Technical Information Micropilot FMR51, FMR52 A F T Level radar Level measurement in liquids Application R Continuous, non-contact level measurement of liquids, pastes and slurries D Features FMR51: • Premium device for level measurements even under extreme conditions • Maximum measuring range: 40 m (131 ft); for version with enhanced dynamics: 70 m (230 ft) • Process connection: 1½" thread/Tri-Clamp/flange • Temp. range: –196 to +450 °C (–321 to +842 °F) • Pressure range: –1 to +160 bar (–14.
Table of contents Micropilot FMR51, FMR52 Table of contents Function and system design . . . . . . . . . . . . . . . . . . . . 6 Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Operating frequency . . . . . . . . . . . . . . . . . . .
Table of contents Micropilot FMR51, FMR52 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . 88 89 D R A F T Patents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Endress+Hauser V. 1, Rev.
Micropilot FMR51, FMR52 Important document information Document conventions Safety symbols Symbol Meaning DANGER DANGER! This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. A0011189-EN WARNING! WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. A0011190-EN CAUTION! This symbol alerts you to a dangerous situation.
Micropilot FMR51, FMR52 Function and system design Measuring principle The Micropilot is a "downward-looking" measuring system, operating based on the time-of-flight method (ToF). It measures the distance from the reference point (process connection) to the product surface. Radar impulses are emitted by an antenna, reflected off the product surface and received again by the radar system.
Micropilot FMR51, FMR52 Output The Micropilot is commissioned by entering an empty distance "E" (=zero), a full distance "F" (=span) and application parameters. The application parameters are automatically adapt into the instrument to the process conditions. For models with a current output, the factory adjustment for zero point "E" and span "F" is 4 mA and 20 mA. For digital outputs and the display module, the factory adjustment for zero point "E" and span "F" is 0 % and 100 %. A linearization with max.
Micropilot FMR51, FMR52 Input Measured variable The measured variable is the distance between the reference point and the product surface. Subject to the empty distance entered "E" the level is calculated. Alternatively, the level can be converted into other variables (volume, mass) by means of linearization (32 points).
Micropilot FMR51, FMR52 Device Storage tank T A0018833 Calm product surface (e.g. intermittent filling, filling from bottom, immersion tubes) Antenna size FMR51 40 mm (1½ in) 50 mm (2 in) FMR52 - 50 mm (2 in) B C A D B C D 4 (13) 5 (16) 8 (26) 8 (26) 10 (32) 15 (49) 15 (49) 25 (82) A0018858 8 (26) 12 (39) A 100 mm (4 in) 80 mm (3 in) - B C F 3 (9.
Micropilot FMR51, FMR52 Buffer tank T Device A0018835 Moving surfaces (e.g. continuous filling, from above, mixing jets) Antenna size 40 mm (1½ in) 50 mm (2 in) 80 mm (3 in) 100 mm (4 in) FMR52 - 50 mm (2 in) 80 mm (3 in) - B C D B C D 2 (6.6) F FMR51 A 5 (16) 5 (16) A B C D B C 10 (32) 15 (49) 15 (49) D 2.5 (8) 3 (9.9) 4 (13) 5 (16) 5 (16) A 5 (16) 7.5 (24) 7.5 (24) 10 (32) 10 (32) R A0018863 10 (32) 15 (49) 7.
Micropilot FMR51, FMR52 Process tank with agitator T Device A0018837 Turbulent surface. Single stage agitator (frot < 1 Hz) Antenna size 40 mm (1½ in) 50 mm (2 in) FMR52 - 50 mm (2 in) B C B D C 1 (3.2) 2 (6.6) 2 (6.6) 80 mm (3 in) 100 mm (4 in) 80 mm (3 in) - F FMR51 D B C D B C D 2.5 (8.2) A 3 (9.8) 3 (9.8) 5 (16) 5 (16) A0018867 5 (16) 7.
Micropilot FMR51, FMR52 Device Stilling well Bypass A0018840 T A0018842 Antenna size FMR51 40 to 100 mm ( 1½ ... 4 in) 40 to 100 mm ( 1½ ... 4 in) FMR52 50 to 80 mm ( 2 ... 3 in) 50 to 80 mm ( 2 ... 3 in) A, B, C, D C, D 20 (66) A F Antenna size A0018851 20 (66) A0018852 D R Measuring range [m (ft)] 12 V. 1, Rev.
Micropilot FMR51, FMR52 Operating frequency K-band (~ 26 GHz) Up to 8 Micropilot transmitters can be installed in the same tank because the transmitter pulses are statistically coded. Transmitting power Distance Average energy density in beam direction Standard version With "Advanced dynamics" application package 1) 1 m (3.3 ft) < 12 nW/cm2 < 64 nW/cm2 5 m (16 ft) < 0.4 nW/cm2 < 2.
Micropilot FMR51, FMR52 Output Output signal HART Signal coding FSK ±0.5 mA over current signal Data transmission rate 1 200 Bit/s Galvanic isolation Yes Signal coding Manchester Bus Powered (MBP) Data transmission rate 31.25 kBit/s, voltage mode Galvanic isolation Yes FOUNDATION Fieldbus (in preparation) Manchester Bus Powered (MBP) Data transmission rate 31.
Micropilot FMR51, FMR52 Depending on the interface, failure information is displayed as follows: • Current output (for HART devices) – Failsafe mode selectable (in accordance with NAMUR Recommendation NE 43): Minimum alarm: 3.6 mA Maximum alarm (= factory setting): 22 mA – Failsafe mode with user-selectable value: 3.59 to 22.
Micropilot FMR51, FMR52 Analog Input: • Level linearized • Distance • Terminal voltage • Electronic temperature • Absolute echo amplitude • Relative echo amplitude Output values Digital Input: • Extended diagnostic blocks • Status output PFS Block Digital Output: • Extended diagnostic block • Level limiter • Sensor block measurement on • Sensor block save history on • Status output • Identification & Maintenance Einfachste Geräteidentifizierung seitens des Leitsystems und des Typenschildes • Automatic
Micropilot FMR51, FMR52 Permanent entries 1 Client VCRs 0 Server VCRs 10 Source VCRs 43 Sink VCRs 0 Subscriber VCRs 43 Publisher VCRs 43 Slot time 4 Min. inter PDU delay 8 Max.
Micropilot FMR51, FMR52 PID Block Number of permanent blocks Number of instantiable blocks Execution time Functionality The PID block serves as proportional1 integralderivative controller and is used almost universally to do closed-loopcontrol in the field including cascade and feedforward. 1 25 ms standard Arithmetic Block This block is designed to permit simple 1 use of popular measurement math functions. The user does not have to know how to write equations.
Micropilot FMR51, FMR52 Power supply Terminal assignment 2-wire: 4-20mA HART 9 8 A el 4-2 0m ope A n + 5 6 1 - 2 mm 4 10 2 T 1 Sp a 711 re pa 08x rt xx 4... HA 20mA RT 2- w 4-2 ire le 0 v H A mA [21 RT ] + + – – F 4...20 mA 3 B 7 1 2 4 1-c han 5 nel ] A [16 + + – – ove + 1 4-2 2 0m rvo A ltag ep rote ctio 711 286 n 17 4...
Micropilot FMR51, FMR52 2-wire: 4-20mA HART, switch output 10 9 8 2- w 4-2 ire 0 HA mA [02 RT /03 ] PF S ope 7 + 1 2 T + + – 2 3 1 4...20 mA 4 6 10 4- ³250W Sp a 711 re pa 08x rt xx mm ++ 31 -42 3+ n 4... HA 20 mA RT A 5 B 3+ + 3 4-2 4 F 11 0m A/ 2-c han 4- [17 ] nel ove rvo + 1 4-2 2 FIE 0mA LD / BU ep S ro ltag tec 711 A – å4 19 2 3 4...
Micropilot FMR51, FMR52 2-wire: 4-20mA HART, 4-20mA 14 13 12 2- w 4-2 ire le 0 v 0m A n mm + 10 + 1 + 1 2 - T 11 Sp a 711 re pa 08x rt xx 4 ... HA 20mA RT ope 4 ... + 3 4 el 4-2 A A 20m HA mA [04 RT /05 ] – 4...20 mA 8 9 + + 2 – 4...20 mA 4 B + + 1 7 F 5 6 3 – + 3 4-2 4 - 4...20 mA 8 A 9 + 2 10 han [17 ] + 1 - 0m A/ 2-c nel 2 4FIE 20mA ove rvo LD / ltag B U ep S ro tec + tion 711 28 6 – 19 - 4...
Micropilot FMR51, FMR52 4-wire: 4-20mA HART (10.4 to 48 VDC) 13 12 11 Sp a 711 re pa 08x rt xx + 3 4 mm 9 n 8 10 10 L+ 1 L2 ope 4... HA 20 mA RT 4... 48 V 10. A = 2- w 4-2 ire 0 HA mA [08 RT ] ³250W 1 2 3 4...20 mA T + 7 6 4 5 Evaluation unit, e.g.
Micropilot FMR51, FMR52 4-wire: 4-20mA HART (90 to 253 VAC) 13 12 11 Sp a 711 re pa 08x rt xx + 3 4 mm 9 n 8 + ³250W 1 2 3 4...20 mA 4 T 10 10 L 1 N 2 ope 4... HA 20 mA RT 3V 9 0. ..25 A ~ 2- w 4-2 ire 0 HA mA [09 RT ] 7 6 5 Evaluation unit, e.g.
Micropilot FMR51, FMR52 PROFIBUS PA / FOUNDATION Fieldbus (in preparation) 5 4 2- 2 Sp a 7110 re pa 0283x4 rt x5x7 PIAE F /LFDF B ++ 31 -42 3+ en + 1 2- 10 4- mm A US F4IEwire -20L lev el mD ABU FA P IE/F S F B PFS [2 06/ LD U 07] 2 S op 3 T 1 B 6 + 3 4 F 3+ 4-2 41 2-c han [17 nel ] + 1 4-2 2 0m A/ ove rvo ltag FIE 0mA / LD BU S ep rote ctio å8 286 n 19 A0011341 Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus Without integrated overvoltage protection With i
Micropilot FMR51, FMR52 Connection examples for the switch output For HART devices, the switch output is available as an option. See product structure, feature 20: "Power Supply, Output", option B: "2-wire; 4-20mA HART, switch output" Devices with PROFIBUS PA and FOUNDATION Fieldbus always have a switch output.
Micropilot FMR51, FMR52 Device plug connectors For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected without opening the housing. Pin assignment of the M12 plug connector 4 1 3 + 2 – nc Pin Meaning 1 Signal + 2 not connected 3 Signal - 4 Ground A0011175 2 3 4 Meaning 1 Signal - 2 Signal + 3 Screen 4 Not connected D R A A0011176 F 1 Pin T Pin assignment of the 7/8" plug connector 26 V. 1, Rev.
Micropilot FMR51, FMR52 Supply voltage An external power supply is required. Various supply units can be ordered from Endress+Hauser: see "Accessories" section (® ä 86) 2-wire, 4-20mA HART, passive "Power Supply, Output" 1) "Approval" 2) Terminal voltage U at the device A: 2-wire; 4-20mA HART • • • • 10.4 to 35 V 3) Non-Ex Ex nA Ex ic CSA GP Maximum load R, depending on the supply voltage U0 at the supply unit R [?] 500 0 T 10.4 to 30 V 3) Ex ia / IS 10 10.
Micropilot FMR51, FMR52 "Power Supply, Output" 1) "Approval" 2) Terminal voltage U at the device 12 to 30 V 3) C: 2-wire; 4-20mA HART, 4-20mA any Maximum load R, depending on the supply voltage U0 at the supply unit R [?] 500 0 10 20 12 30 U0 [V] 23 A0017055 Feature 020 of the product structure Feature 010 of the product structure For ambient temperatures Ta £ -30 °C (-22 °F) a minimum voltage of 16 V is required for the satrtup of the device at the MIN error current (3.6 mA).
Micropilot FMR51, FMR52 4-wire, 4-20mA HART, active "Power supply; Output" 1) Terminal voltage Maximum load Rmax K: 4-wire 90-253VAC; 4-20mA HART 90 to 253 VAC (50 to 60 Hz), overvoltage category II 500 Ω L: 4-wire 10,4-48VDC; 4-20mA HART 10.
Micropilot FMR51, FMR52 FOUNDATION Fieldbus (in preparation) Device basic current 14 mA Error current FDE (Fault Disconnection Electronic) 0 mA Ui 17.5 V Ii 550 mA Pi 5.5 W Ci 5 nF Li 10 mH T FISCO (in preparation) Power supply failure • Configuration is retained in the HistoROM (EEPROM). • Error messages (incl. value of operated hours counter) are stored. Potential equalization No special measures for potential equalization are required.
Micropilot FMR51, FMR52 Overvoltage protection If the measuring device is used for level measurement in flammable liquids which requires the use of overvoltage protection according to DIN EN 60079-14, standard for test procedures 60060-1 (10 kA, pulse 8/20 ms), overvoltage protection has to be ensured by an integrated or external overvoltage protection module.
Micropilot FMR51, FMR52 Performance characteristics Reference operating conditions • • • • • Maximum measured error Typical data under reference operating conditions: DIN EN 61298-2, percentage values in relation to the span. Temperature = +24 °C (+75 °F) ±5 °C (±9 °F) Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.
R Micropilot FMR51, FMR52 3 (0.12) 0 -3 (-12) T D [mm] ([in]) 20 (0.79) -20 (-0.79) 0 D D A Measured value resolution 2 (6.6) D [m] ([ft]) A0019034 Maximum measured error in near-range applications; values for version with the "Advanced dynamics" application package F å 12 A Maximum measured error Distance from the reference point R Lower edge of the antenna Dead band according to EN61298-2: Tank height Sampling rate Step response time < 10 m (33 ft) ³ 3.6 s–1 < 0.
Micropilot FMR51, FMR52 the product surface. The following table illustrates this measured error for a few typical gases/vapors (with regard to distance; a positive value means that too large a distance is being measured): Air/ Nitrogen Hydrogen Water (saturated steam) Temperature Pressure °C °F 1 bar (14,5 psi) 10 bar (145 psi) 50 bar (725 psi) 100 bar (1450 psi) 160 bar (2320 psi) 20 68 0.00 % 0.22 % 1.2 % 2.4 % 3.89 % 200 392 –0.01 % 0.13 % 0.74 % 1.5 % 2.42 % 400 752 –0.
Micropilot FMR51, FMR52 Installation Installation conditions Mounting position 1 2 • Recommended distance A from wall to outer edge of nozzle: ~ 1/6 of tank diameter. Nevertheless the device should not be installed closer than 15 cm (5.91 in) to the tank wall. • Not in the center (2), as interference can cause signal loss. • Not above the fill stream (3). • It is recommended to us a weather protection cover (1) in order to protect the device from direct sun or rain.
Micropilot FMR51, FMR52 Reduction of interference echoes F T Metallic screens mounted at a slope spread the radar signal and can, therefore, reduce interference echoes. A0016890 A Measurement in a plastic vessel D R If the outer wall of the vessel is made of a non-conductive material (e.g. GRP), microwaves can also be reflected off interfering installations outside the signal beam (e.g. metallic pipes (1), ladders (2), grates (3), ...).
Micropilot FMR51, FMR52 Optimization options D R A F T • Antenna size The bigger the antenna, the smaller the beam angle a and the fewer interference echoes (® ä 38). • Mapping The measurement can be optimized by means of electronic suppression of interference echoes. • Antenna alignment Take into account the marker on the flange or threaded connection (® ä 41) (® ä 43) . • Stilling well A stilling well can be applied to avoid interferences (® ä 44).
Micropilot FMR51, FMR52 Beam angle D a W = 2 . D . tan _ 2 a å 13 T W A0016891 Relationship between beam angle a, distance D and beamwidth diameter W F The beam angle is defined as the angle a where the energy density of the radar waves reaches half the value of the maximum energy density (3-dB-width). Microwaves are also emitted outside the signal beam and can be reflected off interfering installations.
Micropilot FMR51, FMR52 2.85 m (9.4 ft) 1.58 m (5.2 ft) 12 m (39 ft) 3.80 m (12 ft) 2.1 m (6.9 ft) 15 m (49 ft) 4.75 m (16 ft) 2.63 m (8.6 ft) 20 m (66 ft) 6.34 m (21 ft) 3.50 m (11 ft) 25 m (82 ft) 7.92 m (26 ft) 4.37 m (14 ft) 30 m (98 ft) 9.50 m (31 ft) 5.25 m (17 ft) 35 m (115 ft) 11.09 m (36 ft) 6.12 m (20 ft) 40 m (131 ft) 12.67 m (42 ft) 7.00 m (23 ft) 45 m (148 ft) - 7.87 m (26 ft) 60 m (197 ft) - 10.50 m (34 ft) D R A F T 9 m (30 ft) Endress+Hauser V. 1, Rev.
Micropilot FMR51, FMR52 • In case of boiling surfaces, bubbling or tendency for foaming use FMR53 or FMR54. Depending on its consistence, foam can either absorb microwaves or reflect them off the foam surface. Measurement is possible under certain conditions. For FMR50, FMR51 and FMR52, the additional option "Advanced dynamics" is recommended in these cases (feature 540: "Application Package", option EM).
Micropilot FMR51, FMR52 Installation in vessel (free space) Horn antenna (FMR51) Alignment • Align the antenna vertically to the product surface. The maximum range may be reduced if the horn antenna is not vertically aligned. • A marking at the flange or the boss enables axial alignment of the antenna. This marking must be aligned towards the tank wall.
Micropilot FMR51, FMR52 Threaded connection • Tighten with the hexagonal nut only. • Tool : Hexagonal wrench 55 mm • Maximum permissible torque: 60 Nm (44 lbf ft) Mesurement from the outside through plastic walls • • • • If possible, use an antenna 100 mm (4"). The distance from the lower edge of the antenna to the tank ceiling should be about 100 mm (4 in). If possible, avoid mounting locations where condensation or build-up might occur.
Micropilot FMR51, FMR52 Horn antenna, flush mount (FMR52) Alignment • Align the antenna vertically to the product surface. The maximum range may be reduced if the horn antenna is not vertically aligned. • A marking at the flange or the boss enables axial alignment of the antenna. This marking must be aligned towards the tank wall.
Micropilot FMR51, FMR52 90 ° Installation in stilling well 1 A0016841 1 Installation in stilling well T å 16 Marking for antenna alignment D R A F • For horn antenna: Align the marking towards the slots of the stilling well. • Measurements can be performed through an open full bore ball valve without any problems. • After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. 44 V. 1, Rev.
Micropilot FMR51, FMR52 Recommendations for the stilling well • • • • • Metal (no enamel coating; plastic on request). Constant diameter. Diameter of stilling well not larger than antenna diameter. Weld seam as smooth as possible and on the same axis as the slots. Slots offset 180° (not 90°). Slot width or diameter of holes max. 1/10 of pipe diameter, de-burred. Length and number do not have any influence on the measurement. Select horn antenna as big as possible. For intermedaite sizes (e.g.
Micropilot FMR51, FMR52 Examples for the construction of stilling wells B A A C 1 2 A-A A 1 3 T 4 100% 100% 4 6 D D R 6 0% A B C D 1 2 3 4 5 6 7 46 ≤ 1 (0.04) F 150…500 (5.91...19.7) A ≤ 1 (0.04) 150…500 (5.91...19.7) 5 0% 7 mm (in) A0019009 Micropilot FMR50/FMR51: Horn 40mm(1½") Micropilot FMR50/FMR51/FMR52/FMR54: Horn 80mm(3") Stilling well with slots Full bore ball valve Marking for axial alignment Threaded connection e.g. welding neck flange DIN2633 Æ hole max.
Micropilot FMR51, FMR52 Installation in bypass 90 ° 2 1 å 17 Installation in bypass Marking for antenna alignment Tank connectors A0019446 F 1 2 T 90 ° 2 D R A • Alighn the marker perpendicular (90°) to the tank connectors. • Measurements can be performed through an open full bore ball valve without any problems. • After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Endress+Hauser V. 1, Rev.
Micropilot FMR51, FMR52 Recommendations for the bypass pipe D R A F T • Metal (no plastic or enamel coating). • Constant diameter. • Select horn antenna as big as possible. For intermediate sizes (e.g. 95 mm (3.5 in)) select next larger antenna and adapt it mechanically (for horn antennas). • At any transition (i.e. when using a ball valve or mending pipe segments), no gap may be created exceeding 1 mm (0.04 in). • In the area of the tank connections (~ ±20 cm (7.
Micropilot FMR51, FMR52 Example for the construction of a bypass A A-A A A ≤ 1 (0.04) 1 F 200 200 (7.87) (7.87) C T 2 100% 3 4 R A B 4 D 0% 200 200 (7.87) (7.87) 3 5 mm (in) A0019010 A B C 1 2 3 4 5 Endress+Hauser Micropilot FMR50/FMR51/FMR52/FMR54: Horn 80mm(3") Full bore ball valve Minimum distance to upper connection pipe: 400 mm (15,7 in) Marking for axial alignment e.g.
Micropilot FMR51, FMR52 Vessels with heat insulation 1 2 A0019142 D R A F T If process temperatures are high, the device must be included in normal tank insulation to prevent the electronics heating up as a result of heat radiation or convection. The insulation may not exceed beyond the neck of the housing. 50 V. 1, Rev.
Micropilot FMR51, FMR52 Environment Ambient temperature range Measuring device –40 to +80 °C (–40 to +176 °F); –50 °C (–58 °F) with manufacturer declaration on request Local display –20 to +70 °C (–4 to +158 °F), the readability of the display may be impaired at temperatures outside the temperature range. When operating the device in the open with strong sunlight: • Mount the device in a shady position. • Avoid direct sunlight, especially in warmer regions.
Micropilot FMR51, FMR52 FMR51 P1 Seal: • Viton GLT, –40 to 150 °C (–40 to 302 °F) • Kalrez, –20 to 150 °C (–4 to 302 °F) Ta P2 P3 Housing: GT19 (Plastics PBT) Temperature unit: °C (°F) Tp P4 P5 A0019351 P1 P2 P3 P4 P5 P6 Ta Tp Ta Tp Ta Tp Ta Tp Ta Tp Ta A -40 (-40) 80 (176) 80 (176) 80 (176) 150 (302) 56 (133) 150 (302) -40 (-40) -40 (-40) -40 (-40) - - B Switch output not used -40 (-40) 76 (169) 76 (169) 76 (169) 150 (302) 56 (133) 150 (302) -40 (-40) -40 (-
Micropilot FMR51, FMR52 FMR51 Seal: Graphite, –40 to 250 °C (–40 to 482 °F) Housing: GT18 (316 L) Temperature unit: °C (°F) P1 Ta P2 P3 Tp P4 P5 A0019351 P1 P2 P3 P4 P5 P6 Ta Tp Ta Tp Ta Tp Ta Tp Ta Tp Ta A -40 (-40) 81 (178) 81 (178) 81 (178) 250 (482) 63 (145) 250 (482) -40 (-40) -40 (-40) -40 (-40) - - B Switch output not used -40 (-40) 82 (180) 82 (180) 82 (180) 250 (482) 64 (147) 250 (482) -40 (-40) -40 (-40) -40 (-40) - - B Switch output used -40 (-40
Micropilot FMR51, FMR52 FMR51 Seal: Graphite, –40 to 250 °C (–40 to 482 °F) Housing: GT20 (Alu, coated) Temperature unit: °C (°F) P1 Ta P2 P3 Tp P4 P5 A0019351 P1 P2 P3 P4 P5 P6 Ta Tp Ta Tp Ta Tp Ta Tp Ta Tp Ta A -40 (-40) 81 (178) 81 (178) 81 (178) 250 (482) 67 (153) 250 (482) -40 (-40) -40 (-40) -40 (-40) - - B Switch output not used -40 (-40) 82 (180) 82 (180) 82 (180) 250 (482) 68 (154) 250 (482) -40 (-40) -40 (-40) -40 (-40) - - B Switch output used -4
Micropilot FMR51, FMR52 FMR51 Seal: Graphite, –196 to 450 °C (–321 to 842 °F) Housing: GT19 (Plastics PBT) Temperature unit: °C (°F) P1 Ta P2 P3 Tp P4 P6 P5 A0019344 P1 P2 P3 P4 P5 P6 Ta Tp Ta Tp Ta Tp Ta Tp Ta Tp Ta A -196 (-321) 80 (176) 80 (176) 80 (176) 450 (842) -29 (-20) 450 (842) -40 (-40) -40 (-40) -40 (-40) -196 (-321) 9 (48) B Switch output not used -196 (-321) 76 (169) 76 (169) 76 (169) 450 (842) -29 (-20) 450 (842) -40 (-40) -40 (-40) -40 (-40) -19
Micropilot FMR51, FMR52 FMR52 Antenna: Horn 50mm/2" Housing: GT18 (316 L) Temperature unit: °C (°F) P1 Ta P2 P3 Tp P4 P5 A0019351 P1 P2 P3 P4 P5 P6 Ta Tp Ta Tp Ta Tp Ta Tp Ta Tp Ta A -40 (-40) 81 (178) 81 (178) 81 (178) 200 (392) 61 (142) 200 (392) -40 (-40) -40 (-40) -40 (-40) - - B Switch output not used -40 (-40) 82 (180) 82 (180) 82 (180) 200 (392) 61 (142) 200 (392) -40 (-40) -40 (-40) -40 (-40) - - B Switch output used -40 (-40) 77 (171) 77 (171) 7
Micropilot FMR51, FMR52 FMR52 Antenna: Horn 50mm/2" Housing: GT20 (Alu, coated) Temperature unit: °C (°F) P1 Ta P2 P3 Tp P4 P5 A0019351 P1 P2 P3 P4 P5 P6 Ta Tp Ta Tp Ta Tp Ta Tp Ta Tp Ta A -40 (-40) 81 (178) 81 (178) 81 (178) 200 (392) 65 (149) 200 (392) -40 (-40) -40 (-40) -40 (-40) - - B Switch output not used -40 (-40) 82 (180) 82 (180) 82 (180) 200 (392) 65 (149 200 (392) -40 (-40) -40 (-40) -40 (-40) - - B Switch output used -40 (-40) 77 (171) 77 (17
Micropilot FMR51, FMR52 FMR52 Antenna: Horn 80mm/2" Housing: GT19 (Plastics PBT) Temperature unit: °C (°F) P1 Ta P2 P3 Tp P4 P5 A0019351 P1 P2 P3 P4 P5 P6 Ta Tp Ta Tp Ta Tp Ta Tp Ta Tp Ta A -40 (-40) 80 (176) 80 (176) 80 (176) 200 (392) 36 (97) 200 (392) -40 (-40) -40 (-40) -40 (-40) - - B Switch output not used -40 (-40) 76 (169) 76 (169) 76 (169) 200 (392) 36 (97) 200 (392) -40 (-40) -40 (-40) -40 (-40) - - B Switch output used -40 (-40) 60 (140) 60 (14
Micropilot FMR51, FMR52 Geometric height according to IEC61010-1 Ed.3 Degree of protection Up to 2 000 m (6 600 ft) above MSL. Can be expanded to 3 000 m (9 800 ft) above MSL by application of an overvoltage protection, e.g. HAW562 or HAW569. • With closed housing tested according to: – IP68, NEMA6P (24 h at 1.83 m under water surface) – For plastic housing with transparent cover (display module): IP68 (24 h at 1.
Micropilot FMR51, FMR52 Process Sensor Seal 1) Process temperature range FMR51 Viton GLT –40 to +150 °C (–40 to 302 °F) Kalrez –20 to +150 °C (–4 to 302 °F) Graphite, -40 ... 250°C / -40 ... 482°F –40 to +250 °C (–40 to 482 °F) Graphite, -196...450°C / -321...842°F –196 to +450 °C (–321 to 842 °F) - –40 to +200 °C (–40 to 392 °F) FMR52 1) Process pressure range Feature 090 of the product structure Sensor Process pressure range FMR51 prel = –1 to 40 bar (–14.
Micropilot FMR51, FMR52 Mechanical construction Dimensions Dimensions of the electronics housing R100 98 (3.86)* 90 (3.54) 141.9 (5.59) 144 (5.67) ø108.5 (ø4.27) T ø10 å 18 Housing GT18 (316L); Dimensions in mm (in) 115.25 (4.54) 3.5 (ø4 .07 ) 78 (3.07) A0011666 F *This measure is valid for devices with integrated overvoltage protection. R100 99.5 (3.92)* 90 (3.54) å 19 163 (6.42) 134.5 (5.3) R ø106 (ø4.17) ø10 A 6 (ø 4.1 7) 78 (3.
Micropilot FMR51, FMR52 Dimensions FMR51 (process connection/antenna) B D C 55 26 (1.02) T L ød øD øA ød 100(3.94) 67.5 (2.66) L 5 (0.2) 5 (0.2) L 26 (1.02) R b 63 (2.48) 67.5 (2.66) 55 5 (0.2) A ød C 62 D b L 26 (1.02) A 100(3.94) 5 (0.2) R L D A B C D R b 63 (2.48) R 55 A0017753 115.4 (4.54) B 121.4 (4.78) A F Threaded connection Clamp adapter 2"/3" Flange version Threaded connection with antenna extension 100 mm (3.
Micropilot FMR51, FMR52 65 (2.56) A 3 (0.12) L b R ød øD 55 63 (2.48) b F L b 26 (1.02) 47 53...453 (2.09...17.8) (1.85) R T C 67.5 (2.66) B 140.1 (5.52) D ød øD A L2 ø27 (1.06) ød øD A0017756 Flange version, coated Version flange with antenna extension > 100 mm (3.94 in) to 500 mm (19.7 in) Version threaded connection with antenna extension > 100 mm (3.94 in) to 500 mm (19.
Micropilot FMR51, FMR52 Dimension b Version PN100 ⌀D DN50 DN80 DN100 DN150 - - 36 mm (1.42 in) - - - ⌀265 mm (10.4 in) - DN50 DN80 DN100 DN150 16 mm (0.63 in) 18 mm (0.71 in) 18 mm (0.71 in) 22 mm (0.87 in) ⌀155 mm (6.1 in) ⌀185 mm (7.28 in) ⌀210 mm (8.27 in) ⌀280 mm (11 in) - - 44 mm (1.73 in) - - - ⌀270 mm (10.6 in) - Dimension b Version 10 K ⌀D b 63 K ⌀D Flanges according to ANSI B16.5 b Version 150 lbs ⌀D b 300 lbs ⌀D 2" 3" 4" 19.1 mm (0.75 in) 23.
Micropilot FMR51, FMR52 Dimensions FMR52 (process connection/antenna) B C b 94(3.7) 4 (0.16) 5 (0.2) 95 (3.74) 2.6 (0.1) 92.6(3.65) A øb T 121(4.76) 4 (0.16) ø75 (2.95) øc ød F øb 28.6 (1.13) ø75 (2.95) 28.6 (1.13) F 2.6 (0.1) 119.6 (4.71) 5 (0.2) 123 (4.84) R øa ø48 (1.89) øc ød b E D ø75 (2.95) 13.8 (0.54) ø48 (1.89) 28.6 (1.13) øa 13.8 (0.54) ø48 (1.89) 13.8 (0.
Micropilot FMR51, FMR52 Flanges according to ANSI B16.5 Dimension Version 2" b ⌀c 150 lbs ⌀d 3" 4" 6" 19.1 mm (0.75 in) 23.9 mm (0.94 in) 23.9 mm (0.94 in) 25.4 mm (1 in) ⌀92 mm (3.62 in) ⌀127 mm (5 in) ⌀158 mm (6.22 in) ⌀212 mm (8.35 in) ⌀152.4 mm (6 in) ⌀190.5 mm (7.5 in) ⌀228.6 mm (9 in) ⌀279.4 mm (11 in) DN50 DN80 DN100 DN150 16 mm (0.63 in) 18 mm (0.71 in) 18 mm (0.71 in) 22 mm (0.87 in) ⌀96 mm (3.78 in) ⌀127 mm (5 in) ⌀151 mm (5.94 in) ⌀212 mm (8.35 in) ⌀155 mm (6.
Micropilot FMR51, FMR52 Housing GT18 - stainless steel, corrosion-resistant No. Part: material No. Part: material 2.2 Cover of the terminal compartment • Cover: 316L (CF-3M, 1.4404) • Cover seal: EPDM 6 Dummy plug: 316L (1.4404) 7 Pressure relief stopper: 316L (1.4404) 3 Cover lock • Screw: A4 • Clamp: 316L (1.4404) 8 Ground terminal • Screw: A4 • Spring washer: A4 • Clamp: 316L (1.4404) • Holder: 316L (1.4404) 4 Turn housing • Screw: A4-70 • Clamp: 316L (1.
Micropilot FMR51, FMR52 Antenna and process connection FMR51 A B 1 C D 7 7 3 3 7 2 2 F G 6 3 H 3 6 5 4 F E T 2 2 A B C D E F G H A 2 A0018961 R Version with screw-in adapter XT version with threaded connection XT version with flange HT version with flange Version with flange and antenna extension > 100 mm (3.94 in) to 500 mm (19.7 in) Version with threaded connection and antenna extension > 100 mm (3.94 in) to 500 mm (19.
Micropilot FMR51, FMR52 Pos. Part Material 5 Extension process adapter 316L (1.4404) Locking washer 6 Process adapter 316L (1.4404) 7 Housing adapter 316L (1.4404) Temperature reduction (XT) 316L (1.4404) Intermediate adapter (HT) 316L (1.4404) Process adapter 316L (1.4404) B 1 1 2 2 4 4 Dairy coupling Clamp adapter Flange version C 1 3 4 F A B C A T FMR52 A0018951 Part Material 1 Adapter 304 (1.4301) 2 Process connection 316L (1.4435) 3 Flange 316L (1.4404/1.
Micropilot FMR51, FMR52 Weather protection cover 1 3.1 3.2 2.1 2.2 2.2 2.1 4 5.1 T 5.2 4 6 A0015473 Nr. Part: material 1 Nr. Part: material Protection cover: 304 (1.4301) 2.1 Washer: A2 4 Bracket: 304 (1.4301) 5.1 Cheese head screw: A2-70 5.2 Nut: A2 6 Ground terminal • Screw: A4 • Spring washer: A4 • Clamp: 316L (1.4404) • Holder: 316L (1.4404) A 2.2 Cheese head screw: A4-70 3.1 Washer: A2 F Weather protection cover D R 3.2 Tightening screw: 304 (1.4301) 70 V. 1, Rev.
Micropilot FMR51, FMR52 Operability Operating concept Operator-oriented menu structure for user-specific tasks • Commissioning • Operation • Diagnostics • Expert level Quick and safe commissioning • Guided menus ("Make-it-run" wizards) for applications • Menu guidance with brief explanations of the individual parameter functions Reliable operation • Local operation in different languages (see product structure, feature "Additional Operation Language") • Standardized operation at the device and in the oper
Micropilot FMR51, FMR52 Operation with remote display and operating module FHX50 3 2 1 A0013137 å 21 1 2 3 Housing of the remote display and operating module FHX50 Display and operating module SD02, push buttons; cover must be removed Display and operating module SD03, optical keys; can be operated through the glass of the cover (in preparation) Via HART protocol T Remote operation FHX50 operating options F 9 6 1 å 22 4 5 7 A0013764 Options for remote operation via HART protocol PLC (progr
Micropilot FMR51, FMR52 Via PROFIBUS PA protocol (in preparation) 2 3 1 PROFIBUS DP ENDRESS + HAUSER PROFIBUS PA T 4 T 4 5 4 A0015775 F Segment coupler Computer with Profiboard/Proficard and operating tool (e.g. FieldCare) PLC (Progrommable Logic Controller) Transmitter Additional functions (valves etc.) D R A 1 2 3 4 5 Endress+Hauser V. 1, Rev.
Micropilot FMR51, FMR52 Via FOUNDATION Fieldbus (in preparation) BT FF-HSE T IN 1 FF-H1 BT PS LD 2 SB 4 3 BT ENDRESS + HAUSER F % PS 1 2 å 23 + E BT A0017188 FOUNDATION Fieldbus system architecture with associated components Industrial network High Speed Ethernet R IN FFHSE FFH1 LD PS SB BT 1 2 3 4 A FF-H1 – FOUNDATION Fieldbus-H1 D Linking Device FF-HSE/FF-H1 Bus Power Supply Safety Barrier Bus Terminator FFblue Bluetooth modem Field Xpert SFX100 FieldCare NI-FF interface c
Micropilot FMR51, FMR52 Via service interface (CDI) 3 – + T E 2 1 A0014019 F Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface) Commubox FXA291 Computer with "FieldCare" operating tool D R A 1 2 3 Endress+Hauser V. 1, Rev.
Micropilot FMR51, FMR52 Integration in tank gauging system The Endress+Hauser Tank Side Monitor NRF590 provides integrated communications for sites with multiple tanks, each with one or more sensors on the tank, such as radar, spot or average temperature, capacitive probe for water detection and/or pressure sensors. Multiple protocols out of the Tank Side Monitor guarantee connectivity to nearly any of the existing industry standard tank gauging protocols. Optional connectivity of analog 4...
Micropilot FMR51, FMR52 System integration via Fieldgate Vendor Managed Inventory By using Fieldgates to interrogate tank or silo levels remotely, suppliers of raw materials can provide their regular customers with information about the current supplies at any time and, for example, account for them in their own production planning. For their part, the Fieldgates monitor the configured level limits and, if required, automatically activate the next supply.
Micropilot FMR51, FMR52 Certificates and approvals CE mark The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. C-Tick symbol The measuring system meets the EMC requirements of the "Australian Communications and Media Authority (ACMA)".
Micropilot FMR51, FMR52 For the use of the devices outside of closed bins or tanks, the following has to be observed: 1. The installation has to be done by trained personnel. 2. The antenna of the device has to be mounted on a fixed place and vertically to the bottom. 3. The mounting place has to be in a distance of at least 4 km to the mentioned astronomical stations or an appropriate permission has to be issued by the national authority.
Micropilot FMR51, FMR52 Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
Micropilot FMR51, FMR52 Ordering information Ordering information Detailed ordering information is available from the following sources: • In the Product Configurator on the Endress+Hauser website: www.endress.com ® Select country ® Instruments ® Select device ® Product page function: Configure this product • From your Endress+Hauser Sales Center: www.endress.
Micropilot FMR51, FMR52 If the option IJ "Customized parametrization HART", IK "Customized parametrization PA" or IL "Customized parametrization FF" has been selected in feature 570 "Service", customer specific presettings can be selected for the following parameters: Communication Selection list / range of values Setup ® Distance unit • HART • PA • FF • in • mm Setup ® Empty calibration • HART • PA • FF 0 to 70 m (0 to 230 ft) Setup ® Full calibration • HART • PA • FF 0 to 70 m (0 to 230 ft) Se
Micropilot FMR51, FMR52 Accessories Device-specific accessories Accessory Description T 222 (8.74) Weather protection cover mm (in) F A0015466 273.8 (10.8) 164 (6.46) 298.5 (11.8) 255.1 (10) 55° b 35° 155 A (6.1 ° 65 ) a mm (in) A0015472 37.8 mm (1.49 in) 54 mm (2.13 in) R a b D The weather protection cover can be ordered together with the device (product structure, feature 620 "Accessory Enclosed", option PB "Weather Protection Cover").
Micropilot FMR51, FMR52 Accessory Description A0019128 F • Material: – Plastics PBT – 316L (in preparation) • Suitable for the display modules: – SD02 (push buttons) – SD03 (touch control) (in preparation) • Connection cable: – Cable with M12 plug; supplied with the FHX50; up to 30 m (98 ft) – Customer supplied standard cable; up to 60 m (196 ft) T Remote display FHX50 A • If the remote display is to be used, the Micropilot must be ordered in the version "Prepared for display FHX50" (feature 030, o
Micropilot FMR51, FMR52 Accessory Description ød Horn protection for 100 mm (4 in) horn antenna 450 (17.72) T ø116 (4.57) ³ DN150 mm (in) F A0019144 For details please refer to the Mounting Instructions SD01084F. Danger of explosion Avoid electrostatic charging of the horn protection. Accessory Description A Communication-specific accessories Commubox FXA195 HART For intrinsically safe HART communication with FieldCare via the USB interface.
Micropilot FMR51, FMR52 Accessory Description Fieldgate FXA320 Gateway for remote monitoring of connected 4-20mA measuring devices via web browser. For details refer to Technical Information TI00025S and Operating Instructions BA00053S Accessory Description Fieldgate FXA520 Gateway for remote diagnosis and parametrization of connected HART measuring devices via web browser.
Micropilot FMR51, FMR52 Documentation The following document types are available: • On the CD supplied with the device • In the Download Area of the Endress+Hauser Internet site: www.endress.
Micropilot FMR51, FMR52 Available for Safety Instructions HART Safety Instructions PROFIBUS FOUNDATION Fieldbus B4 ATEX:II 1/2 G Ex ia IIC T6-T1 Ga/Gb ATEX: II 1/2 G Ex d [ia] IIC T6-T1 Ga/Gb • FMR51 • FMR52 XA00681F XA00689F IA IECEx: Ex ia IIC T6-T1 Ga • FMR51 • FMR52 XA00677F XA00685F IB IECEx: Ex ia IIC T6-T1 Ga/Gb • FMR51 • FMR52 XA00677F XA00685F IC IECEx: Ex d [ia] IIC T6-T1 Ga/Gb • FMR51 • FMR52 XA00680F XA00688F ID IECEx: Ex ic [ia Ga] IIC T6-T1 Ga/Gb/Gc • FMR51 • FMR52 X
Micropilot FMR51, FMR52 PROFIBUSÒ Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany FOUNDATIONTM Fieldbus Registered trademark of the Fieldbus Foundation, Austin, Texas, USA KALREZÒ, VITONÒ Registered trademark of DuPont Performance Elastomers L.L.C., Wilmington, USA TEFLONÒ Registered trademark of E.I. DuPont de Nemours & Co., Wilmington, USA TRI CLAMPÒ Registered trademark of Alfa Laval Inc.