EIO0000001145 03/2012 Emerson Process Management ROC Plus SIO Driver EIO0000001145.01 03/2012 www.schneider-electric.
EIO0000001145 03/2012
Table of Contents Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Chapter 1 ROC Plus SIO Driver. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 7 9 System Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Target Machine Serial Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable Diagrams. . . . . . . . . . . . . . . . . . .
EIO0000001145 03/2012
Safety Information § Important Information NOTICE Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
About the Book At a Glance Document Scope This manual describes the device driver communication settings in the Vijeo Designer screen editing software. Vijeo Designer enables you to design Magelis target machines that communicate with PLCs, drives, field devices, and other equipment. For more information about Vijeo Designer and Magelis target machines, please refer to Vijeo Designer user documentation. Validity Note The data and illustrations found in this book are not binding.
Product Related Information WARNING LOSS OF CONTROL z z z z The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop. Separate or redundant control paths must be provided for critical control functions. System control paths may include communication links.
ROC Plus SIO Driver EIO0000001145 03/2012 ROC Plus SIO Driver 1 Subject of this Chapter This chapter explains Emerson Process Management’s ROC Plus SIO driver.
ROC Plus SIO Driver System Structure Overview The following table describes the basic system setup for connecting Emerson Process Management’s external devices to the Vijeo Designer target machines. Note: z All Vijeo Designer target machines support the ROC Plus SIO driver, except for the XBTGT1100 and XBTGT1130. Connection You can use the COM1 port to connect the target machine with the external device. Series CPU Link I/F Comm.
ROC Plus SIO Driver Series CPU Link I/F Comm.
ROC Plus SIO Driver Target Machine Serial Interface Use the following serial interface diagrams in combination with the cable diagrams in Section 3 to wire connections between the target machine and external equipment. Magelis XBTGK, XBTGC2000, XBTGH2000, and XBTGT2000 Series or higher All XBTGK and XBTGT2000 Series and higher target machines have two COM ports: COM1 and COM2. The XBTGC2000 Series has one COM port: COM1. XBTGH2000 Series (Junction Box) has one COM port: COM1.
ROC Plus SIO Driver RS-422 Pin Number Symbol Description 1 RDA Receive Data A 2 RDB Receive Data B 3 SDA Send Data A 4 ERA Data Terminal Ready A 5 GND Common Ground 6 CSB Send Possible B 7 SDB Send Data B 8 CSA Send Possible A 9 ERB Data Terminal Ready B Note: z z EIO0000001145 03/2012 When making your own connections, attach a loop back between pins 6 (CSB) and 9 (ERB), and between 4 (ERA) and 8 (CSA).
ROC Plus SIO Driver COM2 (RJ45 Socket) WARNING UNINTENDED EQUIPMENT OPERATION When making your own connections, use shielded RJ45 connectors. The shielded connector provides isolation against electromagnetic interference and provides a more secure physical connection in the RJ45 socket. Use of an improper RJ45 connection could lead to insecure connections. Failure to follow these instructions can result in death, serious injury, or equipment damage. COM2 supports RS-422/485 signals only.
ROC Plus SIO Driver Magelis HMIGTO Series The HMIGTO target machines have two COM ports (COM1 and COM2), with the exception of the HMIGTO1310. The HMIGTO1310 has one COM port (COM1), which uses an RJ45 connector. For more information, see Magelis XBTGT1000, XBTGT1005, HMIGTO1310, HMISTO, and HMISTU Series. COM1 is a 9-pin D-Sub male connector, and COM2 is an RJ45 socket. The following tables illustrate the pin layout for these target machines.
ROC Plus SIO Driver Note: z z You can switch pin 9 between RI and VCC via software. The VCC output is not protected against overcurrent. To prevent damage or a unit malfunction, use only the rated current. You can use the Cable Connector (Omron Corporation: XMD-0901), Cable Cover (Omron Corporation: XM2S-0913), and Jack Screw #4-40 UNC (Omron Corporation: XM2Z-0073). COM2 (RJ45 Socket) WARNING UNINTENDED EQUIPMENT OPERATION When making your own connections, use shielded RJ45 connectors.
ROC Plus SIO Driver DANGER ELECTRIC SHOCK The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected inside the unit. When using the SG terminal to connect an external device to the panel: z z Verify that a short-circuit loop is not created when you set up the system. Connect the #8 SG terminal to remote equipment when the host (PLC) unit is not isolated. Connect the #8 SG terminal to a known reliable ground connection to reduce the risk of damaging the circuit.
ROC Plus SIO Driver COM1 (RJ45 Socket) WARNING UNINTENDED EQUIPMENT OPERATION When making your own connections, use shielded RJ45 connectors. The shielded connector provides isolation against electromagnetic interference and provides a more secure physical connection in the RJ45 socket. Use of an improper RJ45 connection could lead to insecure connections. Failure to follow these instructions can result in death, serious injury, or equipment damage.
ROC Plus SIO Driver Cable Diagrams The illustrated cable diagrams and those recommended by Emerson Process Management may differ. However, Schneider Electric recommends using the following connections. When creating your own cables, to identify which pins to connect on the target machine, see Target Machine Serial Interface. z Ensure that the equipment is properly grounded as indicated in the user manual and follows all applicable country standards.
ROC Plus SIO Driver Cable Diagram 3 RS-232C to FB407 LOI Operator Interface Cable Connection Cable Diagram 4 RS-485 Cable Connection 20 EIO0000001145 03/2012
ROC Plus SIO Driver Cable Diagram 5 RS-422, 2-Wire / RS485 (DB9) Cable Connection Cable Diagram 6 RS-422, 4-Wire (DB9) Cable Connection EIO0000001145 03/2012 21
ROC Plus SIO Driver Supported Devices Overview The entire range of Type, Logical, Parameter (TLP) settings are supported for all Emerson Process Management models/series listed in this manual. In the following example for the TLP address [PLC1]92,0,3:UINT8, the address components are described in the table below.
ROC Plus SIO Driver Device Address Configuration Overview WARNING UNINTENDED EQUIPMENT OPERATION Read and understand the instructions in this section to ensure data is properly transferred. If you do not follow these instructions, incorrect data could be written to the PLC and the target machine. Failure to follow these instructions can result in death, serious injury, or equipment damage. To set up a PLC variable, use Input Address Settings or Custom Input Address Settings.
ROC Plus SIO Driver Screen Description 24 Area Description Point Type A list that contains the point types available from the ROC database. Select a point type from the list. Location A point type location. Enter an integer from 0 to 255. Slot The slot number for the physical point type. This property displays only if you selected a physical slot type. Enter an integer from 0 to 255. Channel The channel number for the physical point type.
ROC Plus SIO Driver Custom Input Address Settings You can also set up custom TLP addresses by entering the numeric TLP data in the Device Address property in the [Variable Properties] dialog box. Or you can click the ellipsis beside the Device Address text box to open the following address settings dialog box and then selecting the Custom point type. Screen Description EIO0000001145 03/2012 Area Description Point Type A list that contains the point types available from the ROC database.
ROC Plus SIO Driver Valid Formats for Custom Input Address Settings In the TLP property, enter the TLP. The valid formats are: z [PLC1]TT,LL,PP:DATATYPE [PLC1]TT,LL,PP.BIT:DATATYPE z The addresses represent the following components: TLP Component Description [PLC1] = External device TT = Point Type (range 0 to 255) LL = Logical (range 0 to 255) PP = Parameter (range 0 to 255) BIT DATATYPE Bit range 0-7, 0-15, or 0-31.
ROC Plus SIO Driver Name Description TIME 32 bit signed integer TLP 24 bit integer in 32 bits UINT8 8 bit unsigned integer, or bit address 0-7* UINT16 16 bit unsigned integer, or bit address 0-15* UINT32 32 bit unsigned integer, or bit address 0-31* * Read-modify-write. When you write to one of these bit addresses, the target machine reads the entire word address, sets the defined bit, then returns the new value to the PLC.
ROC Plus SIO Driver I/O Manager Configuration Overview The driver and equipment, which enable communication between the target machine and the PLC, depends on the PLC type. Note: z For information on how to display the [New Driver] dialog box, see the Vijeo Designer Online Help.
ROC Plus SIO Driver Driver Configuration Overview WARNING UNINTENDED EQUIPMENT OPERATION Read and understand the instructions in this section to ensure data is properly transferred. If you do not follow these instructions, incorrect data could be written to the PLC and the target machine. Failure to follow these instructions can result in death, serious injury, or equipment damage.
ROC Plus SIO Driver Screen Description Area 30 Description Manufacturer Displays the name of the driver’s manufacturer. Driver Displays the type of serial connection used to connect the target machine to the driver. COM Port Defines which COM port to use on the target machine to connect to the driver. Serial Interface Defines the serial connection. For details about the supported connections, see Cable Diagrams. Flow Control Defines the signals that control the data flow.
ROC Plus SIO Driver Equipment Configuration Overview WARNING UNINTENDED EQUIPMENT OPERATION Read and understand the instructions in this section to ensure data is properly transferred. If you do not follow these instructions, incorrect data could be written to the driver and the target machine. Failure to follow these instructions can result in death, serious injury, or equipment damage.
ROC Plus SIO Driver Screen Description Area Description Host Address The communication address of the target machine. Enter a value from 1 to 255. Host Group The communication group of the target machine. Enter a value from 0 to 255. Device Address The communication address for the specific ROC. Enter a value from 1 to 255 Device Group The communication group for the specific ROC. Enter a value from 0 to 255. Operator ID* The login ID defined for the ROC.