Operating Instructions Non-Contact Safety Switch CES-I-BP-.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… Contents 1. About this document.............................................................................................. 4 1.1. Scope.............................................................................................................................................4 1.2. Target group...................................................................................................................................4 1.3.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 11. Technical data..................................................................................................... 18 11.1. 11.2. 11.3. Technical data for safety switch CES‑I‑BP‑C07‑…..............................................................................18 11.1.1. Radio frequency approvals.................................................................................................19 11.1.2. Typical system times...........
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 1. About this document 1.1. Scope These operating instructions apply to all CES-I-BP-.-C07-… from version 1.0.0. These operating instructions, the document “Safety information and maintenance” and any enclosed data sheet form the complete user information for your device. 1.2.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 2. Correct use Safety switches series CES‑I‑BP are interlocking devices without guard locking (type 4). The device meets the requirements according to EN IEC 60947‑5-3. Devices with unicode evaluation possess a high coding level, devices with multicode evaluation possess a low coding level.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 3. Description of the safety function Devices from this series feature the following safety functions: Monitoring of the guard position (interlocking device according to EN ISO 14119) ÌÌSafety function: -- The safety outputs are switched off when the guard is open (see chapter 6.3. Switching states on page 8). ÌÌSafety characteristics: category, Performance Level, PFHD (see chapter 11. Technical data on page 18). 4.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 6. Function The safety switch monitors the position of movable guards. The safety outputs are switched on/off when the actuator is moved into/out of the operating distance. The system consists of the following components: coded actuator (transponder) and switch. Whether the device learns the complete actuator code (unicode) or not (multicode) depends on the respective version.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 6.3. Switching states The detailed switching states for your switch can be found in the system status table. All safety outputs, monitoring outputs and display LEDs are described there.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 7. Mounting CAUTION Safety switches must not be bypassed (bridging of contacts), turned away, removed or otherwise rendered ineffective. ÌÌObserve EN ISO 14119:2013, section 7, for information about reducing the possibilities for bypassing an interlocking device. NOTICE Risk of damage to equipment and malfunctions as a result of incorrect installation. ÌÌSafety switches and actuators must not be used as an end stop.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 8. Electrical connection WARNING If there is a mistake, loss of the safety function due to incorrect connection. ÌÌTo ensure safety, both safety outputs must always be evaluated. ÌÌMonitoring outputs must not be used as safety outputs. ÌÌLay the connecting cables with protection to prevent the risk of short circuits. CAUTION Risk of damage to equipment or malfunctions as a result of incorrect connection.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 8.1. Notes about Important! ÌÌFor use and operation as per the requirements 1), a power supply with the feature "for use in class 2 circuits" must be used. Alternative solutions must comply with the following requirements: -- Electrically isolated power supply unit with a max. open-circuit voltage of 30 V DC and a limited current of max. 8 A.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 8.5. Connector assignment of safety switch CES‑I‑BP-…-SB +UB +UB 1 0V 0V 3 FO1A FO1A 2 FO1B FO1B 4 n.c. OD/C 5 M12, 5-pin 1 3 4 3 +UB 0V FO1A 2 4 FO1B 1 5 5 2 n.c.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 8.7. Connection WARNING If there is a mistake, loss of the safety function due to incorrect connection. ÌÌTo ensure safety, both safety outputs (FO1A and FO1B) must always be evaluated. Important! The example shows only an excerpt that is relevant for connection of the CES system. The example illustrated here does not show complete system planning. The user is responsible for safe integration into the overall system.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 8.8. Connection to a BR evaluation unit Important! ÌÌThe example shows only an excerpt that is relevant for connection of the CES system. The exam- ple illustrated here does not show complete system planning. The user is responsible for safe integration into the overall system. Detailed application examples can be found at www.euchner.com. Simply enter the order number of your switch in the search box.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 9. Setup 9.1. LED displays You will find a detailed description of the signal functions in chapter 10. System status table CES‑I‑BP-… on page 17. LED Color STATE green DIA red LEDs 9.2. Teach-in function for actuator (only for unicode evaluation) The actuator must be allocated to the safety switch using a teach-in function before the system forms a functional unit.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 9.3. Functional check WARNING Danger of fatal injury as a result of faults in installation and functional check. ÌÌBefore carrying out the functional check, make sure that there are no persons in the danger zone. ÌÌObserve the valid accident prevention regulations. 9.3.1. Electrical function test After installation and any fault, the safety function must be fully checked. Proceed as follows: 1. Switch on operating voltage.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 10. System status table CES‑I‑BP-… Teach-in operation (unicode only) X off off closed on on open off off 1x closed on on flashes quickly 2 Hz open off off 3x closed off on 1 Hz X off X X off X 1x Fault in the teach-in operation (only unicode), actuator removed from the operating distance prior to the end of the teach-in operation or faulty actuator detected.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 11. Technical data NOTICE If a data sheet is included with the product, the information on the data sheet applies. 11.1. Technical data for safety switch CES‑I‑BP‑C07‑… Parameter Value min. Housing material typ. Unit max. PBT plastic Dimensions 40 x 26.5 x 18 Weight (device without connecting cable) mm 0.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 11.1.1. Radio frequency approvals FCC ID: 2AJ58-12 IC: 22052-12 FCC/IC-Requirements This device complies with part 15 of the FCC Rules and with Industry Canada’s licence-exempt RSSs. Operation is subject to the following two conditions: 1) This device may not cause harmful interference, and 2) this device must accept any interference received, including interference that may cause undesired operation.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 11.1.2. Typical system times Please refer to the technical data for the exact values. Ready delay: After switch-on, the device carries out a self-test. The system is ready for operation only after this time. Switch-on time of safety outputs: The max. reaction time ton is the time from the moment when the actuator is in the operating distance to the moment when the safety outputs switch on.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 11.2. Technical data for actuator CES‑A‑BTN‑C07‑… Parameter Value min. Housing material typ. Unit max. PBT plastic Dimensions 42 x 25 x 18 Weight mm 0.03 Ambient temperature - 40 - Degree of protection IP65/IP67/IP69/IP69K Installation orientation Active face opposite read head Power supply kg + 70 °C Inductive via read head 11.2.1. Dimension drawing Active face NOTICE ÌÌTwo safety screws M4x20 included.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 11.2.2.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… Typical operating distance in installation orientation C -Z -22 2 Y 14 10 6 22 6 -2 10 1 41 -6 82 2 -10 -14 -Y 6 10 14 X X Z X 10 10 6 2 6 2 14 10 6 2 -2 -6 -10 -14 22 18 14 6 10 2 -2 -6 -10 -14 -18 -22 Z Y Switching distances for approach from x direction without center offset (z, y = 0)* Parameter Value Unit min. typ. max.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 11.3. Technical data for actuator CES-A-BDN-06‑158210 Parameter Value min. Housing material Unit typ. max. Macromelt PA-based plastic Dimensions 26 x ∅ 6 mm 0.005 Weight Ambient temperature - 40 Degree of protection acc. to EN IEC 60529 + 70 IP65/IP67/IP69/IP69K Installation orientation kg - °C 1) Active face opposite read head Power supply Inductive via read head 1) With flush installation 11.3.1.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 12. Ordering information and accessories Tip! Suitable accessories, e.g. cables or assembly material, can be found at www.euchner.com. To order, enter the order number of your item in the search box and open the item view. Accessories that can be combined with the item are listed in “Accessories.” 13. Inspection and service WARNING Loss of the safety function because of damage to the device.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… 15.
Operating Instructions Non-Contact Safety Switch CES-I-BP-.
Euchner GmbH + Co. KG Kohlhammerstraße 16 70771 Leinfelden-Echterdingen info@euchner.de www.euchner.com Edition: 2528734-02-08/19 Title: Operating Instructions Non-Contact Safety Switch CES-I-BP-.-C07-… (Translation of the original operating instructions) Copyright: © EUCHNER GmbH + Co. KG, 08/2019 Subject to technical modifications; no responsibility is accepted for the accuracy of this information.