Cooper Bussmann Read and Retain for Future Reference - Version 1.4.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual ATTENTION! Incorrect termination of the supply wires may cause internal damage and will void the warranty. To ensure that your 450U-E enjoys a long life, before turning the power on double-check ALL connections by referring to this User Manual. CAUTION To comply with FCC RF Exposure requirements in section 1.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Manufacturer Model Number Coax Kit Net ELPRO UDP400-3 Includes 3m Cellfoil 1dB Gain ELPRO UDP400-5 Includes 5m Cellfoil Unity Gain ELPRO BU-3/400 CC10/450 2.5dB Gain ELPRO BU-6/400 CC10/450 5.5dB Gain ELPRO YU3/400 CC10/450 3.5dB Loss ELPRO YU6/400 CC10/450 6.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 2. Operation is authorized by the radio frequency regulatory authority in your country on a non-protection basis. Although all care is taken in the design of these units, there is no responsibility taken for sources of external interference. Systems should be designed to be tolerant of these operational delays. 3.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual CHAPTER 1 - INTRODUCTION ................................... 7 1.0 N ETWORK TOPOLOGY ........................................... 7 Access Point vs. Client .............................................7 Bridge vs Router .......................................................9 1.1 G ETTING S TARTED Q UICKLY ................................ 10 CHAPTER 2 - INSTALLATION .................................. 11 2.0 G ENERAL ..............
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 4.6 N ETWORK DIAGNOSTICS ..................................... 64 Ping ................................................................................ 64 4.7 IO DIAGNOSTICS ................................................ 65 Modem Module Information Registers ............................. 65 Expansion I/O Diagnostic/Error Registers ........................ 66 4.8 MONITOR R ADIO C OMMS .................................... 67 4.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual CHAPTER 1 - INTRODUCTION The 450U-E Industrial 802.11 based Wireless Ethernet module provide wireless connections between Ethernet devices and/ 450U-E, 5 Watt max power The 450U-E is a fixed frequency wireless transceiver that operates in the 360MHz to 512 MHz frequency communications band. There are various frequency bands available depending on the model purchased.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Figure 2 AP-Client2 The second diagram shows an existing LAN being extended using 450U-E . In this example, the Access Point is configured at the LAN end - although the wireless link will still work if the Client is at the LAN end. An Access Point can connect to multiple Clients. In this case, the Figure 3 Multi Client 450U-E Clients, which do not have direct reliable radio paths.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Bridge vs Router Each 450U-E when configured as a bridge uses a single IP address for Ethernet and Wireless connections. A Bridge connects devices within the same Ethernet network - for example, extending an existing Ethernet LAN. Figure 5 - Bridge A Router The IP addresses for the Ethernet and the Wireless sides must be different.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual If more than two routers are required within the same radio network, then routing rules may need to be configured (refer to section 3.10 IP Routing more details). There is no limit to the number of Bridges in the same network - although there is a limit of 128 Client units linked to any one Access Point. Figure 8 - Multi Router 1.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual CHAPTER 2 - INSTALLATION 2.0 General The 450U-E modules are housed in a rugged aluminium case, suitable for DIN-rail mounting. Terminals will accept wires up to 2.5 mm2 (12 gauge) in size. All connections to the module must be SELV (Safety Extra Low Voltage). Normal 110-250V mains supply must not be connected to any terminal of the 450U-E module. Refer to Section 2.2 Power Supply .
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Antennas Antennas can be either connected directly to the module connectors or connected via 50 ohm coaxial cable (e.g. RG58 Cellfoil or RG213) terminated with a male SMA coaxial connector. The higher the antenna is mounted, the greater the transmission range will be, however as the length of coaxial cable increases so do cable losses.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Directional antennas. Directional antennas can be Yagi antenna with a main beam and orthogonal elements. Directional radome, which is cylindrical in shape. Parabolic antenna. A directional antenna provides high gain in the forward direction, but lower gain in other directions. This may be used to compensate for coaxial cable loss for installations with marginal radio path.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 13.8VDC 24VDC Quiescent 120mA 70mA TX @500mW 400mA 220mA TX @ 5W 1.2 - 1.5Amps 550mA - 650mA A Ground Terminal is provided on the back of the module. This Terminal should be connected to the Main Ground point of the installation in order to provide efficient surge protection for the module (refer to the Installation Diagram) 2.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual RS485 is a multi-drop communication link or bus that can span relatively large distances (up to 1.2Km (4000ft)) using a balanced differential paired cable. It is recommended that the cable be shielded or twisted pair to reduce potential RF Interference. An RS485 network should be wired as indicated in the diagram below and terminated at each end of the network with a 120-ohm resistor.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 2.4 Input/Output Connections The 450U-E has a single physical on-board I/O channel that can be configured as either a Digital or an Analog via the web interface. The Digital channel can act as an input or an output. It can be monitored, set remotely, or alternatively used an output for a communications alarm status. If more I/O is required, you can add 115S serial expansion I/O modules via the RS232 or RS485 ports. See section 3.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Digital Input When used supports voltage free contact connection such as a mechanical switch or a NPN transistor device such as an electronic proximity switches. Contact wetting current of the input is approximately 5mA and is provided to maintain reliable operation for driving relays. The digital input is activated by connecting between the "IO" and M" terminals.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual CHAPTER 3 - OPERATION 3.0 Start-up Access Point Start-up Normal module startup time is approximately 1 minute and 20 Seconds from when first powered on to where you can connect to the IP address. When the Access Point (AP) has completed its startup process it will immediately begin broadcasting periodic messages, called beacons on the configured channel using the default beacon interval time of 15 seconds.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual LED Indication The following table details the status of the indicating LEDs on the front panel for all operating conditions.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 3.1 Radio Operating Parameters Frequency Bands The radios will operate within the range 360-512MHz; however the radio must be factory set to one of the 20MHz frequency bands shown below. Care must be taken when ordering to select the correct band for your locale as the frequency cannot be configured outside of its band. The following Frequency bands are available.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 3.2 Initial Connection The 450U-E has a built-in web server, for configuration and diagnostics. The preferred web browser is Microsoft® internet explorer version 7 or greater. This program is shipped with Microsoft windows or may be obtained freely via the Microsoft® website or Google chrome which is also downloadable from the web . Other browsers may not be fully compatible on all beta web pages.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Set the RUN/SETUP Switch to the SETUP position. This will start the 450U-E with a default Ethernet IP address, subnet mask, gateway IP address and the radio will be disabled. The default Ethernet address will be within the IP range 192.168.0.1XX where XX is the last two digits of the serial number and should be shown on the label on the back of the module.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Locale Configuration When connecting to the module for the first time (new or factory defaulted module) you will need to configure the model Locale and a number of other radio configuration parameters before the modems can be used, these include Transmit and Receive Frequency the channel step size and the Transmit Power level as per the country regulation.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 3.3 Quickstart Figure 25 - Quick Start The Quick Start Configuration option is designed to guide you through the configuration process with minimal effort. You can access it any time by selecting it from the right hand menu. This is a simple first stage configuration tool that will help configure the basic parameters that are needed to get a connection between two modules.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Default Gateway - This is the address that the device will use to forward messages to remote hosts that are not connected to any of the local bridged network (Ethernet or Wireless). This is only required if the wired LAN has a Gateway unit which connects to devices beyond the LAN - for example, Internet access. If there is no Gateway on the LAN, set to the same address as the Access Point - that is, the efer to section 3.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Note: If making changes to a remote module via the radio link make sure all changes are compliant and accurate before Changes and R top the radio link from working and will require a hard wire connection to change back. Care should be tken when connecting the modem to existing Networks - When configured as a Bridge (default), all broadcast messages appearing at its wired Ethernet port will be transmitted over the radio.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual section 3.6 below for details) Device Mode Used to select Bridge or Router mode. IP addresses and Netmasks are required for the Ethernet and Wireless interfaces. By default this is set to Bridge. Bridge STP Checking this box enables Spanning Tree protocol in bridged networks. See to section 0.0 Bridge STP (Spanning Tree Obtain IP Address Automatically Checking this item enables DHCP client on the 450U-E.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Router Operation (Routed Network) A router joins separate IP sub-networks together. The router has different IP addresses on its wired and wireless ports, reflecting the different IP addresses of the separate Ethernet sub networks. All of the devices in these separate networks identify the router by IP address as their gateway to the other network.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual WEP (128 bit) WEP128 (Wired Equivalent Privacy) encryption is the weakest encryption method, defined by the original IEEE802.11 standard and uses a 104bit key with a 24bit initialization vector to give a 128bit WEP encryption level. WEP is not considered an effective security scheme, and should only be used if it is necessary to interoperate with other equipment which does not support more modern encryption methods.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 3.7 Radio Configuration Figure 33 - Radio Config The Radio Configuration page is where configuration parameters associated with the radio can be adjusted or configured. The first time out of the box configuration will run a configuration wizard that will step you through some radio questions that will allow you to select radio configuration for your country of operation and license.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Receive Frequency The Frequency that you wish to configure for the radio Receiver. Frequency selection will be in multiples of the frequency step configured in the previous parameter. E.g. 450.00500, 450.01000, 450.01500, 450.02000, etc. for 5Khz or 450.00625, 450.01250, 450.01875, 450.02500, etc. for 6.25KHz frequency step size.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 3.8 Serial The Serial page allows configuration of the onboard serial ports. The 450U-E has two ports, one RS-232, and one RS485 port which are used for serial communications with other devices. These ports are completely independent of the other and can be configured for different functions even utilised at the same time.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Save Changes and Activate Destination Register Enter the starting I/O register number in the destination device that the Modbus mapping will transfer I/O to/from. Device ID Comms Fail Register Enter the onboard local I/O Register number to store the communication status for the specified mapping.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Serial Gateway Port Type Select Serial Gateway from the drop down list. Data Rate Serial Data Rate will need to be configured to match that of the serial device that is connected and communicating via the port. Baud rates available from 110 to 230400 baud. Data Format Serial Data Format defines the number of data bits, parity and start/stop bits that is used to communicate with the serial device.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual communicate with the serial device. Flow Control Flow Control is used by some serial devices to regulate the flow of data by turning on/off flags that are used to tell the connected serial devices to start or stop transmitting data. The RS232 supports CTC/RTS hardware flow control. Response Timeout This is the time the TCP/RTU Converter waits for a response from the slave before sending the next poll. TCP Port Fixed to 502.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Local Register (501) specifies a general purpose Bit Storage area in the local module (Unit B). I/O Count (8) specifies that it is passing 8 I/O points. Function Code 02: Read Discretes specifies the standard Modbus function code to read a digital input. Destination Register (501) specifies the register location on the remote Modbus RTU Slave (Unit A).
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Important Notes: All Access Points must be configured on the same radio frequency. Specify SSID for AP/STA modes. SSID and Encryption is not inherited from the main network page. Each WDS interface can be configured with a different encryption algorithm; however each side of a single WDS link must specify the same encryption algorithm and keys.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual One of the most common uses for WDS is to extend the range of the wireless network using repeaters. The diagram in Figure 40 above illustrates a simple example where the four Access Points are all at fixed locations (each of the Access Points could, of course, have one or more client/stations connected).
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual The configuration for Site B is shown below in Figure 43. The WDS is configured with a Virtual Access Point for the virtual clients configured at Sites A & C. The Encryption Method and key are configured the same as the main network for simplicity. Figure 43 - Site B WDS Configuration 2 The WDS configuration for Site A & Site C will be exactly the same as Site B except the Connection Mode will need to be .
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual The above network diagram illustrates a situation where routing rules may need to be configured. In this example, the 450U-E clients need only specify the Access Point as their default gateway (i.e. they require no routing rules to be configured).
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 3.11 Filtering Figure 47 - Filtering The 450U-E has a filtering feature to help reduce unnecessary wireless transmissions and enhance security. The 450U-E may be configured to reject or accept messages to and from certain Addresses. To accept wireless . Filtering applies only to messages appearing at the wired Ethernet port of the configured 450U-E.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Filter Example Figure 48 - Filtering Example Device B needs to communicate with Device E via modems C & D. The Filtering requires that Modem C has Device B in its Whitelist , any traffic from Device E will be passed back into the LAN via Modem C because the destination matches the IP for device B. This works because Device B is a Modbus Master and it initiates all communications.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Blacklist will prevent all listed devices from accessing the module and using the radio link. Whitelist will allow devices with the MAC addresses listed to communicate with the module and utilize the radio link. All other devices are blocked. Add Entry Add a row to the table of Mac Address filter rules Delete Entry Delete the currently selected MAC address filter rule. Enable Check to enable the rule.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual has a reduced throughput compared with other Ethernet modems it is very important that any unnecessary traffic is not broadcast over the radio, therefore it is highly recommended that the ARP filters are enabled and configured. what is required is to add the IP address for all remote modems and any device that is connected to these remote radios in the ARP filter table.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Figure 50 - Modbus TCP Client Mapping Modbus TCP Client Mappings: Local Register Enter the starting onboard I/O register number that the specified Modbus Master transaction will transfer I/O to/from. I/O Count Specify the number of consecutive I/O registers to be transferred for the specified transaction. Function Code Specify the Modbus Function Code for the transaction.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Enabling the Modbus TCP Server within Unit B provides a register location for the polled values from Unit C to be stored. It will also allow an external Modbus TCP Client (DCS or Scada) to monitor the stored I/O values from units A & C.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 3.13 Input/Output Configuration The 450U-E has a single physical on-board I/O channel that can be configured as either a Digital or an Analog via the web interface. The Digital channel can also act as an input or an output.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Analog Input configuration parameters Name Configure a descriptive name for the Analog input. Zero This parameter is used to configure the scale of the analog input. This is the starting variable (in counts) when the analog input is at the bottom or zero scale. Default is 8192 which equates to the number of raw counts in the register when the input is at the zero or minimum value, i.e. 0mA on the analog input.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Fail-Safe State The state that the output will be set to if countdown has elapsed. If the Failsafe state is enabled (ticked), the LED and the digital output will be turned ON. If the Failsafe state is disabled (unticked), the LED and the digital output will be turned OFF. Digital Input Configuration of the I/O channel as a Figure 55- Input Mode If you wish to adjust the digital input parameters see below for details.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Digital Input Bits Registers Purpose 10001 Local Digital Input Register 10002 Setpoint status Register for Analog Input 1 10003 Setpoint status Register for VSupply 10021 - 10500 I/O Space for locally attached 115S expansion I/O modules. 20 registers per module address. Max 24. 10501 - 12500 General Purpose Bit Storage storage.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Analog input 1 will be at register location 30321 ((16*20) +30001) See Appendix D - Expansion I/O Registers When adding expansion I/O modules to the 450U-E, there are two inbuilt registers used to indicating the communication status of the module. ocated at register location 10020 + offset value.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Figure 60 - Invalid Register State All registers within the module can have various states depending on what type of register it is and what sort of value it holds, a typical analog range is between 0 and 65535 and a digital can be 0 or 1. Registers can also have so does not hold a value but more a non-value or null. as a shown above. Any mapping with an invalid register will be inhibited from sending.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Select Operating Mode as Access Point. Enter a System Address (ESSID) string. And record as this will need to be exactly the same for all radios in the example. The Radio Encryption is configured for WPA2 AES and will require an encryption key which will also need to be the same on all radios in the example. Change the IP addresses to 192.168.0.100 Leave the Subnet masks at the default 255.255.255.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual LAN B Configuration All devices on LAN B should be configured so their Gateway IP addresses are configured with the IP address 169.254.102.54 which is the 450U-E Access Point/Router. Access Point Configuration Connect straight through Ethernet cable between the PC and the 450U-E.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Extending range of a network with a Repeater hop Configure units as described in example above. Place the Access Point at the remote intermediate repeater location. Additional repeaters can be added using Wireless Distribution System (WDS) refer Section 3.9 Repeaters (WDS) for further details. Figure 63 - Example Repeaters Rev Version 1.4.0 www.cooperbussmann.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual CHAPTER 4 - DIAGNOSTICS 4.0 Diagnostics Chart LED Indicator Condition Meaning OK GREEN Normal Operation OK RED Solid Factory Default Mode, Supply voltage low or Internal Module Fault OK RED At Power On Boot Loader delay at start-up OK Fast Flash RED / GREEN Module Boot Sequence OK Slow Flash RED / GREEN Module Boot Sequence Radio RX GREEN flash Radio is receiving a valid Elpro 450U-E data frame.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 4.1 Connectivity The Connectivity webpage displays information on the current connection with either the Client or the Access Point depending on how it is configured. Wireless information will display the MAC address, IP address, which interface is being used, the radio data rate, received signal strength (RSSI), authentication status and the inactive time.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual startup. Beacon Interval Shows the Beacon Interval configure on the AP SSID Shows the Access Points SSID 4.2 Throughput Testing Radio Throughput There are a number of throughput estimations that may help to determine the amount of data that can be successfully transmitted through the modems. These throughput estimations are based on perfect radio conditions, i.e.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Iperf Throughput Test A more thorough test is to perform a throughput test which will check the amount of data that can be reliably achieved via the Wireless link. There are a number of software tools that we can use to check the data throughput, i.e. FTP - file transfer protocol, Iperf, Qcheck, etc. bandwidth measurement application that is run on a Laptop or PC at each end of the radio link.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Routes: will display the current IP routes configured in the module. IP statistics: show a number of statistics for each interface TCP/UDP Statistics: shows the number of TCP and UDP connections currently established Memory Statistics: shows the amount of memory available for each function. Serial Statistics: shows the current status of each of the serial ports.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Channel Utilisation Graphs: The Channel Survey screen displays a graph showing the percentage of time that a channel is being utilised by any of the following causes: 1. The connected modem is transmitting. 2. The connected modem is receiving valid data from other Elpro 450U-E modems in the system. 3.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual The third screen shot shows the Channel utilisation for each minute over a one hour period. Each minute is calculated from the running average of the 60 second scan. Figure 70 - Background Noise Minutes The last screen shot shows the running radio background average noise level for each minute over the last 0ne hour period.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual useful for determining if the communications get through after the first retry or it continues to fail TX Acknowledge messages The percentage of time spent transmitting acknowledgment messages from the modem and Broadcast messages. Radio Hold off The percentage of time that the radio has spent holding off from transmitting data, possibly because the channel is busy.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Example Two. In the second example we can see chart one shows the radio is transmitting a large amount of data in the last half of the sixty second scan. We can configure the second chart to read specific information about the radio link which can help us determine what shows that the radio is holding off from transmitting around 36% of the time which is a clear indication that the radio frequency is busy.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Remote IP Address Count / Max Hops back. This is the IP address that you want to Ping This is the number of Ping probes that are send out. You should see this many responses come Interval Wait time between ping requests. Default is 5 seconds and generally will not need to be changed unless using repeaters.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Expansion I/O Diagnostic/Error Registers The 450U-E has a number of diagnostics registers that are allocated for Expansion I/O diagnostic information. Every connected module will have its own diagnostic information which will indicate the module type, error counts, error codes, etc. The Register locations are dynamic with regard to the module address and require an offset to read the correct location.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 4.8 Monitor Radio Comms The Monitor Radio Comms page shows radio communication frames that are received or transmitted by the radio. Note: Comms log will display Elpro 450U-E data frames only. Figure 75 - Monitor Radio Comms Figure 75 - Monitor Radio Comms Comms Comms above shows typical data frames from the communication log screen. Below is a table explaining each of the fields within the data frame. e frame.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Figure 76 Monitor IP Comms 4.10 System Tools The System Tools Page has a number of tools that help maintain the module firmware and configuration. System Log File Shows an event log of the modules operation, used for diagnosing problems. Read Configuration File This option will show the module configuration in XML format. This file can be saved for future reference or backup.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual name (hostname) of the device if you are using DNS. Owner A text field for owner name. Contact A text field for owner phone number, email address etc. Description A text field used for a description of the purpose of the unit. Location A text field used to describe the location of the 450U-E.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Figure 78 - Ping-t This A good test for the network once it is first set up is to use IP address. This gives a good indication of the network s reliability and how responsive it is from point to point. When you enter Ctrl-received-lost percentage. Ip ipconfig can be used to show your current TCP/IP information, including your address, DNS server addresses, adapter type and so on.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual R Route is used when joining two or more different networks together via the 450U-E. Refer to Section 1.1 for more details. When routing from one subnet to another devices on one subnet need to know where to pass the message to get it to the other subnet. This is done one of two ways; Setting up a route within the device which is a lookup table showing a list of subnets and which IP address to use as the Gateway.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual CHAPTER 5 - SPECIFICATIONS Transmitter/Receiver Frequency 360-512MHz (8 x 20MHz bands) Transmit Power Licensed - 5 Watt (+37dBm), Unlicensed Data Encoding 2-FSK, 4-FSK Receiver Sensitivity 25 KHz channel : -99dBm @19,200 baud, -110dBm @ 9600 baud 12.5 KHz channel : -100dBm @9600 baud, -111dBm @ 4800 baud Channel Bandwidths 25 KHz channel 12.5 KHz channel Data Rate 25 KHz channel : 4800 baud, 9600 baud 12.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Embedded Modbus Master/Slave for I/O transfer Security Data Encryption 802.11i With CCMP 128bit AES Support for 802.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Appendix A - Firmware Upgrades You can check the firmware version that is present in the module by viewing the Home webpage of the module. Firmware upgrades should be done locally with a PC connected directly to the module, remote firmware upgrades are not recommended over the radio link due to bandwidth limitations.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual DISKPART> list partition Partition ### Type Size Offset ------------- ---------------- ------- ------- Partition 1 Primary 1910 MB 64 KB You can now format the drive using the diskpart utility. If the or if there is more than one Partition, as indicated in the examples below, follow steps 6 and 7 below to re-configure the drive.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Formatting USB Memory Stick Plug the USB stick in to the PC, select and right click the stick from within Windows Figure 82 - Format USB -selected before pressing the Start button. Figure 83 - Quick Format Upgrade Procedure 1. Prior to performing the upgrade you will need to copy the supplied firmware files to the USB Stick root directory. They should look something like the screenshot shown in Figure 84.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual firmware version has been updated and that all other configuration settings are ok, configuration should not have been changed or erased during this process. DO NOT remove the Flash drive or interrupt the power to the module while this is happening. If the upgrade process is interrupted module could become unserviceable and will need to be returned to ELPRO for repair. Figure 87 - Firmware Update LEDs Web based Upgrade .
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Appendix B - USB Ethernet connection Connecting to the Secondary Ethernet Port To use the secondary Ethernet port you first need to install the USB Driver file, which can be downloaded from our Technical Resource Library at www.cooperbussmann.com/wirelessresources. Save the file in a known location as you will need to find further on in the procedure.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 6. You will probably get a Windows Security alert as the Driver publisher will Figure 93 - Windows Security 7. When successfully installed close the window Figure 94 - Success Now you will then need to open the Network connections window by Connections window open you will see a new Network adaptor called Figure 95 - New Network Adaptor 8. IP address 1.1.1.1 and Subnet Mask 255.255.255.0.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Appendix C - GLOSSARY ACK Acknowledgment. Access Point An access point connects wireless network Stations (or Clients) to other Stations within the wireless network and also can serve as the point of interconnection between the wireless network and a wired network. Each Access Point can serve multiple users within a defined network area. Also known as a base station.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual website has its own specific IP address on the Internet. DSL Digital Subscriber Line Various technology protocols for high-speed data, voice and video transmission over ordinary twisted-pair copper POTS (Plain Old Telephone Service) telephone wires. Encryption key An alphanumeric (letters and/or numbers) series that enables data to be encrypted and then decrypted so it can be safely shared among members of a network.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual connection-oriented services between two nodes on the network. SPX is used primarily by client/server applications. ISDN A type of broadband Internet connection that provides digital service from the customer's premises to the dial-up telephone network. ISDN uses standard POTS copper wiring to deliver voice, data or video.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual facility so that access points can be optimally placed. SSL Secure Sockets Layer. A commonly used encryption scheme used by many online retail and banking sites to protect the financial integrity of transactions. When an SSL session begins, the server sends its public key to the browser.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Appendix D - Expansion I/O Registers Adding 115S Expansion I/O modules to the 450U-E the I/O will automatically be added to the 450U-E modules I/O store. To calculate the register location, add the address of the I/O point from the tables below to the offset. The offset ids calculated by finding the address of the Modbus Slave X 20. E.g1. Digital input #1 on an 115S-11 with address 5 would be: (5x20) +10001 = 10101 E.g2.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 30018 + Offset Modbus Last Error Code for this 115S module. (Appendix E - Modbus Error Codes) 30019 + Offset Modbus Lost Link Counter for this 115S module 30020 + Offset Module type (0x0301) = 769.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 65288 FF08 Memory Parity Error Specialized, use in conjunction with function codes 20 and 21 and reference type 6, to indicate that the extended file area failed to pass a consistency check. 65290 FF0A Gateway Path Unavailable Specialized, use in conjunction with gateways. Indicates that the gateway was unable to allocate an internal communication path from the input port to the output port for processing the request.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Appendix G - External Iperf Test This Appendix shows how to set up and use the Iperf application to test the throughput of Ethernet Modems. Iperf is a tool used to measure the throughput and quality of a network link. Jperf can be used in conjunction with Iperf to graphically display the Iperf data results. This instruction covers both Iperf and Jperf; it does not cover the setup and configuration of the modems.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual This will run a test over the radio link to the Server PC and report back results as seen in Figure 99. These results show the Bandwidth (Throughput) of the test as 19.2 Kbits/sec. Figure 99 - Iperf Results It is recommended that the test be run a number of times to get an average. JPerf Application Jperf is a graphical interface that runs over the top of Iperf. It will display a graph result from the Iperf test. -2.0.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual Appendix H - GNU Free Doc License Version 2, June 1991 patent licenses, in effect making the program Copyright (C) 1989, 1991 Free Software Foundation, proprietary. To prevent this, we have made it clear that Inc. any patent must be licensed for everyone's free use or 51 Franklin Street, Fifth Floor, Boston, MA 02110-1301, not licensed at all.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual a whole at no charge to all third parties under the terms of this License.
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 7. If, as a consequence of a court judgment or allegation of patent infringement or for any other reason (not limited to patent issues), conditions are imposed on you (whether by court order, agreement or otherwise) that contradict the conditions of this License, they do not excuse you from the conditions of this License.