Instruction Manual DVC2000 Digital Valve Controller D103176X012 April 2014 Fisher FIELDVUE DVC2000 Digital Valve Controller This manual applies to Instrument Level HC, AD, PD Device Type 05 Device Revision 1 Hardware Revision 1&2 Firmware Revision 1, 2, 3, 4 & 5 DD Revision 3 AC F5 1 1&2 1, 2, 3, 4 & 5 1 Contents Section 1 Introduction and Specifications . 3 Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instrument Description . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual DVC2000 Digital Valve Controller D103176X012 April 2014 General Information . . . . . . . . . . . . . . . . . . . . . . . . HART Tag Message Descriptor Date Valve Serial Number Instrument Serial Number Polling Address LUI Language Measured Variable Units and Ranges . . . . . . . . . . . Analog Input Units Analog Input Range High and Low Pressure Units Temperature Units Actuator and Valve Information . . . . . . . . . . . . . . .
Instruction Manual Introduction and Specifications D103176X012 April 2014 Section 1 Introduction and Specifications1‐1‐ Scope of Manual This instruction manual is a supplement to the DVC2000 Quick Start Guide (D103203X012) that ships with every instrument. This instruction manual includes specifications, installation, initial setup, configuration, operation, troubleshooting, maintenance information and replacement part details.
Introduction and Specifications Instruction Manual April 2014 D103176X012 Local Interface— The DVC2000 comes standard with a Liquid Crystal Display (LCD) and four (4) pushbuttons. The local interface provides the capability to setup and calibrate the positioner and view basic diagnostic messages. Magnet Assembly—This is the feedback component that is mounted directly to the valve stem. It supplies a magnetic field that is sensed by the digital valve controller.
Introduction and Specifications Instruction Manual April 2014 D103176X012 Table 1‐1. Specifications J Integral mounting to the Fisher GX Control Valve and Actuator System J Sliding-stem applications J Quarter-turn rotary applications Air Consumption(2) Supply pressure: At 1.5 bar (22 psig) (3): 0.06 normal m3/h (2.3 scfh) At 4 bar (58 psig) (4): 0.12 normal m3/h (4.
Instruction Manual Introduction and Specifications D103176X012 April 2014 Table 1‐1.
Introduction and Specifications Instruction Manual April 2014 D103176X012 Table 1‐2.
Introduction and Specifications April 2014 Instruction Manual D103176X012 Educational Services For information on available courses for the DVC2000 digital valve controller, as well as a variety of other products, contact: Emerson Process Management Educational Services - Registration P.O. Box 190 Marshalltown, IA 50158-2823 Phone: 800-338-8158 or 641-754-3771 FAX: 641-754-3431 e-mail: education@emerson.
Instruction Manual D103176X012 Installation April 2014 Section 2 Installation2‐2‐ Installation Note The DVC2000 is not designed to correct for significant stem rotation on sliding-stem actuators. WARNING Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before mounting the DVC2000 digital valve controller: D Always wear protective clothing, gloves, and eyewear when performing any installation procedures to avoid personal injury or property damage.
Instruction Manual Installation D103176X012 April 2014 Figure 2‐1.
Instruction Manual Installation D103176X012 April 2014 The linear magnet arrays have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor (on the back of the DVC2000 housing) has to remain within this range throughout the entire valve travel. See figure 2‐2. The linear magnet arrays are symmetrical. Either end may be up. Figure 2‐2.
Installation April 2014 Instruction Manual D103176X012 Sliding-Stem (Linear) Actuators 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock-out procedures to be sure that the above measures stay in effect while you work on the equipment. 2. Attach the mounting bracket to the actuator. 3.
Instruction Manual Installation D103176X012 April 2014 Figure 2‐4. Air-to-Open Magnet Array Alignment Figure 2‐5. Air-to-Close Magnet Array Alignment ALIGNMENT TEMPLATE ALIGNMENT TEMPLATE LINE UP WITH UPPER EXTREME OF VALID TRAVEL RANGE LINE UP WITH LOWER EXTREME OF VALID TRAVEL RANGE W9220 W9221 7. Mount the digital valve controller to the mounting bracket, using the mounting bolts. See figure 2‐6. 8. Check for clearance between the magnet assembly and the DVC2000 feedback slot.
Instruction Manual Installation D103176X012 April 2014 Mounting on GX Actuators The DVC2000 digital valve controller mounts directly on the GX actuator without the need for a mounting bracket. However, in applications where the process temperature exceeds 80_C (176_F), it may be necessary to apply an insulating gasket between the actuator yoke and the DVC2000, as shown in figure 2‐8, The heat conducted from the process line will transmit through the valve body and actuator and ultimately to the DVC2000.
Instruction Manual Installation D103176X012 April 2014 If the process and ambient temperatures exceed the limits indicated by zone 2, then the DVC2000 high temperature mounting kit can not be used. If temperatures exceed zone 2, you must use an extension bonnet or bracket mounted instrument. Identify the yoke side to mount the DVC2000 digital valve controller based on the actuator fail mode. Refer to the GX Control Valve and Actuator System instruction manual (D103175X012). 1.
Instruction Manual Installation D103176X012 April 2014 5. Tighten the fasteners and remove the alignment template. Continue on with the appropriate step 6 below. Note Use a flat end hex key to tighten the mounting assembly fasteners to a torque of 2.37 N•m (21 in•lbf) for 4 mm screws, and 5.08 N•m (45 in•lbf) for 5 mm screws. While tightening the fasteners using the hex key should be sufficient, blue (medium) thread locker may be used for additional security. For Air-to-Open GX Actuators 6.
Instruction Manual Installation D103176X012 April 2014 8. Check for clearance between the magnet assembly and the DVC2000 feedback slot. The magnet assembly should be positioned so that the index mark on the pole pieces (back of the positioner housing) is within the valid range on the magnet assembly throughout the range of travel. See figure 2‐2. 9. Install tubing between the actuator casing and the pneumatic positioner output connection that has the arrow pointing away from the opening.
Instruction Manual Installation D103176X012 April 2014 Figure 2‐14. Magnetic Assembly Orientation on Quarter-Turn Actuators ORIENTATION AT ONE TRAVEL EXTREME ORIENTATION AT MID-TRAVEL (FLATS PARALLEL TO DVC2000 CHANNEL) 1 ORIENTATION AT THE OTHER TRAVEL EXTREME W8836 1 THIS EXAMPLE SHOWS AN ACTUATOR WITH 90 TRAVEL. ON AN ACTUATOR THAT HAS LESS THAN 90 TRAVEL THE MAGNET ASSEMBLY MAY NOT BE PARALLEL AT THE MID-TRAVEL POINT.
Instruction Manual Installation D103176X012 April 2014 Electrical and Pneumatic Connections The electrical and pneumatic connections on the digital valve controller are available with the following combinations: D 1/4 NPT supply and output with 1/2 NPT conduit connections D G1/4 supply and output with M20 conduit connections Supply Connections WARNING Severe personal injury or property damage may occur from process instability if the instrument air supply is not clean, dry, and oil-free.
Instruction Manual Installation D103176X012 April 2014 Wire the digital valve controller as follows: 1. Remove the main instrument cover. 2. Route the field wiring into the terminal box through the conduit connection. When applicable, install conduit using local and national electrical codes that apply to the application. 3. Connect the control system output card positive wire “current output” to the +11 terminal.
Instruction Manual D103176X012 Installation April 2014 Position Transmitter On units that are supplied with an integral valve position transmitter, additional terminals provide the field wiring connection point. The position transmitter circuit in the DVC2000 derives it's operating power from the 4-20 mA control system input in the same manner as a 2-wire transmitter.
Installation April 2014 22 Instruction Manual D103176X012
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Section 3 Basic Setup and Calibration with Local User Interface3‐3‐ The local user interface is available on all DVC2000 digital valve controllers. The interface consists of a liquid crystal display, four pushbuttons, and a switch for position transmitter configuration. The DVC2000 is supplied with one of three different language packs preinstalled, depending on the firmware revision and ordering option.
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Basic Setup WARNING Changes to the instrument setup may cause changes in the output pressure or valve travel. Depending on the application, these changes may upset process control, which may result in personal injury or property damage. When the DVC2000 digital valve controller is ordered as part of a control valve assembly, the factory mounts the digital valve controller and sets up the instrument as specified on the order.
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Table 3‐2. Actuator Information for Setup Actuator Manufacturer Actuator Model Actuator Style Actuator Size Starting Tuning Set(1) Feedback Connection 585C & 585CR Piston Dbl w/ or w/o Spring. See actuator instruction manual and nameplate. 25, 50, 60, 68, 80, 100, 130 Undefined SStem-Standard for travels up to 4 inches.
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Quick Setup When installing the DVC2000 digital valve controller on an actuator for the first time, the quick setup procedure will calibrate and tune the instrument automatically. Table 3‐3 lists the values that are preconfigured at the factory. Table 3‐3.
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Travel Calibration WARNING During calibration you will be asked to move the valve full stroke. To avoid personal injury and property damage caused by the release of pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the process fluid.
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Tuning WARNING Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly. To manually tune the instrument or automatically tune the instrument without changing the calibration values, the TUNING routine is available.
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Table 3‐4. Gain Values for Preselected Turning Sets Tuning Set Proportional Gain Velocity Gain Minor Loop Feedback Gain C 5 2 55 D 6 2 55 E 7 2 55 F 8 2 52 G 9 2 49 H 10 2 46 I 11 2 44 J 12 1 41 K 14 1 38 L 16 1 35 M 18 1 35 A typical starting point for most small actuators is “C”. Using the UP (Y) and DOWN (B) arrow keys will apply the values immediately.
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Figure 3‐5. Detailed Setup Flow Chart TRAVEL = 66.8% 14.6 MA 0.92 BAR Y B QUICK SETUP Y B TRAVEL CALIBRATION Y B TUNING Y B DETAILED SETUP " ZERO CTL SIGNAL VALVE CLOSED A " PRESSURE UNITS BAR Only with Optional Position Transmitter / Limit Switches TRANSMITTER A 4MA CLOSED CLOSED OPEN " INPUT RANGE LOW 4 MA BAR PSI KPA CLOSED OPEN " A " INPUT RANGE A HIGH 20 MA A " CHARACTERISTIC LINEAR 20MA ...
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Figure 3‐6. XMTR Switch TRANSMITTER SWITCH FOR FAIL SIGNAL + HIGH (SHOWN) OR - LOW Switch #1 Trip Point—Defines the threshold for the limit switch wired to terminals +41 and -42 in percent of calibrated travel. Switch #1 Closed—Configures the action of the limit switch wired to terminals +41 and -42. Selecting ABOVE configures the switch to be closed when the travel is above the trip point.
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Analog Input Calibration WARNING During calibration you will be asked to move the valve full stroke. To avoid personal injury and property damage caused by the release of pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the process fluid. The DVC2000 digital valve controller is shipped from the factory with the analog input already calibrated.
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Position Transmitter Calibration Note This procedure will not move the control valve. The instrument will simulate an output for calibration purposes only. This procedure is only available on units that have the optional position transmitter / limit switch hardware installed. The DVC2000 digital valve controller is shipped from the factory with the position transmitter already calibrated.
Instruction Manual Basic Setup and Calibration D103176X012 April 2014 Local Control This procedure allows the user to manually control the position of the valve (see figure 3‐9). To enter this procedure from the home screen, press the DOWN (B) arrow key seven times and then press the RIGHT (") arrow key. If you select ANALOG, you will return to the home screen and the digital valve controller will respond to the loop current.
Instruction Manual D103176X012 Basic Setup and Calibration April 2014 Diagnostic Messages, Codes and Details The DVC2000 digital valve controller is constantly diagnosing itself for abnormal conditions while powered-up. The following messages will appear on the local user interface if a fault condition exists (identified on the default screen by the alert symbol ! ).
Basic Setup and Calibration April 2014 36 Instruction Manual D103176X012
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 Section 4 Detailed Setup and Calibration via HART Communication4‐4‐ Detailed Setup The DVC2000 digital valve controller has the capability to communicate via the HART protocol. This section describes the advanced features that can be accessed with the Field Communicator.
Detailed Setup and Calibration April 2014 Instruction Manual D103176X012 calibration or stroke valve. However, if you abort from a procedure where the instrument is in the Test mode, it may remain in this mode. To take the instrument out of the Test mode, select Control Mode then select either Analog or Digital. Restart Control Mode Restart Control Mode (Restart Cont Mode) lets you choose which operating mode you want the instrument to be in after a restart.
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 Table 4‐1.
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 Setting Protection Setup & Diag > Detailed Setup > Protection (1-2-2) Field Communicator Some setup parameters may require changing the protection with the Field Communicator. Two levels of protection are available: D None—Neither setup nor calibration is protected. Allows changing calibration and setup parameters. D Config & Calib—Both setup and calibration are protected.
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 Table 4‐2.
Detailed Setup and Calibration Instruction Manual D103176X012 April 2014 D Date—Enter a date with the format MM/DD/YY. Date is a user-defined variable that provides a place to save the date of the last revision of configuration or calibration information. D Valve Serial Num—Enter the serial number for the valve in the application with up to 12 characters. D Inst Serial Num—Enter the serial number on the instrument nameplate, up to 12 characters.
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 Figure 4‐1.
Detailed Setup and Calibration Instruction Manual D103176X012 April 2014 Setting Response Field Communicator Setup & Diag > Detailed Setup > Response Control (1-2-6) Follow the prompts on the Field Communicator to configure the following response control parameters: WARNING Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 Figure 4‐2.
Detailed Setup and Calibration Instruction Manual D103176X012 April 2014 Travel Limit Lo—Defines the low limit for the travel in percent (%) of ranged travel. It is the minimum allowable travel (in percent of ranged travel) for the valve. During operation, the travel target will not exceed this limit. When a Travel Limit Low is set, the Travel Cutoff Low is deactivated, since only one of these parameters can be active. Travel Limit Low is deactivated by setting it to -25.0%.
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 Setting Travel Alerts Setting High, High-High, Low and Low-Low Alerts Follow the prompts on the Field Communicator to set the following travel alerts: D Tvl Hi/Lo Enab—Yes or No. Travel Hi/Lo Enable activates checking of the ranged travel against the Travel Alert High and Low Points. Travel Alert Hi is set if the ranged travel rises above the alert high point.
Detailed Setup and Calibration Instruction Manual April 2014 D103176X012 D Tvl Alrt DB—Travel Alert Deadband is the travel, in percent (%) of ranged travel, required to clear a travel alert, once it has been set. The deadband applies to both Travel Alert Hi/Lo and Travel Alert Hi Hi/Lo Lo. See figure 4‐3. Note The Travel Alert Deadband applies to the Travel Deviation as well as Travel Alert Hi/Lo and Travel Alert Hi Hi/Lo Lo.
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 Figure 4‐4. Travel Accumulator Deadband (set at 10%) DEADBAND EXCEEDED, NEW REFERENCE POINT ESTABLISHED DEADBAND REFERENCE POINT DEADBAND (+/- 5%) THIS AMOUNT OF CHANGE IS ADDED TO THE TRAVEL ACCUMULATOR. A6534 Cycle Counter Alert Follow the prompts on the Field Communicator to set the following cycle counter alerts: D Cycl Cnt Alrt Enab—Yes or No.
Detailed Setup and Calibration Instruction Manual April 2014 D103176X012 D Cycle Count—Cycle Counter records the number of times the travel changes direction. The change in direction must occur after the deadband has been exceeded before it can be counted as a cycle. See figure 4‐5. You can reset the Cycle Counter by configuring it as zero. Other Alerts Follow the prompts on the Field Communicator to configure Drive Alert Enable: D Drive Alert Enab—Yes or No.
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 Self Test Failures for Instrument Shutdown Field Communicator Setup & Diag > Detailed Setup > Self Test Shutdown (1-2-8) Upon shutdown, the instrument attempts to drive its output pressure to the zero current condition and no longer executes its control function. In addition, the appropriate failure statuses are set.
Detailed Setup and Calibration Instruction Manual D103176X012 April 2014 Transmitters/Switches Field Communicator Setup & Diag > Detailed Setup > Transmitter/Switches (1-2-9) Note These menu items are only available on units that have the optional position transmitter / limit switch hardware installed. If optional limit switches are being used, power must be applied to the switch circuits throughout the calibration routine. Failure to power the switches may result in incorrect switch orientation.
Instruction Manual D103176X012 Detailed Setup and Calibration April 2014 Tuning WARNING Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly. Automatic Field Communicator Calibrate > Calibrate > Auto Tuner (1-4-5) The auto tuner is used to optimize digital valve controller tuning.
Detailed Setup and Calibration Instruction Manual D103176X012 April 2014 1. Set the current source to the target value shown on the display. The target value is the Input Range Low value. Press OK. 2. The following message appears: Use Increase and Decrease selections until the displayed current matches the target. Press OK when you have read this message. 3. The value of the Analog Input appears on the display. Press OK to display the adjustment menu. 4.
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 2. Place the instrument In Service and verify that the travel properly tracks the current source. Manual Calibrate Travel Two procedures are available to manually calibrate travel: D Analog Adjust D Digital Adjust Analog Calibration Adjust Connect a variable current source to the instrument LOOP + and LOOP - terminals. The current source should be capable of generating 4 to 20 mA.
Detailed Setup and Calibration Instruction Manual D103176X012 April 2014 If another adjustment is required, repeat step 1. Otherwise, select Done and go to step 2. 2. From the adjustment menu, select the direction and size of change required to set the travel to 100%. If another adjustment is required, repeat step 2. Otherwise, select Done and go to step 3. 3. From the adjustment menu, select the direction and size of change required to set the travel to 50%.
Instruction Manual Detailed Setup and Calibration D103176X012 April 2014 Press OK when you have read the message. 6. The value of the output pressure appears on the display. Press OK to display the adjustment menu. 7. From the adjustment menu, select the direction and size of adjustment to the displayed value. Selecting large, medium, and small adjustments causes changes of approximately 3.0 psi/0.207 bar/20.7 kPa, 0.30 psi/0.0207 bar/2.07 kPa, and 0.03 psi/0.00207 bar/0.207 kPa, respectively.
Detailed Setup and Calibration April 2014 58 Instruction Manual D103176X012
Instruction Manual Viewing Device Variables and Diagnostics D103176X012 April 2014 Section 5 Viewing Device Variables and Diagnostics5‐5‐ Viewing Variables Note These variables are not available for instrument level AC. Analog Input, Travel, Valve Set Point, Drive Signal and Output Pressure The following variables are displayed on the Online menu: Analog In shows the value of the instrument analog input in mA (milliamperes) or % (percent) of ranged input.
Instruction Manual Viewing Device Variables and Diagnostics D103176X012 April 2014 D Tvl Accum—Travel Accumulator contains the total change in travel, in percent of ranged travel. The accumulator only increments when travel exceeds the deadband. Then the greatest amount of change in one direction from the original reference point (after the deadband has been exceeded) will be added to the Travel Accumulator. The value of the Travel Accumulator can be reset from the Travel Accum Alert menu.
Instruction Manual Viewing Device Variables and Diagnostics D103176X012 April 2014 Viewing Instrument Status Field Communicator Instrument Status (7) Note Instrument Status is not available for instrument level AC. The following describes the various displays for the Instrument Status menu. D Done—Select this when you are done viewing the instrument status. Note Alerts are not available with instrument level AC.
Instruction Manual Viewing Device Variables and Diagnostics D103176X012 April 2014 D Failure Alerts—If a self-test failure has occurred, it will appear when the Failure Alerts menu item is selected. If there are multiple failures, they will appear on the display one at a time in the order listed below. 1. Offline/Failed—This failure indicates a failure, enabled from the Self Test Shutdown menu, caused an instrument shutdown.
Instruction Manual D103176X012 Viewing Device Variables and Diagnostics April 2014 D Operational Status—This menu item indicates the status of the Operational items listed below. The status of more than one operational may be indicated. If more than one Operational status is set, they will appear on the display one at a time in the order listed below. 1. Out of Service 2. Auto Calibration in Progress 3. Input Char Selected 4. Custom Char Selected 5. Diagnostic in Progress 6. Calibration in Progress 7.
Viewing Device Variables and Diagnostics April 2014 64 Instruction Manual D103176X012
Instruction Manual Maintenance and Troubleshooting D103176X012 April 2014 Section 6 Maintenance and Troubleshooting6‐6‐ The DVC2000 digital valve controller has the capability to provide predictive maintenance information through the use of ValveLink software. This software allows you to pinpoint instrument and valve problems without disrupting the process. For information on using ValveLink software, see the ValveLink software User Guide.
Instruction Manual Maintenance and Troubleshooting D103176X012 April 2014 D Done—Select this if you are done. All ramping is stopped when DONE is selected. D Ramp Open—ramps the travel toward open at the rate of 1.0% per second of the ranged travel. D Ramp Closed—ramps the travel toward closed at the rate of 1.0% per second of the ranged travel. D Ramp to Target—ramps the travel to the specified target at the rate of 1.0% per second of the ranged travel.
Instruction Manual Maintenance and Troubleshooting D103176X012 April 2014 6. Remove the bolts connecting the DVC2000 housing to the mounting bracket. Note The magnet assembly may remain on the valve stem (or shaft). When replacing the instrument, be sure to follow the mounting procedure outlined in Section 2. Once the instrument is mounted, perform the Quick Setup routine outlined in Section 3.
Maintenance and Troubleshooting Instruction Manual April 2014 D103176X012 Removal 1. Remove the main cover. 2. Remove three screws that hold the EMI shield and remove the shield (refer to figure 6‐1). 3. Remove the three screws holding the electronics board to the mounting frame (refer to figure 6‐1). 4. Pull the main electronics straight off of the mounting frame. The board is electrically connected to an interconnecting board with a rigid connector.
Instruction Manual Maintenance and Troubleshooting D103176X012 April 2014 Figure 6‐2. Mounting Frame Assembly INTERCONNECT BOARD MANIFOLD ASSEMBLY INTERCONNECT BOARD SCREW (1) PNEUMATIC RELAY SCREWS (2) I/P BOARD SCREW (1) W9103 I/P CONVERTER SCREW HOLES (4) (SCREWS NOT SHOWN) MOUNTING FRAME SCREW HOLES (2) (SCREWS NOT SHOWN) Assembly 1. Replace the short conductive gasket (key 24) if necessary. 2.
Instruction Manual Maintenance and Troubleshooting D103176X012 April 2014 Figure 6‐3. Installation of Conductive Gasket TERMINAL BARRIER CONDUCTIVE GASKET W8844 10. Tighten the self-tapping screw (key 42) on the Interconnect Board. 11. Install the Primary Shield (key 37) with three screws. 12. Recalibrate the instrument and install the cover. Replacing the I/P Converter The I/P converter is fastened to the mounting frame. On the I/P mounting surface is a replaceable screen with O-ring seal.
Instruction Manual Maintenance and Troubleshooting D103176X012 April 2014 4. Pull the main electronics straight off of the mounting frame. The board is electrically connected to an interconnecting board with a rigid connector. 5. Remove the two screws holding the mounting frame to the instrument housing (refer to figure 6‐2 for location of screws). 6. Pull the manifold assembly straight out. The interconnecting board is electrically connected to the termination board with a rigid connector. 7.
Maintenance and Troubleshooting April 2014 Instruction Manual D103176X012 7. Remove the two screws holding the pneumatic relay to the mounting frame. 8. Pull the pneumatic relay straight out. Assembly When installing a new pneumatic relay, follow the reverse procedure as outlined above and recalibrate the instrument. Troubleshooting What is a healthy unit? In order to troubleshoot the DVC2000 digital valve controller, it is critical to understand how a healthy unit is supposed to behave.
Instruction Manual Maintenance and Troubleshooting D103176X012 April 2014 2. Check the instrument protection (LCD via pushbuttons and Configure/Calibrate via HART) 3. Check for local device diagnostic messages 4. Check the alerts via HART 5. Check the feedback setup Is the pole piece on the DVC2000 housing within the valid travel range of the feedback array? 6. Observe the stem movement and pressure delivery Determine the logical causes.
Instruction Manual Maintenance and Troubleshooting D103176X012 April 2014 Checking Voltage Available WARNING Personal injury or property damage caused by fire or explosion may occur it this test is attempted in any area which contains a potentially explosive atmosphere or has been classified as hazardous. To check the Voltage Available at the instrument, perform the following: 1.
Instruction Manual Maintenance and Troubleshooting D103176X012 April 2014 Technical Support Checklist Have the following information available prior to contacting your Emerson Process Management sales office for support. 1. Instrument serial number as read from nameplate ________________________________________________ 2. Is the digital valve controller responding to the control signal? Yes _________ No _________ If not, describe: 3.
Maintenance and Troubleshooting Instruction Manual April 2014 D103176X012 Mounting 1. Actuator application: Sliding Stem? _______ Rotary? _______ 2. What Make, Brand, Style, Size, etc. actuator is the DVC6000 SIS mounted on? ________________________ 3. What is the Mounting Kit part number? _________________________________________________________ 4. If mounting kits are made by LBP/Customer, please provide pictures of installation. 5.
Instruction Manual Parts D103176X012 April 2014 Section 7 Parts7‐7‐ Parts Ordering Whenever corresponding with your Emerson Process Management sales office about this equipment, always mention the controller serial number. When ordering replacement parts, refer to the 11-character part number of each required part as found in the following parts list. Parts which do not show part numbers cannot be ordered. WARNING Use only genuine Fisher replacement parts.
Instruction Manual Parts D103176X012 April 2014 Description Part Number Feedback Array Kit (cont'd) Rotary [kit contains feedback assembly, pointer, and travel indicator scale]. Stainless steel kits only for use with stainless steel mounting kits.
Instruction Manual Parts D103176X012 April 2014 Figure 7‐1. FIELDVUE DVC2000 Digital Valve Controller Assembly, Housing A APPLY LUBRICANT/SEALANT NOTE: 1.
Parts April 2014 Figure 7‐2. FIELDVUE DVC2000 Digital Valve Controller Assembly, Housing A APPLY LUBRICANT/SEALANT NOTE: 1.
Instruction Manual Parts D103176X012 April 2014 Figure 7‐3. FIELDVUE DVC2000 Digital Valve Controller Assembly, Housing A SEE VIEW B SEE VIEW B POSITIONER WITH TRANSMITTER AND LIMIT SWITCHES POSITIONER ONLY VIEW B APPLY LUBRICANT/SEALANT NOTE: 1.
Parts April 2014 82 Instruction Manual D103176X012
Instruction Manual Principle of Operation D103176X012 April 2014 Appendix A Principle of OperationA‐1‐ DVC2000 Operation The DVC2000 digital valve controller uses a traditional 4-20 mA input signal and converts it into a pneumatic output pressure that is delivered to the control valve actuator. Accurate control of the position of the valve is enabled by valve stem position feedback. The way in which the DVC2000 accomplishes this is through a two-stage positioner design.
Principle of Operation April 2014 Instruction Manual D103176X012 D The I/P converter assembly is connected to supply pressure and converts the drive signal into a pressure signal. The I/P converter is the pre-amplifier stage in the two-stage positioner design. This component enables high static gain for responsiveness to small changes in the input signal. D The I/P output is sent to the pneumatic relay assembly.
Instruction Manual D103176X012 Local Interface Flow Chart/Menu Trees April 2014 Appendix B Local Interface Flow Chart and Field Communicator Menu TreesB‐B‐ This section contains the Local Interface Flow Chart and the Field Communicator menu trees for instrument level HC, AD, and PD and instrument level AC. It also contains Fast Key Sequence tables with coordinates to help locate the function/variable on the appropriate menu tree.
Instruction Manual Local Interface Flow Chart/Menu Trees D103176X012 April 2014 Local Interface Flow Chart These items are identified by an alert icon on the default screen TRAVEL = 66.8% 14.6 MA 0.92 BAR Y 1 Y Home Screen TRAVEL DEVIATION SHUTDOWN ACTIVATED ! CHECK MOUNTING CHECK I/P CONVERTER CHECK SUPPLY Y FINDING 0% ... Y FINDING 50% ... FINDING 0% ... Y FINDING 50% ... Y MOVE VALVE TO 0% TRAVEL Y FINDING 50% ...
Instruction Manual Local Interface Flow Chart/Menu Trees D103176X012 April 2014 Y Y FW3:1, HW1:2 TUNING = C Y SWITCH1 = OPEN SWITCH 2 = CLOSED Y Y REPLACE MAIN BOARD Y Only when transmitter / limit switch hardware is installed PROTECTION OFF 1 OFF ON Y Y Y QUICK SETUP COMPLETE 1 CALIBRATION COMPLETE 1 CALIBRATION FAILED 1 Y SAVE AND PRESS EXIT? + INVERT DISPLAY 180 Note: Hold + for 3 to 10 seconds + CANCEL (TAKES YOU TO THE HOME SCREEN) Note: Hold + for 3 to 10 seco
Instruction Manual Local Interface Flow Chart/Menu Trees D103176X012 April 2014 Field Communicator Fast‐Key Sequence (Instrument Level HC, AD and PD) Function/Variable Actuator Style Alert Record Analog Input Analog Input Calibration Analog Input Range High Analog Input Range Low Analog Input Units Auto Calibrate Travel Auto Setup Auto Tuner Basic Setup Burst Calibrate Control Mode Custom Characteristic Table Cycle Count Cycle Count Alert Cycle Count Alert Enable Cycle Count Alert Point Cycle Count Dea
Instruction Manual Local Interface Flow Chart/Menu Trees D103176X012 April 2014 Field Communicator Menu Tree for Instrument Level HC, AD and PD Hot Key 1 Instrument Mode 2 Protection 3 Tuning 1 Tuning Set 2 Damping Factor 3 Expert Tuning Gains 1‐1‐1‐4 Auto Setup 1 2 3 4 1‐1 1 Tuning Set 2 Damping Factor 3 Expert Tuning Gains 1‐1‐1 1 Vel Gain 2 MLFB Gain Setup Wizard Auto Calib Travel Auto Tuner Tuning 1‐1‐2‐2 Manual Setup 1 Auto Setup 2 Manual Setup 1‐2‐1 1 Instrument Mode 2 Press & Actuato
Instruction Manual Local Interface Flow Chart/Menu Trees D103176X012 April 2014 Field Communicator Fast‐Key Sequence (Instrument Level AC) Function/Variable Analog Input Calibration Fast‐Key Sequence Coordinates(1) Function/Variable Fast‐Key Sequence Coordinates(1) 1‐2‐3‐6‐2 6‐F 1‐3‐1 3‐E Integral Gain 1‐2‐2‐1 4‐E Integral Settings 1‐2‐3‐6 6‐F 1‐3‐2 3‐E LUI Language 1‐2‐1‐8 4‐E Auto Setup 1‐1‐1 3‐B LUI Pressure Units 1‐2‐2‐5 4‐E Auto Tuner 1‐1‐1‐3 3‐B Manual Calibrate Trave
Instruction Manual Local Interface Flow Chart/Menu Trees D103176X012 April 2014 Field Communicator Menu Tree for Instrument Level AC Hot Key 1 Instrument Mode 2 Protection 3 Tuning 1 Tuning Set 2 Damping Factor 3 Expert Tuning Gains A 1 Prop Gain 2 Vel Gain 3 MLFB Gain 1‐1‐1 Auto Setup 1 2 3 4 1‐1 Basic Setup 1 Auto Setup 2 Manual Setup 1‐1‐1‐4 Setup Wizard Auto Calib Travel Auto Tuner Tuning B Tuning 1 Tuning Set 2 Damping Factor 3 Expert Tuning Gains 1‐1‐1‐4‐3 Expert Tuning Gains Manual Set
Local Interface Flow Chart/Menu Trees April 2014 92 Instruction Manual D103176X012
Instruction Manual Glossary D103176X012 April 2014 Glossary Alert Point An adjustable value that, when exceeded, activates an alert. Algorithm A set of logical steps to solve a problem or accomplish a task. A computer program contains one or more algorithms. Alphanumeric Consisting of letters and numbers. Analog Input Units Units in which the analog input is displayed and maintained in the instrument.
Instruction Manual Glossary D103176X012 April 2014 Controller A device that operates automatically to regulate a controlled variable. Deviation Usually, the difference between set point and process variable. More generally, any departure from a desired or expected value or pattern. Current‐to‐Pressure (I/P) Converter An electronic component or device that converts a milliamp signal to a proportional pneumatic pressure output signal.
Instruction Manual Glossary D103176X012 Equal Percentage A valve flow characteristic where equal increments of valve stem travel produce equal percentage changes in existing flow. One of the input characteristics available for a FIELDVUE Instrument. See also, Linear and Quick Opening. Feedback Signal Indicates to the instrument the actual position of the valve. The travel sensor provides the feedback signal to the instrument printed wiring board assembly.
Instruction Manual Glossary D103176X012 April 2014 Instrument Protection Determines if commands from a HART device can calibrate and/or configure certain parameters in the instrument. There are two types of instrument protection: Configuration and Calibration: Prohibits changing protected setup parameters; prohibits calibration. None: Permits both configuration and calibration. The instrument is ”unprotected.
Instruction Manual Glossary D103176X012 Pressure Sensor A FIELDVUE instrument internal device that senses pneumatic pressure. DVC2000 digital valve controllers have one actuator pressure sensor. April 2014 Seat Load Force exerted on the valve seat, typically expressed in pounds force per lineal inch of port circumference. Seat load is determined by shutoff requirements. Primary Master Masters are communicating devices. A primary master is a communicating device permanently wired to a field instrument.
Instruction Manual Glossary D103176X012 April 2014 Travel Accumulator Alert Checks the difference between the Travel Accumulator value and the Travel Accumulator Alert Point. The Travel Accumulator Alert is active when the Travel Accumulator value exceeds the Travel Accumulator Alert Point. It clears after you reset the Travel Accumulator to a value less than the alert point. Travel Alert Low Point Value of the travel, in percent of ranged travel, which, when exceeded, sets the Travel Alert Lo alert.
Instruction Manual Glossary D103176X012 Travel Limit A setup parameter that defines the maximum allowable travel (in percent of ranged travel) for the valve. During operation, the travel target will not exceed this limit. There are two travel limits: high and low. Typically the travel limit low will be used to keep the valve from going completely closed. Travel Range Travel, in percent of calibrated travel, that corresponds to the input range.
Glossary April 2014 100 Instruction Manual D103176X012
Instruction Manual Index D103176X012 April 2014 Index A AC (Auto Calibrate), 3, 60 Auto Calibrate Travel, 54 Auto Calibration in Progress, 63 auto tuner, 53 Actuator and Valve Information, 43 AD (Advanced Diagnostics), 3, 60 Advanced Diagnostics (AD), 3, 60 B Air Capacity, 5 Basic Setup, 24 Air Consumption, 5 Burst Mode Commands, 38 Enabling, 38 Airset option, 6 Alert Record, 50, 62 Clearing, 50 Displaying, 50 Enabling Alert Groups, 50 Alert Record has Entries, 61 Alert Record is full, 61 Alerts
Instruction Manual Index D103176X012 April 2014 Control Mode, 37 Drive Alert Enab, 50 Critical NVM Fail, Self Test Failure, enabling to cause instrument shutdown, 51 Drive Alert Enable, 50 Critical NVM Failure, 62 CSA, Hazardous Area Classification, 5 Custom Char Selected, 63 Cycl Cnt Alrt Enab, 49 Cycl Count Alrt Pt, 49 Cycle Counter Displaying Value, 59 Enabling Alert, 49 Resetting, 50 Drive Current Fail, 51 Self Test Failure, enabling to cause instrument shutdown, 51 Drive Current Failure, 62 Dr
Instruction Manual Index D103176X012 G General Information, 41 GOST‐R, Russian, Certification, 6 GX actuator, converting from fail-open to fail-close, or fail-close to fail-open, 17 April 2014 Installation, 9 Instrument Clock, Setting, 50 Instrument Level, 3, 60 Instrument Mode, 37 Instrument Removal, 66 Instrument Replacement, 66 H Instrument Serial Number, 42 Instrument Status, 61 hall sensor, 11 Instrument Time is Invalid, 61 HART Communicating (HC), 3, 60 Integral Dead Zone, 46 HART Tag, 41
Instruction Manual Index D103176X012 April 2014 M magnet array, 10, 15 Magnet Assemblies, 11 NVM Fail, 51 O Magnet Assembly, 4 Offline/Failed, 62 Magnetic Feedback Assembly, Replacing, 67 Operational Status, 63 Magnetic Tip Screw Drivers , 10 Options Boards, 4, 20 Magnetic Tools, use of with DVC2000, 10 Other Alerts, 50 Magnets, High Power, General Guidelines for use of, 10 Out of Service, 63 Main Elec Rev, 60 Output Pressure Sensor, Calibration, 56 Main Electronics Installation, 68 Remov
Instruction Manual Index D103176X012 Pressure Sensor Failure, 51, 62 pressure signal, 84 April 2014 Serial Number Instrument, 42 Valve, 42 Pressure Units, 29, 42 Set Point Filter Active, 63 Principle of Operation, 83 drive signal, 83 input signal, 83 pneumatic output signal, 84 pressure signal, 84 Set Point Filter Time, 45 Protection, 40 Q Quick Setup, via Local Interface, 26 Setting Alerts, 50 Setting Response, 44 Shaft Rotation, 6 Shutdown Activated, 35 Special Instructions for ”Safe Use” and
Instruction Manual Index D103176X012 April 2014 Travel Accumulator Displaying Value, 60 Enabling Alert, 48 Resetting, 48 Tvl Alert Hi Hi, 61 Travel Accumulator Alert Point, 48 Tvl Alert Lo, 61 Travel Accumulator Deadband, 48 Tvl Alert Lo Lo, 61 Travel Alert Deadband, 48 Tvl Alert Lo Lo Pt, 47 Travel Alert High Point, 47 Tvl Alert Lo Pt, 47 Travel Alert Low Point, 47 Tvl Alrt DB, 48 Travel Alerts High and Low, 47 High High and Low Low, 47 Tvl Dev Alrt Enab, 48 Travel Calibration, via Local
Instruction Manual D103176X012 Digital Valve Controller April 2014 107
DVC2000 Digital Valve Controller April 2014 Instruction Manual D103176X012 Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.