User's Manual

September 2010 IL42-5016A
1
EA_Water 2.0 module
Installation instructions
General
This leaflet contains instructions for Elster’s EA_Water 2.0 module for use on water meters to provide readings to the
EnergyAxis
®
System. For proper installation and maximum life of the modules, use the following procedures.
Familiarize yourself with the location and identification of the terminals on your water meter registers before any installation
procedure.
Connection instructions
The EA_Water 2.0 module register connections are as follows:
Installation instructions
Integral mount
The EA_Water 2.0 module is shipped fully assembled and ready to install. You will need to mount the EA_Water 2.0 module
directly onto the water meter register. The integral mount cover has a hoop that fits around the water meter register.
1. Align the hoop EA_Water 2.0 module over the water meter register so that the EA_Water 2.0 module wires are
able to connect to the water meter terminals.
2. Securely attach the EA_Water 2.0 module over the water meter register.
Function
Module
cable color
Register terminal color
Elster AMCO Badger Sensus Hersey Neptune
Data Black Red Green Green Green Red
Power (or power/clock) Red Green Red Red Red Black
Common Green Black Black Black Black Green
EA_Water 2.0 remote module
Integral mount cover