Instruction Manual

www.Fisher.com
Supplement to HART
r
Communicating Fisher
r
FIELDVUE
t
Digital Valve Controller Instruction
Manuals
FIELDVUE Digital Valve Controller Split Ranging
Processes requiring extended rangeability may use two or more control valves. The first valve operates over the first
portion of the range. When the first valve is nearly 100% open, the control action begins to open the second valve. This
is called split ranging. When split ranging is performed a single signal from the control system is supplied to the valve
actuators. This single signal is split among the positioning devices on each valve. The positioning devices are used to
achieve full valve travel over the reduced input range. Most applications need a predictable overlap region in the
middle of the signal range to avoid a zone of no control. Positioning devices provide accuracy to ensure the correct
overlap exists.
When split ranging FIELDVUE digital valve controllers, each device requires a minimum voltage available at the
instrument terminals of at least 12 volts (See the appropriate instruction manual for details). Many control systems
provide a compliance voltage that is less than the minimum requirement of 24 volts for two instruments wired in
series. This supplement describes two methods to address the potential discrepancy between the compliance voltage
and the requirements of FIELDVUE instruments.
Limitations of Split Ranging FIELDVUE Digital Valve Controllers
Split ranging FIELDVUE digital valve controllers provides the following limitations:
 Most control systems cannot provide the 24 volt compliance voltage. A device to boost the compliance voltage may
be required, such as the Action Instruments Action Pak
AP4380-2000.
 To communicate with multiple HART instruments on one pair of wires may require the polling addresses for the
instruments be nonzero. This means the instrument polling addresses must be reset and the HART devices (either
the 475/375 Field Communicator or ValveLink software with a HART modem) must be programmed to poll for
instruments at polling addresses other than zero.
 Use of the HART Tri‐Loop
is limited to communication with only one instrument.
 The instrument polling addresses may be nonzero, thus limiting communication with a HART multiplexer.
Guidelines for Split Ranging FIELDVUE Instruments
1. Check the voltage available at the instrument terminals using the method in the instrument instruction manual.
2. Verify that the control system compliance voltage is at least 24 volts DC at 20 mA output. If the compliance voltage
is less than 24 volts DC, add a device to boost the compliance voltage (such as the Action Instruments Model
AP4380‐2000). (Note: the AP4380‐2000 does not have any hazardous area approvals. Appropriate non‐hazardous
installations should be selected.)
Instruction Manual Supplement
D103262X012
FIELDVUE Digital Valve Controllers
February 2011

Summary of content (6 pages)