Maintenance Instructions

29
Lower-Left Keep-Out Zone – The Left Keep-Out Zone will prevent the monitor from moving down and
to the left into a specified zone (reference figure 1).
Put the EXM2 system into the Setup Mode (reference Part B of the Operating Instructions section)
Move the monitor to the top right corner of the keep out zone
The Keep-Out Zone should be set within the previously set monitor calibration points. If a Keep-Out
Zone is set outside the intended operating area, operation of the monitor may be unpredictable.
Hold the PRESET button, the press the CLOSE button, and then release both.
When the EXM2 system is taken out of Setup Mode, the monitor will be prevented from moving
below and to the left of this point
H. Stow Position
The Stow Position is a preset position that can be used to bring the monitor into a position
suitable for when the system is powered off. A stow position must be within the allowed travel
area defined by any travel limits or keep-out zones, therefore it is recommended that travel limits
and keep-out zones are set before setting a stow position.
Move the monitor discharge to the desired stow position using the monitor controls.
Put the EXM2 system into the Setup Mode (reference Part B of the Operating Instructions section).
Press and release the stow button to program this as the stow position.
Exit Setup Mode
Move monitor away from programmed stow position and test stow function. See operation
instructions step A, stow, on page 22.
!
Warning! Water SHOULD NOT be flowing while stowing the monitor.
Figure 1: Keep-Out Zones