Operating Instructions Micropilot M FMR250 Level-Radar 6 BA284F/00/en/08.04 Nr. 52025089 Valid as of software version: V 01.01.00 (amplifier) V 01.01.
Micropilot M FMR250 with HART/4...20 mA Brief overview For quick and simple commissioning: Safety Instructions Explanation of the warning symbols You can find special instructions at the appropriate position in the chapter in question. The positions are indicated with the icons Warning #, Caution " and Note !. → Page 6 ff. Æ Installation The steps for installing the device and installation conditions (e.g. dimensions) can be found here. → Page 11 ff.
Micropilot M FMR250 with HART/4...20 mA Brief operating instructions KA 235F/00/a2/08.04 52025245 Contrast: 000 measured value - + - E 00 basic setup 01 safety settings + + 004 process cond. 003 medium cond. - liquid - dome ceiling - horizontal cyl. - bypass … - unknown - standard - DC: <1.9 - calm - DC: 1.9 … 4 surface - DC: 4 … 10 - add. - DC: >10 agitator … - solid 00A vessel / silo 00B medium cond. - unknown - unknown - metal silo - DC: 1.6...1.9 - concrete - DC: 1.9 …2.5 - DC: 2.
Micropilot M FMR250 with HART/4...
Micropilot M FMR250 with HART/4...20 mA Table of contents Table of contents 1 Safety instructions . . . . . . . . . . . . . . . . 6 1.1 1.2 1.3 1.4 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation, commissioning and operation . . . . . . . . Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . Notes on safety conventions and symbols . . . . . . . . . 2 Identification . . . . . . . . . . . . . . . . . . . . 8 2.1 2.2 2.3 2.4 Device designation . .
Safety instructions Micropilot M FMR250 with HART/4...20 mA 1 Safety instructions 1.1 Designated use The Micropilot M FMR250 is a compact level radar for the continuous, contactless measurement of predominantly solids. The device can also be freely mounted outside closed metal vessels because of its operating frequency of about 26 GHz and a maximum radiated pulsed energy of 1mW (average power output 1 µW). Operation is completely harmless to humans and animals. 1.
Micropilot M FMR250 with HART/4...20 mA 1.4 Safety instructions Notes on safety conventions and symbols In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin.
Identification Micropilot M FMR250 with HART/4...20 mA 2 Identification 2.1 Device designation 2.1.1 Nameplate The following technical data are given on the instrument nameplate: L00-FMR2xxxx-18-00-00-en-001 Fig. 1: 2.1.
Micropilot M FMR250 with HART/4...20 mA Identification Ordering structure Micropilot M FMR250 (continued) 30 Antenna seal; Temperature: E Y FKM Viton GLT; -40...200°C/-40...392 °F Special version 40 Antenna extension: 1 2 3 9 50 Not selected 250mm/10" 450mm/18" Special version Process connection: GGJ GNJ X3J XCJ XEJ 60 – Threaded boss – Thread DIN2999 R1-1/2, 316L Thread ANSI NPT1-1/2, 316L – Universal-Flanges – UNI flange DN200/8"/200A, 316L max PN1/14.
Identification Micropilot M FMR250 with HART/4...20 mA 2.
Micropilot M FMR250 with HART/4...20 mA # Installation 3 Installation 3.
Installation Micropilot M FMR250 with HART/4...20 mA 3.3 Installation conditions 3.3.1 Dimensions Housing dimensions 65 max. 110 78 150 Ø 129 ENDRESS+HAUSER F12 housing (Aluminium) 85 L00-F12xxxx-06-00-00-en-001 max. 100 65 94 78 162 Ø 129 ENDRESS+HAUSER T12 housing (Aluminium) 85 L00-T12xxxx-06-00-00-en-001 104 150 Ø 129 40 max.
Micropilot M FMR250 with HART/4...
Installation Micropilot M FMR250 with HART/4...20 mA E+H UNI flange The number of bolts has sometimes been reduced. The bolt-holes have been enlarged for adaption of dimensions, therefore, the flange needs to be properly aligned to the counterflange before the bolts are tightened. 8 A-A E+H UNI flange DN200 compatible with: - DN200 PN10/16, - ANSI 8" 150 lbs, - JIS 10K 200A M80x1.
Micropilot M FMR250 with HART/4...20 mA 3.3.2 Installation Engineering hints Orientation • Recommended distance (1) wall – outer edge of nozzle: ~1/6 of vessel diameter. However, the device should not, under any circumstances, be mounted less than 20 cm/ 8“ from the vessel wall. • Not in the centre (3), interference can cause signal loss. • Not above the fill stream (4). • It is recommended to use a weather protection cover (2) in order to protect the transmitter from direct sun or rain.
Installation Micropilot M FMR250 with HART/4...20 mA Beam angle The beam angle is defined as the angle a where the energy density of the radar waves reaches half the value of the maximum energy density (3dB-width). Microwaves are also emitted outside the signal beam and can be reflected off interfering installations.
Micropilot M FMR250 with HART/4...20 mA Installation Measuring conditions • The measuring range begins, where the beam hits the vessel bottom. Particularly with dish bottoms or conical outlets the level cannot be detected below this point. • In case of media with a low dielectric constant (groups A and B), the vessel bottom can be visible through the medium at low levels. In order to guarantee the required accuracy in these cases, it is recommended to position the zero-point at a distance C =50...
Installation Micropilot M FMR250 with HART/4...20 mA Measuring range The usable measuring range depends on the size of the antenna, the reflectivity of the medium, the mounting location and eventual interference reflections. The maximum configurable range is 70 m (229 ft) for Micropilot M FMR250. To achieve an optimised Signal strength it is recommended to use an antenna with as large as possible diameter (DN200/8" parabolic antenna, DN100/4" horn). Reduction of the max.
Micropilot M FMR250 with HART/4...20 mA Installation 3.4 Installation instructions 3.4.1 Mounting kit For the mounting , you will require the following tool: • The tool for flange mounting or • a key AF60 for threaded boss and • 4 mm/0.1" Allen wrench for turning the housing. 3.4.
Installation Micropilot M FMR250 with HART/4...20 mA Standard installation FMR250 with horn antenna • Observe installation instructions on Page 15. • Marker is aligned towards vessel wall. • The marker is always exactly in the middle between two bolt-holes in the flange. • After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. • The horn antenna should protrude from the nozzle.
Micropilot M FMR250 with HART/4...20 mA Installation Standard installation FMR250 with parabolic antenna • Observe installation instructions on Page 15. • Marker is aligned towards vessel wall. • The marker is always exactly in the middle between two bolt-holes in the flange. • After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. • Ideally the parabolic antenna should protrude from the nozzle (1).
Installation Micropilot M FMR250 with HART/4...
Micropilot M FMR250 with HART/4...20 mA Installation FMR250 with top target positioner Using top target positioner it is possible to tilt the antenna axis by up to 15° in all directions. The top target positioner is used for the optimum alignment of the radar beam with the bulk solids surface. ±15° ±15° L00-FMR250xx-17-00-00-de-008 Align antenna axis: 1. Loosen screws. 2. Align antenna axis (here this is possible up to max. ±15° in all directions). 3. Tighten screws.
Installation Micropilot M FMR250 with HART/4...20 mA 3.4.3 Turn housing After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: • Undo the fixing screws (1) • Turn the housing (2) in the required direction • Tighten up the fixing screws (1) F12 / F23 housing T12 housing 2 2 1 1 allen key 4 mm/0.1” L00-FMR2xxxx-17-00-00-en-010 3.
Micropilot M FMR250 with HART/4...20 mA Wiring 4 Wiring 4.1 Quick wiring guide Wiring in F12/F23 housing " ● Switch off power supply before connecting up the device. ● 1 Connect Equipotential bonding to transmitter ground terminal before connecting up the device. Tighten the locking screw: It forms the connection between the antenna and the housing ground potential. IP65 1 xxxxxx x= U 16 ... 30 V DC 4...20 mA TA >70°C : t >85°C Dat./Insp.: if modification see sep. label 3 PN max.
Wiring Micropilot M FMR250 with HART/4...20 mA Wiring in T12 housing ● The power supply must be identical to the data on the nameplate (1). ● Switch off power supply before connecting up the device. Caution! ● 1 Connect Equipotential bonding to transmitter ground terminal before connecting up the device. IP65 1 xxxxxx x= Tighten the locking screw: It forms the connection between the antenna and the housing ground potential. U 16 ... 30 V DC 4...20 mA TA >70°C : t >85°C Dat./Insp.
Micropilot M FMR250 with HART/4...20 mA 4.2 Wiring Connecting the measuring unit Terminal compartment Three housings are available: • Aluminium housing F12 with additionally sealed terminal compartment for: – standard, – EEx ia, – EEx ia with dust Ex. • Aluminium housing T12 with separate terminal compartment for: – standard, – EEx d, – EEx ia (with overvoltage protection), – dust Ex. • 316L housing F23 for: – standard, – EEx ia, – EEx ia with dust Ex.
Wiring Micropilot M FMR250 with HART/4...20 mA Supply voltage The following values are the voltages across the terminals directly at the instrument: Communication Terminal voltage Current consumption minimal maximal 4 mA 16 V 36 V 20 mA 7.5 V 36 V 4 mA 16 V 30 V 20 mA 7.5 V 30 V 4 mA 16 V 30 V 20 mA 11 V 30 V 4 mA 16 V 30 V 20 mA 11 V 30 V HART standard EEx ia EEx d dust Ex Fixed current, adjustable e.g.
Micropilot M FMR250 with HART/4...20 mA 4.2.1 Wiring HART connection with E+H RMA422 / RN221N - ToF Tool FieldTool Package FXA193 4...20 mA ENDRESS + HAUSER RMA 422 RMA422 RN221N 1 2 3 4 - ToF Tool FieldTool Package - FieldCare dsdmdm df das. asdas fa asas la. FMP40: LIC0001 ONLINE 1 GROUP SELECT 2 PV HELP 8.7 m SAVE Page Up Bksp Delete Page On #%& ABC 2 1 Copy GHI Paste JKL 4 PQRS DEF 3 Hot Key MNO 5 6 Insert + Hot Key TUV W XY Z 7 8 9 ,()‘ _<> +*/ .
Wiring Micropilot M FMR250 with HART/4...20 mA 4.3 Recommended connection 4.3.1 Equipotential bonding Connect the equipotential bonding to the external ground terminal of the transmitter. 4.3.2 " Wiring screened cable Caution! In Ex applications, the screen must only be grounded on the sensor side. Further safety instructions are given in the separate documentation for applications in explosion hazardous areas. 4.
Micropilot M FMR250 with HART/4...20 mA Operation 5 Operation 5.1 Quick operation guide ENDRESS + HAUSER – + X E F 3x X O basic setup safety settings F X X media type O liquids solids F linearisation extended ... S F tank shape O dome ceiling horizontal cyl >3 s medium property O bypass S S ... F flat ceiling X vessel / silo O unknown F metal silo S Group Selection unknown DC: < 1.9 bin / bunker dome stockpile DC: 4 ...
Operation Micropilot M FMR250 with HART/4...20 mA 5.1.1 General structure of the operating menu The operating menu is made up of two levels: • Function groups (00, 01, 03, …, 0C, 0D): The individual operating options of the instrument are split up roughly into different function groups. The function groups that are available include, e.g.: "basic setup", "safety settings", "output", "display", etc. • Functions (001, 002, 003, …, 0D8, 0D9): Each function group consists of one or more functions.
Micropilot M FMR250 with HART/4...20 mA 5.2 Operation Display and operating elements END RES II R IP T LCD (liquid crystal display) Maulburg range U 16...36 max. 4...20 20 m V mA DC 65 A >70°C : t >85°C Made in Germany Order MICR S+HA OPIL Ser.-NoCode: OT USE .: Messbe Measur reich ing ENDRESS + HAUSER – + E Symbols 3 keys L00-FMxxxxxx-07-00-00-en-001 Fig.
Operation Micropilot M FMR250 with HART/4...20 mA 5.2.2 Display symbols The following table describes the symbols that appear on the liquid crystal display: Sybmol Meaning ALARM_SYMBOL This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a warning. LOCK_SYMBOL This lock symbol appears when the instrument is locked,i.e. if no input is possible. COM_SYMBOL This communication symbol appears when a data transmission via e.g.
Micropilot M FMR250 with HART/4...20 mA Operation 5.3 Local operation 5.3.1 Locking of the configuration mode The Micropilot can be protected in two ways against unauthorised changing of instrument data, numerical values or factory settings: "unlock parameter" (0A4): A value <> 100 (e.g. 99) must be entered in "unlock parameter" (0A4) in the "diagnostics" (0A) function group. The lock is shown on the display by the symbol and can be released again either via the display or by communication.
Operation Micropilot M FMR250 with HART/4...20 mA 5.3.2 Unlocking of configuration mode If an attempt is made to change parameters on display when the instrument is locked, the user is automatically requested to unlock the instrument: unlock parameter" (0A4): By entering the unlock parameter (on the display or via communication) 100 = for HART devices the Micropilot is released for operation.
Micropilot M FMR250 with HART/4...20 mA 5.3.3 " Operation Factory settings (Reset) Caution! A reset sets the instrument back to the factory settings. This can lead to an impairment of the measurement. Generally, you should perform a basic setup again following a reset.
Operation Micropilot M FMR250 with HART/4...20 mA 5.4 Display and acknowledging error messages Type of error Errors that occur during commissioning or measuring are displayed immediately on the local display. If two or more system or process errors occur, the error with the highest priority is the one shown on the display. The measuring system distinguishes between two types of error: • A (Alarm): Instrument goes into a defined state (e.g. MAX 22 mA) Indicated by a constant symbol.
Micropilot M FMR250 with HART/4...20 mA 5.5 Operation HART communication Apart from local operation, you can also parameterise the measuring instrument and view measured values by means of a HART protocol. There are two options available for operation: • Operation via the universal handheld operating unit, the HART Communicator DXR375. • Operation via the Personal Computer (PC) using the operating program (e.g. ToF Tool or Commuwin II) (For connections, see Page 29).
Operation Micropilot M FMR250 with HART/4...
Micropilot M FMR250 with HART/4...20 mA Commissioning 6 Commissioning 6.1 Function check Make sure that all final checks have been completed before you start up your measuring point: • Checklist “Post installation check” (see Page 24). • Checklist “Post connection check” (see Page 30). 6.
Commissioning Micropilot M FMR250 with HART/4...20 mA 6.
Micropilot M FMR250 with HART/4...20 mA Commissioning The basic setup is sufficient for successful commissioning in most applications. Complex measuring operations necessitate additional functions that the user can use to customise the Micropilot as necessary to suit his specific requirements. The functions available to do this are described in detail in the BA291F.
Commissioning Micropilot M FMR250 with HART/4...20 mA 6.4 Basic Setup with the VU331 Function "measured value" (000) ENDRESS + HAUSER – + E ⇒ This function displays the current measured value in the selected unit (see "customer unit" (042) function). The number of digits after decimal point can be selected in the "no.of decimals" (095) function. 6.4.
Micropilot M FMR250 with HART/4...20 mA Commissioning Function "tank shape" (002), liquids only ENDRESS + HAUSER – + E ⇒ This function is used to select the tank shape.
Commissioning Micropilot M FMR250 with HART/4...20 mA Function "medium property" (003), liquids only ENDRESS + HAUSER – + E ⇒ This function is used to select the dielectric constant. Selection: • unknown • DC: < 1.9 • DC: 1.9 ... 4 • DC: 4 ... 10 • DC: > 10 1) 46 Product class DC (εr) A 1,4...1,9 B 1,9...4 non-conducting liquids, e.g. benzene, oil, toluene, … C 4...10 e.g.
Micropilot M FMR250 with HART/4...20 mA Commissioning Function "process cond." (004) , liquids only ENDRESS + HAUSER – + E ⇒ This function is used to select the process conditions. Selection: • standard • calm surface • turb. surface • agitator • fast change • test:no filter standard calm surface For all applications that do not fit into any of the following groups.
Commissioning Micropilot M FMR250 with HART/4...20 mA Function "vessel / silo" (00A), solids only ENDRESS + HAUSER – + E ⇒ This function is used to select the vessel / silo. Selection: • unknown • metal silo • concrete silo • bin / bunker • dome • stockpile • conveyor belt Function "medium property" (00B), solids only ENDRESS + HAUSER – + E ⇒ This function is used to select the dielectric constant. Selection: • unknown • DC: 1.6 ... 1.9 • DC: 1.9 ... 2.5 • DC: 2.5 ... 4 • DC: 4 ...
Micropilot M FMR250 with HART/4...20 mA Commissioning Function "process cond." (00C), solids only ENDRESS + HAUSER – + E ⇒ This function is used to select the process conditions.
Commissioning Micropilot M FMR250 with HART/4...20 mA Function "empty calibr." (005) ENDRESS + HAUSER – + E ⇒ This function is used to enter the distance from the flange (reference point of the measurement) to the minimum level (=zero). L00-FMR2xxxx-14-00-06-en-008 " 50 Caution! For dish bottoms or conical outlets, the zero point should be no lower than the point at which the radar beam hits the bottom of the vessel.
Micropilot M FMR250 with HART/4...20 mA Commissioning Function "full calibr." (006) ENDRESS + HAUSER – + E ⇒ This function is used to enter the distance from the minimum level to the maximum level (=span). L00-FMR2xxxx-14-00-06-en-009 In principle, it is possible to measure up to the tip of the antenna. However, due to considerations regarding corrosion and build-up, the end of the measuring range should not be chosen any closer than 50 mm (2") to the tip of the antenna.
Commissioning Micropilot M FMR250 with HART/4...20 mA Function "pipe diameter" (007) ENDRESS + HAUSER – + E ⇒ This function is used to enter the pipe diameter of the stilling well or bypass pipe. L00-FMR2xxxx-14-00-00-en-011 Microwaves propagate more slowly in pipes than in free space. This effect depends on the inside diameter of the pipe and is automatically taken into account by the Micropilot. It is only necessary to enter the pipe diameter for applications in a bypass or stilling well.
Micropilot M FMR250 with HART/4...20 mA Commissioning Function "check distance" (051) ENDRESS + HAUSER – + E ⇒ This function triggers the mapping of interference echoes. To do so, the measured distance must be compared with the actual distance to the product surface. The following options are available for selection: Selection: • distance = ok • dist. too small • dist. too big • dist.
Commissioning Micropilot M FMR250 with HART/4...20 mA Function "range of mapping" (052) ENDRESS + HAUSER – + E ⇒ This function displays the suggested range of mapping. The reference point is always the reference point of the measurement (see Page 42 ff.). This value can be edited by the operator. For manual mapping, the default value is 0 m.
Micropilot M FMR250 with HART/4...20 mA Commissioning display (008) ENDRESS + HAUSER – + E ⇒ The distance measured from the reference point to the product surface and the level calculated with the aid of the empty adjustment are displayed. Check whether the values correspond to the actual level or the actual distance. The following cases can occur: • Distance correct − level correct → continue with the next function, "check distance" (051) • Distance correct − level incorrect → Check "empty calibr.
Commissioning Micropilot M FMR250 with HART/4...20 mA 6.4.2 Envelope curve with VU331 After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E) function group) is recommended. Function "plot settings" (0E1) ENDRESS + HAUSER – + E ⇒ Select which information will be displayed in the LCD: • envelope curve • env.curve+FAC (on FAC see BA291F) • env.curve+cust.map (i.e.
Micropilot M FMR250 with HART/4...20 mA Commissioning Function "envelope curve display" (0E3) The envelope curve is displayed in this function. You can use it to obtain the following information: full calibr. quality of evaluated echo evaluated echo is marked empty calibr.
Commissioning Micropilot M FMR250 with HART/4...20 mA Move mode Then press F to switch to Move mode. Either • O shifts the curve to the right. • S shifts the curve to the left. or S O is displayed. L00-FMxxxxxx-07-00-00-yy-008 Vertical Zoom mode Press F once more to switch to Vertical Zoom mode. options. • O increases the vertical scale. • S reduces the vertical scale. The display icon shows the current zoom factor ( S is displayed. You now have the following to ).
Micropilot M FMR250 with HART/4...20 mA 6.5 Commissioning Basic Setup with the ToF Tool To carry out the basic setup with the ToF Tool operating program, proceed as follows: • Start the ToF Tool operating program and establish a connection • Select the "basic setup" function group in the navigation window The following display appears on the screen: Basic Setup step 1/4: • Status image • Enter the measuring point description (TAG number).
Commissioning Micropilot M FMR250 with HART/4...20 mA Basic Setup step 2/4: • Enter the application parameters: – vessel / silo (for a description, see Page 48) – medium property (for a description, see Page 48) – process cond. (for a description, see Page 49) L00-FMR250xx-20-00-00-en-011 Basic Setup step 3/4: If "metal silo", "concrete silo", "..." is selected in the "vessel / silo" function, the following display appears on the screen: • empty calibr. (for a description, see Page 50) • full calibr.
Micropilot M FMR250 with HART/4...20 mA Commissioning If "conveyor belt" is selected in the "vessel / silo" function, the following display appears on the screen: • empty calibr. (for a description, see Page 50) • full calibr.
Commissioning Micropilot M FMR250 with HART/4...20 mA 6.5.1 Envelope curve with the ToF Tool After the basic setup, an evaluation of the measurement using the envelope curve is recommended. L00-FMR250xx-20-00-00-en-008 ! Note! If the level of echo is very weak or there is a heavy interference echo, an orientation of the Micropilot can help optimise the measurement (increase of the useful echo/reduction of the interference echo) (see "Orientation of the Micropilot" on Page 73).
Micropilot M FMR250 with HART/4...20 mA 7 Maintenance Maintenance The Micropilot M measuring instrument requires no special maintenance. Exterior cleaning When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the surface of the housing and the seals. Replacing seals The process seals of the sensors must be replaced periodically, particularly if molded seals (aseptic construction) are used.
Accessories Micropilot M FMR250 with HART/4...20 mA 8 Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Micropilot M. Weather protection cover A Weather protection cover made of stainless steel is available for outdoor mounting (order code: 543199-0001). The shipment includes the protective cover and tension clamp. F12 / F23 / T12 housing EN D M RE Orde ICR SS r OP +HA Se Code r.-No ILO US : .
Micropilot M FMR250 with HART/4...20 mA Accessories Remote display FHX40 Dimensions Micropilot M Levelflex M Prosonic M Wall-mounting (without mounting bracket) Pipe-mounting (mounting bracket and plate supplied optionally, s. product structure) 8, 5 W Separate housing FHX 40 (IP 65) EN DR ES S+H AU SE ES S 0°C : +H 65 t >8 5°C AU SE H R Maulburg Me Messberei asuri ch ng ran ge U 16 ma x. 20 4...20...36 m mAV DC T A >7 0°C : t >8 5°C 160 DR A >7 180 Orde r Co Se r.-N de: o.
Trouble-shooting Micropilot M FMR250 with HART/4...20 mA 9 Trouble-shooting 9.1 Trouble-shooting instructions Micropilot M FMR 250 -Trouble Shooting Check voltage and compare it with the specifications on the nameplate. Instrument does not respond Not ok Connect the correct voltage Yes Instrument works? Ready No ok Check the polarity of the voltage.
Micropilot M FMR250 with HART/4...20 mA 9.2 Endress + Hauser Trouble-shooting System error messages Code Description Possible cause Remedy A102 checksum error general reset & new calibr.
Trouble-shooting 68 Micropilot M FMR250 with HART/4...20 mA Code Description Possible cause Remedy E641 no usable echo channel 1 check calibr. echo lost due to application conditions or built up on antenna check installation; optimize orientation of antenna; clean antenna (cf.
Micropilot M FMR250 with HART/4...20 mA 9.3 Application errors in liquids Output Possible cause Remedy A warning or alarm Depending on the configuration has occurred. See table of error messages (see Page 67) 1. See table of error messages (see Page 67) Measured value (00) is incorrect Measured distance (008) OK? D m/ft (008) Error Trouble-shooting F m/ft yes → 100% 1. Check empty calibr. (005) and full calibr. (006). 2. Check linearisation: → level/ullage (040) → max.
Trouble-shooting Error If the surface is not calm (e.g. filling, emptying, agitator running), the measured value jumps sporadically to a higher level Micropilot M FMR250 with HART/4...20 mA Output 100% actual Possible cause Remedy Signal is weakened by the rough surface – the interference echoes are sometimes stronger 1. Carry out tank mapping → basic setup 2. Set the process cond. (004) to "turb. surface" or "agitator" 3. Increase the output damping (058) expected 4.
Micropilot M FMR250 with HART/4...20 mA 9.4 Application errors in solids Output Possible cause Remedy A warning or alarm Depending on the configuration has occurred. See table of error messages (see Page 67) 1. See table of error messages (see Page 67) Measured value (00) is incorrect Measured distance (008) OK? D m/ft (008) Error Trouble-shooting F m/ft yes → 100% 1. Check empty calibr. (005) and full calibr. (006). 2. Check linearisation: → level/ullage (040) → max.
Trouble-shooting Error During filling or emptying the measured value jumps sporadically to a higher level Micropilot M FMR250 with HART/4...20 mA Output 100% actual expected Possible cause Remedy Signal is weakened (e.g. by fluidisation of the surface, extreme dust formation) – the interference echoes are sometimes stronger 1. Carry out tank mapping → basic setup 2. Increase the output damping (058) 3. Optimise the orientation (see Page 73) 4.
Micropilot M FMR250 with HART/4...20 mA 9.5 Trouble-shooting Orientation of the Micropilot For orientation a marker is found on the flange or threaded boss of the Micropilot.
Trouble-shooting Micropilot M FMR250 with HART/4...20 mA L00-FMRxxxxx-19-00-00-en-004 Fig. 7: Vessel empty, no interference echo Fig. 8: Vessel empty, interference echo obtained L00-FMRxxxxx-19-00-00-en-005 7. Fix the flange or threaded boss in this position. If necessary, replace the seal. 8. Carry out tank mapping, see Page 53. Top target positioner - optional Using top target positioner it is possible to tilt the antenna axis by up to 15° in all directions.
Micropilot M FMR250 with HART/4...20 mA 9.6 ! Trouble-shooting Spare parts Note! You can order spare parts directly from your E+H service organization by giving the serial number which is printed on the measuring transducer nameplate (see Page 8s. Seite 8 ff.). The corresponding spare part number also appears on each spare part. Installation instructions are given on the instruction card that is also delivered.
Trouble-shooting Micropilot M FMR250 with HART/4...
Micropilot M FMR250 with HART/4...20 mA Trouble-shooting Spare parts Micropilot M FMR250, T12 housing with separate wiring and electronics compartment 25 65 35 10 65 11 IP T A >7 0°C 30 65 : t >85° C Made in Germany Mea er surineich g ra nge U 16 max . 20 4...2 ...36 m 0m VD A C Maulburg EN D MIC RES Ord er RO S+H Ser Cod PIL AU e: .-N o.
Trouble-shooting Micropilot M FMR250 with HART/4...
Micropilot M FMR250 with HART/4...20 mA 65 Sealing kit 535720-9010 Endress + Hauser Trouble-shooting consists of: 2 x gasket Pg13.5 FA 2 x O-ring 17.0x2.0 EPDM 1 x O-ring 49.21x3.53 EPDM 2 x O-ring 17.12x2.62 FKM 1 x O-ring 113.9x3.63 EPDM 1 x O-ring 72.0x3.
Trouble-shooting Micropilot M FMR250 with HART/4...
Micropilot M FMR250 with HART/4...20 mA 9.7 Trouble-shooting Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present. This is especially important if the fluid is dangerous to health, e.g. corrosive, poisonous, carcinogenic, radioactive, etc.
Technical data Measured variable Micropilot M FMR250 with HART/4...20 mA 10 Technical data 10.1 Additional technical data 10.1.1 Input The measured variable is the distance between a reference point and a reflective surface (i.e. medium surface). The level is calculated based on the tank height entered. The level can be converted into other units (volume, mass) by means of a linearization. 10.1.
Micropilot M FMR250 with HART/4...20 mA Influence of ambiente temperature Technical data The measurements are carried out in accordance with EN 61298-3: • digital output (HART): – FMR250 average TK: 5 mm/10 K, max. 15 mm over the entire temperature range -40 °C...+80 °C • Current output (additional error, in reference to the span of 16 mA): – Zero point (4 mA) average TK: 0,03 %/10 K, max. 0,45 % over the entire temperature range -40 °C...+80 °C – Span (20 mA) average TK: 0,09 %/10 K, max.
Technical data Micropilot M FMR250 with HART/4...20 mA 10.1.6 Dielectric constant Seal / Temperature E Pressure -1 ...16 bar (...232 psi), E+H UNI flange: -1...1 bar (...14.5 psi) Antenna cone PEEK Wetted parts PEEK, seal and 316 L/1.4404/1.4435 Optional: top target positioner ±15°, seal: FKM Viton GLT FKM Viton GLT, -40 °C...+200 °C (-40 °F...+392 °F) • in free space: εr ≥ 1.6 10.1.
Micropilot M FMR250 with HART/4...20 mA Control Drawings Correlation of Control Drawings (ZD) to the instrument: Instrument Certificate Explosion protection Output Communication FMR250 S FM IS A, B, K HART A, B, D ZD168F/00/en T FM XP A, B, K HART C ZD169F/00/en U CSA IS A, B, K HART A, B, D ZD170F/00/en V CSA XP A, B, K HART C ZD171F/00/en 10.1.
Appendix basic setup Micropilot M FMR250 with HART/4...20 mA 00 media type 001 11 Appendix 11.1 Operating menu HART (display modul), ToF Tool tank shape 002 dome ceiling horizontal cyl. bypass stilling well flat ceiling sphere liquid solid vessel / silo 01 output on alarm 003 00A medium cond. 00B 010 outp. echo loss 00C output on alarm 011 005 empty calibr. full calibr. 006 enter value 005 delay time full calibr.
Micropilot M FMR250 with HART/4...20 mA dist./meas.value 007 015 from blocking distance default: 0.1m D and L are displayed 046 max. scale 046 dist./meas.value 008 range of mapping 052 start mapping 053 off on input of mapping range 056 is displayed simulation 008 D and L are displayed in safety dist. 016 diameter vessel ackn. alarm 017 no yes overspill protection 018 standard german WHG 047 D and L are displayed echo quality dist./meas.value dist. unknown dist.
Appendix Micropilot M FMR250 with HART/4...20 mA 11.2 ! 88 Description of functions Note! A detailed description of the function groups, functions and parameters is given in the documentation BA291F/00/en "Description of the instrument functions of the Micropilot M" on the enclosed CD-ROM.
Micropilot M FMR250 with HART/4...20 mA Appendix 11.3 Function and system design 11.3.1 Function (Measuring principle) The Micropilot is a "downward-looking" measuring system, operating based on the time-of-flight method. It measures the distance from the reference point (process connection) to the product surface. Radar impulses are emitted by an antenna, reflected off the product surface and received again by the radar system.
Appendix Micropilot M FMR250 with HART/4...20 mA Output The Micropilot is commissioned by entering an empty distance E (=zero), a full distance F (=span) and an application parameter. The application parameter automatically adapts the instrument to the process cond.. The data points “E” and “F” correspond with 4mA and 20mA for instruments with current output. They correspond with 0 % and 100 % for digital outputs and the display module. A linearization with max.
Micropilot M FMR250 with HART/4...20 mA Appendix On-site operation • with display and operating module VU331, • with a Personal Computer, FXA193 and the operating software "ToF Tool - FieldTool Package" respectively "FieldCare". The ToF Tool is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle (radar, ultrasonic, guided micro-impulse). It assists with commissioning, securing data, signal analysis and documentation of the measuring point.
Micropilot M FMR250 with HART/4...20 mA Index Index A accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . air purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . antenna size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . application errors in liquids. . . . . . . . . . . . . . . . . . . . . . . . application errors in solids . . . . . . .
Micropilot M FMR250 with HART/4...20 mA Index S safety distance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 service interface FXA193. . . . . . . . . . . . . . . . . . . . . . . . . . 64 software history. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 spare parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 stilling well . . . . . . . . . . . .
Micropilot M FMR250 with HART/4...
"CAJ?P?RGML MD AMLR?KGL?RGML $EAR CUSTOMER "ECAUSE OF LEGAL DETERMINATIONS AND FOR THE SAFETY OF OUR EMPLOYEES AND OPERATING EQUIPMENT WE NEED THIS $ECLARATION OF CONTAMINATION WITH YOUR SIGNATURE BEFORE YOUR ORDER CAN BE HANDLED 0LEASE INCLUDE THE COMPLETELY FILLED IN DECLARATION WITH THE DEVICE AND THE SHIPPING DOCUMENTS IN ANY CASE !DD ALSO SAFETY SHEETS AND OR SPECIFIC HANDLING INSTRUCTIONS IF NECESSARY 4YPE OF DEVICE SENSOR 3ERIAL NO -EDIUM CONCENTRATION 4EMPERATURE 0RESSURE #
www.endress.com/worldwide BA284F/00/en/08.04 52025089 CCS/FM+SGML 6.