04 Auxiliary heater control 1 Auxiliary heater control 2 Heat pump prohibition control Auxiliary heater control by outdoor temperature 1 Auxiliary heater control by outdoor temperature 2 ♦ 12) Operating temperature switching of external heaters Sets the temperature conditions when the external heater is ON. For details, refer to "External heater output" on page 24.
Function number Setting value Setting description Factory setting 42.8 °F (6 °C) 14.0 °F (-10 °C) 17.6 °F (-8 °C) 21.2 °F (-6 °C) 24.8 °F (-4 °C) 28.4°F (-2 °C) 32.0 °F (0 °C) 35.6 °F (2 °C) 39.2 °F (4 °C) 42.8 °F (6 °C) 46.4 °F (8 °C) 50.0 °F (10 °C) 53.6 °F (12 °C) 57.2 °F (14 °C) 60.8 °F (16 °C) 64.4 °F (18 °C) ♦ 67 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 15) Heat insulation condition (building insulation) Heat insulation conditions differ according to the installed environment.
To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code. When 2 or more air conditioners are installed in a room, and the remote controller is operating an air conditioner other than the one you wish to set, change the custom code of the remote controller to operate only the air conditioner you wish to set.
Part name Exterior Q’ty Part name Exterior Q’ty Operating manual 1 Tapping screw (large) 5 Installation manual 1 Tapping screw (small) 2 Wall hook bracket 1 Cloth tape 1 Remote controller 1 Filter holder 2 Remote controller holder 1 Air cleaning filters 1 Battery 2 - 44 - 12. Accessories WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS 12.
WALL MOUNTED ASUG09-12LMAS WALL MOUNTED ASUG09-12LMAS 13. Optional parts 13-1. Controllers Exterior Office Model name Fri 10:00AM Mode Custom Auto Away Part name Cool Heat Set Temp. Cool Heat 84°F 68°F 80°F 74°F Fan Auto Room Temp. 76°F Vacation Status Menu Wired remote controller UTY-RNRUZ* Summary Easy finger touch operation with LCD panel. Backlit LCD enables easy operation in a dark room. Wire type: Non-polar 2-wire Optional communication kit is necessary for installation.
Exterior Part name Model name Required when external device is UTY-XWZXZ5 connected. External connect kit 13-2. Others Summary External input and output PCB UTY-XCSXZ2 Use to connect with external devices and air conditioner PCB. Optional External connect kit is necessary for installation. Communication kit UTY-TWRXZ2 Use to connect Non-polar 2-core wired remote controller.
Part 2.
1. Specifications Type Inverter heat pump AOUG09LMAS1 Power supply Power supply intake Available voltage range Starting current Airflow rate Fan A Cooling Heating Type × Q'ty Motor output Sound pressure level *1 4.0 954 (1,620) 954 (1,620) CFM (m3/h) Cooling Heating dB (A) Dimensions (H × W × D) in (mm) 46 48 Main1: 19-13/16 × 34-15/16 × 11/16 (504 × 888 × 18.19) Main2: 19-13/16 × 20-1/16 × 11/16 (504 × 510 × 18.
2. Dimensions 2-1.
3. Installation space ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
• Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following example “When an obstruction in the upper space:”.
Outdoor units installation in multi-row Unit: in (mm) Multiple parallel unit arrangement 10 4 (100) or more 40 (1,000) or more 8 (200) or more 20 (500) or more 10 (25 (25 0) or mo re 8 (200) or more 0) or mo 80 (2,000) or more re 16 (400) or more 40 (1,000) or more 8 (200) or more 10 (250) or more 40 (1,000) or more 8 (200) or more NOTES: • If the space is larger than stated above, the condition will be the same as when there is no obstacle.
4. Refrigerant circuit Heat exchanger (INDOOR) OUTDOOR UNIT AOUG09-12LMAS1 3-way valve ThPI 2-way valve Muffler Th R Muffler Compressor Th D 4-way valve Strainer Expansion valve Heat exchanger (OUTDOOR) Strainer ThHO ThO Cooling Heating ThD : Thermistor (Discharge temperature) ThO : Thermistor (Outdoor temperature) ThHO : Thermistor (Heat exchanger out temperature) ThR : Thermistor (Room temperature) ThPI : Thermistor (Pipe temperature) 4-1.
5. Wiring diagrams OUTDOOR UNIT AOUG09-12LMAS1 OUTDOOR UNIT AOUG09-12LMAS1 5-1. Models: AOUG09LMAS1 and AOUG12LMAS1 5-1. Models: AOUG09LMAS1 and AOUG12LMAS1 - 54 - 5.
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is lower than outdoor unit *2 OUTDOOR UNIT AOUG09-12LMAS1 OUTDOOR UNIT AOUG09-12LMAS1 Indoor unit is higher than outdoor unit *1 Outdoor unit Indoor unit H H Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOUG09LMAS1 and AOUG12LMAS1 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
7. Additional charge calculation Refrigerant type Refrigerant amount R410A 2 lb 2 oz 950 lb oz g OUTDOOR UNIT AOUG09-12LMAS1 OUTDOOR UNIT AOUG09-12LMAS1 7-1. Model: AOUG09LMAS1 ¢ Refrigerant charge ft m oz g Total pipe length Additional charge 49 or less 15 or less 0 0 66 (Max.) 20 (Max.) 3.5 100 0.22 oz/ft (20 g/m) 7-2. Model: AOUG12LMAS1 Refrigerant type Refrigerant amount R410A 2 lb 3 oz 1,000 lb oz g ¢ Refrigerant charge Total pipe length Additional charge 7-1.
8. Airflow Cooling OUTDOOR UNIT AOUG09-12LMAS1 OUTDOOR UNIT AOUG09-12LMAS1 8-1. Model: AOUG09LMAS1 Airflow m3/h 1,620 450 954 l/s CFM Heating Airflow m3/h 1,620 450 954 l/s CFM 8-2. Model: AOUG12LMAS1 Cooling Airflow m3/h 1,810 503 1,065 l/s CFM Heating Airflow m3/h 1,810 503 1,065 l/s CFM 8-1. Model: AOUG09LMAS1 - 57 - 8.
9. Operation noise (sound pressure) Cooling Heating 80 Octave band sound pressure level, dB: (0 dB = 0.0002 μbar) 80 Octave band sound pressure level, dB: (0 dB = 0.
9-2. Sound level check point Rear Microphone OUTDOOR UNIT AOUG09-12LMAS1 OUTDOOR UNIT AOUG09-12LMAS1 Microphone Airflow 40 in (1 m) Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. 9-2. Sound level check point - 59 - 9.
10. Electrical characteristics OUTDOOR UNIT AOUG09-12LMAS1 Power supply AOUG09LMAS1 Voltage Frequency MCA *1 Starting current Wiring spec. *2 MAX. CKT. BKR *3 Power cable Size Connection Limited wiring cable *4 length V Hz A A A AWG AWG ft (m) AOUG12LMAS1 208/230~ 60 9.7 4.0 11.5 6.0 15 14 14 69 (21) *1: Minimum Circuit Ampacity (Calculation based on UL60335-2-40) *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
11. Safety devices Circuit protection Current fuse (Main PCB) Fan motor protection Thermal protection program AOUG09LMAS1 Activate Reset Thermal protection program (Discharge temp.) Compressor protection Model Protection form Thermal protection program (Outdoor temp.) (Only in COOL or DRY mode) Activate Reset Activate Reset - 61 - AOUG12LMAS1 250 V, 15 A 250 V, 5 A 250 V, 3.
12. Accessories Exterior Q’ty Part name Exterior Q’ty Installation manual 1 Cable tie 2 Drain pipe 1 Drain cap 5 - 62 - 12.