O B ID i-scan Installation Instructions ID ISC.LRM200-A/B M00602-1e-ID-B.
Identification System OBID i-scan Copyright 2000 by FEIG ELECTRONIC GmbH Lange Straße 4 D-35781 Weilburg-Waldhausen Germany http://www.feig.de Edition: er/01/01/04 - m00602-1e-id-b.doc With the edition of this manual, all previous editions become void. Indications made in this manual may be changed without previous notice. The reproduction of this document as well as the utilization and communication of its contents are strictly forbidden, as far as not expressly conceded.
Installation Instructions ID ISC.LRM200-A/B Contents: 1. Safety Instructions / Warning ......................................................................................4 2. Features of the ID ISC.LRM200-A/B Reader Module ..................................................5 2.1. Features ............................................................................................................................. 5 2.2. Available modules ....................................................................
Identification System OBID i-scan 1. Safety Instructions / Warning Read before startup ! • The device may be used only for the purpose intended by the manufacturer. • The Installation Instruction should be kept in an accessible location and handed out to every user and maintenance person. • Non-approved modifications and the use of replacement parts and accessories which have not been purchased or recommended by the manufacturer of the device may cause fires, electrical shocks and injury.
Installation Instructions ID ISC.LRM200-A/B 2. Features of the ID ISC.LRM200-A/B Reader Module 2.1. Features The ID ISC.LRM200-A/B Reader Module has been developed for reading passive data tags, socalled „Smart Labels“, at an operating frequency of 13.56 MHz. It is suitable for all applications in which long reading distances are required. Depending on the specific Reader Module used, a basic antenna (ID ISC.LRM200-A) or a basic antenna plus complementary antenna (ID ISC.
Identification System OBID i-scan 3. Installation and wiring The Reader Module is designed for installation on a heat sink. Mounting is accomplished using the ∅ 4.5 mm holes located in each corner of the base plate (see Fig. 3-1). To fully exploit the performance of the Reader Module, the heat sink should have a thermal resistance RThK of max. 0.8 K/W.
Installation Instructions ID ISC.LRM200-A/B 3.1. Terminals, sockets and switches 1 2 3 4 ON OFF X13 X19 S1 J50 J5 J4 V1 V2 V3 V4 V5 J402 X21 J51 J8 J350 J6 J1 X20 X15 X16 J2 J3 S2 X14 X18 Upper circuit board J401 J400 J405 J407 J403 X11 X6 X7 X9 X10 Lower circuit board X2 X3 X1 Fig. 3.
Identification System OBID i-scan 3.2. Antenna connection Two SMA sockets are provided on the lower circuit board for connecting the basic antenna or, in the case of ID ISC.LRM200-B, the basic/complementary antenna combination. The maximum tightening torque for the SMA socket is 0.45 Nm. Terminal Description X1 For connecting the complementary antenna (only ID ISC.
Installation Instructions ID ISC.LRM200-A/B 3.3. Supply voltage The supply voltage of 24 VDC is connected on Terminal X3 on the lower circuit board. The cable length between the power supply and the Reader Module must not exceed 3 m. Note: • Reversing the power supply wires may destroy the device. Terminal Name Description X3 / Pin 1 +24V + 24 V DC supply voltage X3 / Pin 2 GND Supply voltage ground X3 1 2 +24 V DC GND ! X1 Fig. 3.
Identification System OBID i-scan 3.4. X7: Inputs (optocoupler isolated) The optocoupler inputs on Terminal X7 are galvanically isolated from the Reader electronics and must therefore be powered by a separate external DC supply. The input LED’s on the optocouplers have an internal input series resistor of 500 Ω. For supply voltages above 10V the input current must be limited to max. 20 mA by an additional external dropping resistor (see Table 3.4-1).
Installation Instructions ID ISC.LRM200-A/B 3.5. X6: Output (optocoupler isolated) The transistor connections, collector and emitter, of the two optocoupler outputs are galvanically isolated from the Reader electronics and brought out on Terminal X8 without any additional circuitry. The outputs must therefore be supplied externally.
Identification System OBID i-scan 3.6. X11: Relay The relay output is a change-over contact. Terminal Name Description 1 COM 2 NC Normally closed contact 3 NO Normally open contact Working contact Notes: • The relay outputs are configured for max. 24 V DC / 60 W. • The relay outputs are designed to switch resistive loads only. If using an inductive load, the relay contacts must be protected by means of an external protection circuit.
Installation Instructions ID ISC.LRM200-A/B 3.7. X9: RS485 interface The asynchronous interface can be configured for RS485 or RS232 (see Section 5.1: Interface configuration using jumpers). The RS485 interface is configured on X9. The transmission parameters can be software configured. Configuration for X9 (RS485 interface): Terminal Name Description 1 4xxB RS485 – (B +) 2 4xxA RS485 - (A -) 3 4xxG RS485 – GND 4 422Y n.c. 5 422Z n.c. 6 422G n.c. ID ISC.
Identification System OBID i-scan 3.8. X10: RS232 interface The asynchronous interface can be configured for RS485 or RS232 (see Section 5.1: Interface configuration using jumpers). The RS232 interface is configured on X10. The transmission parameters can be software configured. Configuration for X10 (RS232 interface): Terminal Name Description 1 GND RS232 – GND 2 RxD RS232 - RxD 3 TxD RS232 - TxD ID ISC.
Installation Instructions ID ISC.LRM200-A/B 4. Control and display elements 4.1. LED´s Table 4.1-1 shows the configuration of the LED´s. Name LED V1 (green) LED V2 (red) LED V3 (red) Description "RUN-LED" - Indicates proper running of the internal Reader software - Flashing rate ca.
Identification System OBID i-scan 4.2. Buttons / switches Name Description S1 Reset button S2 1 - 3: Setting data bus addresses (0 ... 7) 4: not used Note : To set the bus address using S2, the Reader must be set to software address „0“ (factory setting).
Installation Instructions ID ISC.LRM200-A/B 5. Startup 5.1. Interface configuration using jumpers Jumpers J400 – J401 are used to configure the asynchronous interface for RS232 or RS485. Jumper RS232 RS485 400 1-2 2-3 401 1-2 2-3 Jumpers J403, J405 and J407 can be used to insert the termination resistors which may be required for the RS485 interface.
Identification System OBID i-scan 5.2. Setting addresses for bus operation For bus operation the Reader allows you to set the required bus address either using DIP switch S2 or through the software. a) Setting the bus address on S2 : Addresses „0“ to „7“ can be set on S2. To set the bus address using S2, the Reader must be set to software address „0“ (factory setting).
Installation Instructions ID ISC.LRM200-A/B 6. Technical Data for ID ISC.LRM200-A/B Mechanical Data • Dimensions ( W x H x D ) 120 x 160 x 69 mm • Weight 650 g Electrical Data • Supply voltage 24 V DC +5%/-1% Ripple : max. 20 mV • Power consumption max. 60 W • Operating frequency 13.56 MHz • Transmitting power 0.5 to 10 W* (software settable in 0.
Identification System OBID i-scan Functional characteristics • EEPROM (for parameters) 1 kB (10,000 write cycles) • RAM 256 kB • FLASH 512 kB (software update on interface possible) • Supported transponders I•Code, Tag-it (ISO transponder requires software update) • Address setting for interface Optional : - 3-position DIP switch (up to 8 addresses) - Software (up to 254 addresses) • Optical indicators 5 LED´s for status diagnostics • Multi-Reader mode Protocol synchronization through use of