Maintenance Instructions

17
Position Feedback Display –
Using the Position Display template located at www.elkhartbrass.com,
drill the two 11/64” holes as shown through the panel intended for
mounting the display.
Mount the Position Feedback Display using two (2) 6-32 x ½” fasteners
secured with blue Loctite 242 or equivalent. Torque to
50-60 in-lbs (5.6-6.8 Nm).
Connect plug 2 to the appropriate CAN line.
Supply power to the Position Feedback Display by
connecting plug 1 leads red (+) and black (-) to an
appropriate power source.
Install a 1 Amp fuse into the positive red (+) power lead of
the Position Feedback Display for a 12V system (1/2 Amp
for 24V system).
Termination requires CAN splitter (P/N 24196000) and
CAN termination plug (P/N 24197000) not included.
Non-termination requires CAN splitter (P/N 24196000)
not included.
Refer to the respective figures for information on the
plugs’ pins.
!
Important: Ensure horizontal & vertical calibration is correct or display may not
accurately show position. See Installation Step 3: Calibrate the EXM2 System.
Electric Actuated Unibody Valve – E14X/E16X
Install the valve into the water supply line.
Supply power to the valve by connecting the red and black leads coming from the valve -1 plug to an
appropriate power source, red (+), black (-). Do not power valve until ready to calibrate it (see page 21).
Install a 30 Amp fuse to the positive power lead of the valve for a 12V system (20 Amp for 24V system).
Connect plug 2 to the appropriate CAN line.
Termination requires no additional items as CAN lead contains termination. Non-termination requires
CAN splitter (P/N 24196000, not included) and removal of terminated CAN lead and installation of
unterminated lead. Unterminated lead and instructions are included with valve.
Valve Plug
Actuator Plug
E14X (E16X for EB6D)
Valve Plug 1
1
2
2