Product Overview

Specifications
Material:
Steel – 22 Gauge
Finish:
Red enamel
Styles:
3 Spare sprinklers, ½ or ¾
6 Spare sprinklers, ½ or ¾
6 Spare, ESFR, ½, ¾ or 1”
12 Spare sprinklers ½ or ¾
24 Spare sprinklers
36 Spare sprinklers
3198 LIONSHEAD AVE
CARLSBAD, CA 92010
TEL + 1 760 599-1168
+ 1 800 344-1822
FAX + 1 800 344-3775
© 2016 Fire Protection Products, Inc.
Description
Fire Protection Products, Inc. Spare Sprinkler Head Cabinets are designed to allow for
spare sprinkler head storage as required by NFPA guidelines. The Spare Sprinkler Head
Cabinets are available in six congurations. Three head, six head, six head ESFR, twelve
head, twenty-four head, and thirty-six head. All six styles are manufactured with “knockouts”
to accommodate the most common size sprinklers. The shelf is positioned to allow for the
storage of a typical sprinkler head wrench. Each cabinet is nished in red enamel. Each spare
head cabinet comes with a hinged door which remains closed to protect the spare sprinklers
from the elements and features holes on the back panel to allow for attachment to most
surfaces utilizing the appropriate fasteners. Not intended for exposed or harsh environments.
WWW.FPPI.COM
Spare Sprinkler Head Storage Cabinet
Installation
Select the correct Spare Sprinkler Head Cabinet in accordance with the Automatic
Sprinkler Systems Handbook. As per the 1989 Edition the correct number of spare
sprinkler is as follows:
0-300 sprinklers, not less than 6; 300-1000, not less than 12; 1000 or more, not
less than 24. Stock of spare sprinklers shall include all types and ratings installed.*
Once the correct Spare Sprinkler Head Cabinet has been selected, installation
is accomplished by inserting the correct fastener in each of the holes inside the
cabinet, securing the cabinet securely to the wall. Insert the correct number and
type of sprinklers in accordance with the “handbook”.
*Final determination is subject to approval by the AHJ.