Installation Manual

20'
- 01-
-03-
-02-
DESCRIPTION
MWOS
MWOS
Occupancy / Vacancy
Voltage ................................................................ 120/277VAC,50/60Hz
Motor .............................................................. 1/4HP-120VAC,50/60Hz
Adjustment Time Delay............................................... 15Sec to 30Mins
SPECIFICATIONS
Multi-Technology PIR/Ultrasonic
INSTALLATION INSTRUCTIONS
Light Level Adjustment.................................100 Lux --daylight(trimpot)
Operation Temperature................................................... 32° F--131° F
Incandescent....................................................800W-120VAC,50/60Hz
Load Requirments:
Walk-Through Mode.......................3 minutes if no activity after 30 sec.
Test Mode ..................... 15 sec. at initial power up or DIP switch reset
This Multi-Technology Wall Switch Sensor combine advanced passive
infrared (PIR) and ultrasonic technologies into one unit. The combined
technologies help to avoid false triggering.
Selectable operating modes
it on as long as either or
movement is detected
A "walk-through"
activity is detected
This sensor also
present, the sensor
Sensor Switch
(2-IN-1)
Ultrasonic Adjustment .........................
INSTALLATION
Turn off the circuit breaker before installation.
WARNING:
Do not exceed electrical ratings.
Line(Hot), Red lead to Load wire, White lead to Neutral wire, Green
4. Gently position wires in wall box, attach sensor switch to the box.
3. Mount device “TOP”up.
5. Restore power at circuit breaker or fuse, wait
7. Locate the adjustment trimpots on the control panel to perform test
Indoor use only.
Wiring Diagram:
Figure 1
2. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead to
6. Remove the small cover plate. (illustrated as Figure 3. )
8. Replace the small cover plate after testing and adjustment.
and adjustment.(illustrated as Figure 3 and 4. )
lead to Ground.
one
minute.
the area is occupied.
Minimum to Maximum (trimpot)
PIR Adjustment...............................................High or Low (DIP switch)
1. Make sure that the power has been turned OFF at the circuit breaker.
COVERAGE PATTERN
40'
Top View
10'
20'
10'
20'
5'
4'
Neutral
White
Hot
Black
Ground
Green
Load
Red
Neutral
Load
Figure 2
Figure 3
OFF OCC VAC
1
4
2
3
1
4
2
3
LIGHT
ULTRASONIC
OFF OCC VAC
Mode
OFF
Description
after set time delay.
Position
Left
Center
Right
Occupancy Mode:
Vacancy Mode: Manual On only,
automatic Off after set time delay.
React to the push-button
Manually toggles
Manually toggles
Automatic On, automatic Off
Band switch prescription.
On / Off the load.
On/Off the load.
OCC
VAC
None
Circuit is permanently opened.
Figure 4
(switched off)
Default position: Daylight (100% at position 4)
Adjustable: Daylight to 100Lux (Counter clockwise)
Ambient Light Level Adjustment Trimpot
Control Panel Cover
Mounting Yoke
ULTRASONIC
LIGHT
PIR Lens
Ultrasonic Cones
Detection LEDs
Red=PIR
Blue=Ultrasonic
PIR Coverage: 1200 ft
Ultrasonic Coverage: 400 ft
2
2
Ultrasonic Sensitivity Adjustment Trimpot
Default position: Center at 65%
Adjustable: 30% (Position 1) to 100% (Position 4)
Note: Turn toward right for greater room space.
Turn toward left to avoid false alert in smaller room and near
the door way or heat source.
ADJUSTMENT
White
Fluorescent.........................800VA-120VAC,1600VA-277VAC,50/60Hz
ON
OFF
1 2 3 4 5 6 7
allow the sensor to turn a load on, and hold
both technologies detect occupancy . After no
for the selected time delay, the lights switch off.
mode can turn lights off after only 3 minutes, if no
after 30 seconds following an occupancy detection.
contains a light level sensor. If adequate daylight is
holds the load OFF until light levels drop, even if

Summary of content (2 pages)