Instruction Manual

www.Fisher.com
INMETRO Hazardous Area Approvals for
FIELDVUE™ DVC2000 Digital Valve Controller
This supplement provides INMETRO Hazardous Area Approval information for the DVC2000 digital valve controller
instruction manual and quick start guide. Use this in conjunction with information provided in the instruction manual
(D103176X012) or quick start guide (D103203X012).
INMETRO— National Institute of Metrology, Quality and Technology. INMETRO approval is accepted in Brazil.
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring
requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may
override, the standard installation procedures. Refer to the instruction manual or quick start guide for for all other
information regarding DVC2000 digital valve controllers.
Note
This information supplements the nameplate markings affixed to the product.
Always refer to the nameplate itself to identify the appropriate certification.
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion,
and area re‐classification.
Certificate Number: 10IEx0004X
INMETRO Marking: Ex ia IIC T4/T5 Ga IP66
T4: -40
°C Tamb +80°C; T5: -40°C Tamb +40°C
Standards Used for Certification: NBR IEC 600790:2008, NBR IEC 6007911:2009
Instruction Manual Supplement
D103780X012
DVC2000 Digital Valve Controller
April 2013

Summary of content (2 pages)