Instruction Manual

www.Fisher.com
Supplement to Fisherr FIELDVUEt DVC6000 or
DVC6200 Digital Valve Controller Instruction
Manuals
Implementation of Lock‐in‐Last Strategy
Many applications require a valve assembly to remain in the position it was prior to a specific control system failure
(lock‐in‐last position). Functionality and safety can be designed into valve assemblies with FIELDVUE digital valve
controllers by utilizing an array of accessories. The following paragraphs describe standard solutions for a number of
generic lock‐in‐last applications with DVC6000 or DVC6200 digital valve controllers.
Note
This instruction manual supplement is for use with HARTr communicating FIELDVUE DVC6000 or DVC6200 digital valve
controllers only.
Lock‐in‐Last on Loss of Supply Pressure
Once the supply pressure falls below a minimum value, the digital valve controller can no longer position a valve
assembly; the valve will start to go to the actuator “at rest” position. The locking device senses this change and
activates, preventing the remaining air from venting. The valve is “locked‐in” this new position.
Note
The locked‐in valve position depends on the exhausting speed of the actuator.
Assemblies with Single‐Acting Actuators
A Fisher 164A three‐way switching valve should be used for locking a single‐acting actuator in place on loss of supply
pressure. Figure 1 is a schematic representing proper assembly layout. In normal operation, the digital valve controller
output passes through the switching valve from port A to port B and on to the actuator.
Instruction Manual Supplement
D103261X012
DVC6000/DVC6200 Digital Valve Controllers
February 2011

Summary of content (8 pages)