Operating Instructions Transponder-Coded Safety Switch with Guard Locking CTP/CTA-L1/2-BP Unicode/Multicode EN
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP Contents 1. About this document.............................................................................................. 4 1.1. Scope.............................................................................................................................................4 1.2. Target group...................................................................................................................................4 1.3.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 11. 10.3. Fuse protection for power supply....................................................................................................17 10.4. Requirements for connecting cables................................................................................................18 10.5. Connector assignment of safety switch CTP/CTA-…‑BP‑…‑SII‑… with plug connectors 2 x M12.........................................................
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 1. About this document 1.1. Scope These operating instructions are valid for all CTP‑L1/2‑BP and CTA-L1/2-BP… from version V1.0.0. These operating instructions, the document Safety information and any enclosed data sheet form the complete user information for your device. 1.2.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 2. Correct use Safety switches series CTP‑L1/2-… and CTA-L1/2-… are interlocking devices with guard locking solenoid (type 4). The device meets the requirements according to EN IEC 60947‑5‑3. Devices with unicode evaluation possess a high coding level, devices with multicode evaluation possess a low coding level.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 3. Description of the safety function Devices from this series feature the following safety functions: Monitoring of guard locking and the position of the guard (interlocking device with guard locking according to EN ISO 14119) Ì Safety function (see chapter 6.5. Switching states on page 10): - The safety outputs are switched off when guard locking is released (monitoring of the locking element).
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 4. Exclusion of liability and warranty In case of failure to comply with the conditions for correct use stated above, or if the safety regulations are not followed, or if any servicing is not performed as required, liability will be excluded and the warranty void. 5. General safety precautions Safety switches fulfill personnel protection functions. Incorrect installation or tampering can lead to fatal injuries to personnel.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 6. Function The device permits the locking of movable guards. The system consists of the following components: coded actuator (transponder) and switch. Transponder-coded actuator Whether the device learns the complete actuator code (unicode) or not (multicode) depends on the respective version.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 6.2.7. Communication connection C A monitoring output with the suffix C has the additional function of providing a communication connection to a BR/IO-Link Gateway. The switch delivers cyclical and acyclical data. You will find an overview of the communication data in chapter 11. Using communication data on page 21. If no BR/IO-Link Gateway is connected, this output behaves like a monitoring output. 6.3.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 6.5. Switching states The detailed switching states for your switch can be found in the system status table (see chapter 13. System status table CTP/CTA-L1/2-BP on page 26). All safety outputs, signals and display LEDs are described there.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 7. Manual release Important! No further release functions can be retrofitted on Extended variants with control elements in position 1 (S1) and position 2 (S2). S1 S2 S3 Some situations require the guard locking to be released manually (e.g. malfunctions or an emergency). A function test must be performed after release. More information on this topic can be found in the standard EN ISO 14119:2013, section 5.7.5.1.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 7.1.2. Actuating auxiliary key release On devices with auxiliary key release (can be retrofitted), simply turn the key to release. Function as for auxiliary release. For mounting, see the auxiliary key release supplement. 7.2. Emergency release It permits opening of a locked guard from outside the danger zone without tools. For mounting, see the mounting supplement.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 7.3. Escape release The escape release is optional on CTP devices; on CTA devices it is optional or can be retrofitted. It permits opening of a locked guard from the danger zone without tools (see chapter 14.5.1. Dimension drawing for safety switch CTP… on page 31). Important! Ì It must be possible to operate the escape release manually from inside the protected area without tools.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 7.4.1. Laying wire front release Important! Ì Loss of the release function due to mounting errors, damage or wear. Ì Check the release function every time after mounting. Ì When routing the wire front release, ensure that it operates smoothly. Ì Observe the min. bending radius (100 mm) and minimize the number of bends. Ì The switch is not allowed to be opened. Ì Please observe the notes on the enclosed data sheets. 8.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 9. Mounting CAUTION Safety switches must not be bypassed (bridging of contacts), turned away, removed or otherwise rendered ineffective. Ì Observe EN ISO 14119:2013, section 7, for information about reducing the possibilities for bypassing an interlocking device. CAUTION Risk of damage to equipment and malfunctions as a result of incorrect installation. Ì Safety switches and actuators must not be used as an end stop.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 10. Electrical connection WARNING In the event of a fault, loss of the safety function due to incorrect connection. Ì To ensure safety, both safety outputs FO1A and FO1B must always be evaluated. Ì Monitoring outputs must not be used as safety outputs. Ì Lay the connecting cables with protection to prevent the risk of short circuits. CAUTION Risk of damage to equipment or malfunctions as a result of incorrect connection.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 10.1. Notes about Important! Ì This device is intended to be used with a Class 2 power source in accordance with UL1310. As an alternative an LV/C (Limited Voltage/Current) power source with the following properties can be used: - This device shall be used with a suitable isolating source in conjunction with a fuse in accordance with UL248. The fuse shall be rated max. 3.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 10.4. Requirements for connecting cables CAUTION Risk of damage to equipment or malfunctions as a result of incorrect connecting cables. Ì Use connection components and connecting cables from EUCHNER. Ì On the use of other connection components, the requirements in the following table apply. EUCHNER provides no warranty for safe function in case of failure to comply with these requirements.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 10.5. Connector assignment of safety switch CTP/CTA-…‑BP‑…‑SII‑… with plug connectors 2 x M12 Plug connector (view of connection side) 2 x M12 X1.5 X1.1 X1.2 X1.4 X1.3 X2.5 X2.1 X2.2 X2.4 X2.3 Pin Designation Function Conductor coloring of connecting cable 1) X 1.1 UB Electronics operating voltage, 24 V DC BN X 1.2 FO1A X 1.3 0VUB X 1.4 FO1B X 1.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 10.7. Connection The device is connected as shown in Fig. 3. The monitoring outputs can be routed to a control system. The switch can be reset via the RST input. To do this, a voltage of 24 V is applied to the RST input for at least 3 s. The RST input must be connected to 0 V if it is not used. If there is an internal error (see chapter 13. System status table CTP/CTA-L1/2-BP on page 26), the reset does not work.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 11. Using communication data A BR/IO-Link Gateway is required to use the device’s communication data and forward them to a higher-level bus system. The following devices are suitable: Ì GWY-CB-1-BR-IO (BR/IO-Link Gateway) Ì ESM-CB (safety relay with integrated BR/IO-Link Gateway) 11.1. Connection to a BR/IO-Link Gateway GWY-CB The Gateway is an IO-Link device.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 11.3.2.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 11.4. Notes on operation with safe control systems Observe the following requirements for connection to safe control systems: Ì Use a common power supply for the control system and the connected safety switches. Ì A pulsed power supply must not be used for UB. Tap the supply voltage directly from the power supply unit.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 12. Setup 12.1. LED displays You will find a detailed description of the signal functions in chapter 13. System status table CTP/CTA-L1/2-BP on page 26. LED Color STATE green LOCK yellow DIA red LED STATE LOCK DIA 12.2. Teach-in function for actuator (only for unicode evaluation) The actuator must be allocated to the safety switch using a teach-in function before the system forms a functional unit.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 12.2.1. Actuator teach-in 1. Establish teach-in standby: - Devices in the condition as supplied: unlimited teach-in standby after switching on. - Switch already taught-in: teach-in standby is available for approx. 3 min after switching on. ¨ Teach-in standby indication, STATE LED flashes 3x repeatedly. 2. Insert the actuator during teach-in standby. ¨ The automatic teach-in operation starts (duration approx. 30 s).
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP off off 5 Hz X off off off 5 Hz closed on on on open off off off 1x closed off off on 1 x inverse open off off off 1x Normal operation, door open open off off off 3x Device in teach-in standby closed off X on 1 Hz X off X X X off x x 1x X off off off 3x X off off off 4x X off X X 5x X off off off State LOCK (yellow) STATE (green) DIA (red) and diagnostic signal OI
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 14. Technical data NOTICE If a data sheet is included with the product, the information on the data sheet applies. 14.1. Technical data for safety switch CTP-L1/2-BP Parameter Value min. typ. Unit max.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP Parameter Value min. typ. Unit max. Reliability values acc. to EN ISO 13849‑1 Mission time 20 years Monitoring of guard locking and the guard position Category 4 Performance Level (PL) e PFHD 5.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP Parameter Value min. Monitoring outputs OL/C, OI, OD Output voltage Max. load typ. Unit max. 3 semiconductor outputs, p-switching, short circuit-proof 0.8 x UB - UB V DC 1 - 50 mA Solenoid Solenoid operating voltage UIMP (reverse polarity protected, regulated, residual ripple < 5%) DC 24 V +10%/-15% Solenoid current consumption IIMP Connection rating Duty cycle 400 mA 6 W 100 % 20 years Reliability values acc.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 14.4. Radio frequency approvals FCC ID: 2AJ58-13 IC: 22052-13 FCC/IC-Requirements This device complies with part 15 of the FCC Rules and with Industry Canada’s licence-exempt RSSs. Operation is subject to the following two conditions: 1) This device may not cause harmful interference, and 2) this device must accept any interference received, including interference that may cause undesired operation.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 14.5. Dimension drawing for safety switch CTP/CTA… 14.5.1. Dimension drawing for safety switch CTP… Version with plug connector M12 With escape release h 33 The actuator shaft for the escape release can be extended using extensions (max. 94 mm) 41,5 37,5 10 34 0,5 44 / 74 / 94 144 Auxiliary release 40 14 190 35 ∅ 5.3 (4x), 1.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 14.5.2. Dimension drawing for safety switch CTA… Version with plug connector M12 h 0,5 The actuator shaft for the escape release can be extended using extensions (max. 94 mm) 0,5 Basic position for escape release 14 44 / 74 / 9444 / 74 / 94 40 144 144 190 190 ∅ 5.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 14.5.3. Dimension drawing for connections and variants CTP/CTA … Plug connectors 2 x M12 Plug connector M12 Cable outlet C Cable outlet A 36 Cable outlet A 36 Cable outlet C With auxiliary key release With release, automatic return max.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 14.6. Technical data for actuator CTP/CTA‑… Parameter Value min. Housing material Fiber reinforced plastic -20 Degree of protection - Straight actuator 165497 (black) 1) 126015 (red) - Hinged actuator - Bent actuator Installation orientation Power supply - kg +55 °C IP65/IP67/IP69/IP69K Mechanical life Locking force Unit max. 0.03 … 0.06 (depending on version) Weight Ambient temperature typ.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 14.6.1. Dimension drawing for actuator CTP/CTA‑… Min. door radius [mm] Order no./item 9 8,5 2 2,5 Dimension drawing 0 R > 30 20 18 11 18 17 30 45 126015 A-C-H-G-SST-126015 R>1400 4,4 Straight actuators R>1200 Color: red Only for CTA 17 20 +4 -1 29,5 45 35 11 0,5 20 37,5 max.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP Dimension drawing Min. door radius [mm] R>300 1,25 37,5 8,5 16 2 Order no./item 4,4 122667 52 30 18 9 A‑C‑H‑W‑SST‑122667 45 12,45 R >1400 2,5 Bent actuators R >1200 bent, upward A-A 4,4 37,5 4,4 max.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP Dimension drawing Min. door radius [mm] Order no./item 33,5 8,5 18 1 30 45 0,5 3,25 122671 45 35 A‑C‑H‑RL‑LS‑122671 max. 28 X +4 -1 0,5 4 16 14 40 45 5,5 5,5 4 35 12 X = 53 mm (122671, 122672) X = 49 mm (122669, 122670) 40 122672 A‑C‑H‑RR‑LS‑122672 R>200 35 50 R>20 27 Hinged actuators 20 0 0,5 max.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP Tip! The actuator is supplied with screws that cannot easily be unscrewed with a tool. 15. Ordering information and accessories Tip! Suitable accessories, e.g. cables or assembly material, can be found at www.euchner.com. To order, enter the order number of your item in the search box and open the item view. Accessories that can be combined with the item are listed in Accessories. 16.
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP EU-Konformitätserklärung EU declaration of conformity Déclaration UE de conformité Dichiarazione di conformità UE Declaración UE de conformidad Original DE Translation EN Traduction FR Traduzione IT Traducción ES Die nachfolgend aufgeführten Produkte sind konform mit den Anforderungen der folgenden Richtlinien (falls zutreffend): The beneath listed products are in conformity with the requirements of the following directives (if applic
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP * Benannte Stelle Notified Body Organisme notifié Sede indicata Entidad citada 0340 DGUV Test Prüf- und Zertifizierungsstelle Elektrotechnik Fachbereich ETEM Gustav-Heinemann-Ufer 130 50968 Köln Genehmigung der umfassenden Qualitätssicherung (UQS) durch die benannte Stelle 0035 Approval of the full quality assurance system by the notified body 0035 Approbation du système d'assurance qualité complet par l'organisme notifié 0035 Approva
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP EN 2537377-02-07/21 (translation of the original operating instructions) 41
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP 42 (translation of the original operating instructions) 2537377-02-07/21
Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP EN 2537377-02-07/21 (translation of the original operating instructions) 43
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 70771 Leinfelden-Echterdingen Germany info@euchner.de www.euchner.com Edition: 2537377-02-07/21 Title: Operating Instructions Transponder-Coded Safety Switch CTP/CTA-L1/2-BP (translation of the original operating instructions) Copyright: © EUCHNER GmbH + Co. KG, 07/2021 Subject to technical modifications; no responsibility is accepted for the accuracy of this information.