500 Series 510 Surge Protective Device Installation, Operation and Maintenance Manual
Surge Protective Devices EMERSON NETWORK POWER SURGE PROTECTIVE DEVICE INSTALLATION, OPERATION AND MAINTENANCE MANUAL TABLE OF CONTENTS UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Handling Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .
Surge Protective Devices LOCATION CONSIDERATIONS UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection 1. Inspect the shipping crate(s) for damage or signs of mishandling before unpacking the unit. 2. Remove any securing bands and cardboard packing and inspect the unit for any obvious shipping damages. 3. If any damage as a result of shipping is observed, immediately file a claim with the shipping agency and forward a copy to your local Emerson Network Power Surge Protection Sales Representative.
Surge Protective Devices MODEL NUMBER CONFIGURATION Model #: _ _ _ _ _ _ _ _ _ _ _ _ _ 1 2 3 4 (1-3) Series 510 = Modular/Non-Modular MOV (4-5) Configuration & Voltage See Chart Below (6-7) Surge Rating Per Mode 06 = 65kA 08 = 80kA 10 = 100kA 12 = 125kA 16 = 160kA 20 = 200kA 25 = 250kA Installation, Operation and Maintenance Manual 5 6 7 8 9 (8) Modes of Protection A = All Modes of Protection B = L-N & N-G E = L-L F = L-N G = L-G (9) Connection Type N = Wiring terminals/Lugs R = Rotary Disconnec
Surge Protective Devices ELECTRICAL CONNECTIONS All electrical connections should be installed by a qualified (licensed) electrician only. All wiring must comply with the National Electrical Code (NEC) and applicable local codes. VERIFY THAT ALL POWER CIRCUITS ARE DE-ENERGIZED AND LOCKED OUT BEFORE MAKING ELECTRICAL CONNECTIONS.
Surge Protective Devices PARALLEL CONNECTIONS Typical Parallel Connections (without Internal Rotary Disconnect) Typical Parallel Connections (with Internal Rotary Disconnect) Neutral Phases Ground Neutral Phases Ground To Protected Loads To Protected Loads Neutral Phase(s) Surge Protective Device Neutral Transient Ground Protected Panel Wire should be less than 5 feet and straight as possible Rotary Disconnect Safety Ground Surge Protective Device Transient Ground Protected Panel Groundi
Surge Protective Devices INSTALLATION INSTRUCTIONS The Emerson Network Power 510 Series Surge Protective Devices (SPDs) are high quality, high energy surge current diversion systems designed to protect sensitive equipment from damaging transient voltage surges. Proper installation is required for maximum system performance. 6. Apply power. The surge protector is fully operational when the GREEN LED s on the modules (when applicable), and the front of the enclosure are illuminated.
Surge Protective Devices NEMA 12 (Metal) Enclosure Option SUGGESTED CIRCUIT BREAKER AND WIRE SIZE Allowable Range Surge Rating Per Mode 60kA-80kA 100kA-160kA 200kA-250kA Factory Suggested Size Connection Wire Size Circuit Breaker Size With Disconnect Without Disconnect With Disconnect Without Disconnect 40A-150A 15A-100A #8-1/O #14-#2 Circuit Breaker Size 40 Amp 40 Amp 100 Amp Connection Wire Size #8 AWG #8 AWG #2 AWG DIMENSIONAL INFORMATION Surge Rating Per Mode 60kA-80kA 100kA-160kA 200kA-2
Surge Protective Devices NEMA 1 Panelboard Extension Enclosure Option SUGGESTED CIRCUIT BREAKER AND WIRE SIZE Overcurrent Protection (Circuit Breaker): Allowable Range: 15A - 100A Suggested Size: 30A Connection Wire: Allowable Range: #14 - #2 Suggested Size: #10 Weight: 30 lb. (13.6 kg) Summary Alarm Contacts Connection shall be with #18 22 AWG. Form C contacts are rated 5 amps at 250 VAC max.
Surge Protective Devices MONITORING FEATURES Servicing The Emerson Network Power 510 Series comes with a ten year warranty. For servicing assistance, contact your local Sales Representative or Emerson Network Power, Surge Protection at 800-288-6169 or 607-721-8840. External Status Indicators (Standard) These indicators provide a summary of the status of the surge SPD module. For normal conditions, the green OK LED is illuminated and the red Service LED is extinguished.
Surge Protective Devices Installation, Operation and Maintenance Manual 10 IO-70103 Rev 0, 1/2013
Surge Protective Devices Emerson Network Power 100 Emerson Parkway Binghamton, NY 13905 800 288 6169 Phone (U.S. & Canada Only) 607 721 8840 (Outside U.S.) 607 722 8713 FAX United States of America Emerson Network Power European Headquarters Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX Emerson Network Power Asia Pacific 29/F, The Orient Square Building F. Ortigas Jr.