Commercial Electro Boilers Large Specifications Sheet

07/22/2010 BL508
Specification Data Sheet - TS Large Electro-Boiler
TM
Specifi cations subject to change without notice,
all rights reserved.
WATER FLOW REQUIREMENTS (MINIMUM 4 GPM WATER FLOW THROUGH BOILER)
Model
Water Temperature Rise
Flow - 20° F/6° C
Head Loss
Flow - 30° F/11° C
Head Loss
Flow - 40° F/16° C
Head Loss
gpm lpm ft m gpm lpm ft m gpm lpm ft m
EB-C*-18-60 6.14 23.24 .002 .0006 4.09 15.48 .001 .0003
3.07
11.62
.0008 .0002
EB-C*-24-60 8.19 31.00 .002 .0006 5.46 20.66 .001 .0003 4.09 15.48 .0008 .0002
EB-C*-30-60 10.23 38.72 .06 .018 6.82 25.81 .07 .021 5.11 19.34 .07 .021
EB-C*-36-60 12.28 46.49 .01 .003 8.19 31.00 .004 .001 6.14 23.24 .002 .0006
EB-C*-45-60 15.35 58.10 .02 .006 10.23 38.72 .01 .003 7.67 29.03 .01 .003
EB-C*-54-60 18.43 69.77 .02 .006 12.28 46.49 .01 .003 9.21 34.86 .01 .003
EB-C*-18-48 6.14 23.24 .002 .0006 4.09 15.48 .001 .0003
3.07
11.62
.0008 .0002
EB-C*-36-48 12.28 46.49 .01 .003 8.19 31.00 .004 .001 6.14 23.24 .002 .0006
EB-C*-54-48 18.43 69.77 .02 .006 12.28 46.49 .01 .003 9.21 34.86 .01 .003
EB-C*-27-20 9.21 34.86 .01 .003 6.14 23.24 .002 .0006 4.60 17.41 .001 .0003
EB-C*-40-20 13.82 52.32 .01 .003 9.21 34.86 .01 .003 6.91 26.16 .003 .0009
EB-C*-27-24 9.21 34.86 .01 .003 6.14 23.24 .002 .0006 4.60 17.41 .001 .0003
EB-C*-40-24 13.82 52.32 .01 .003 9.21 34.86 .01 .003 6.91 26.16 .003 .0009
EB-C*-31 10.75 40.69 .06 .018 7.16 27.10 .07 .021 5.37 20.33 .07 .021
EB-C*-36 12.28 46.49 .06 .018 8.19 31.00 .06 .018 6.14 23.24 .07 .021
EB-C*-40 13.65 51.67 .01 .003 9.10 34.44 .01 .003 6.82 25.81 .003 .0009
EB-C*-44 15.01 56.82 .02 .006 10.01 37.89 .01 .003 7.50 28.39 .01 .003
* = A or O
Result below minimum required fl ow of boiler, make sure system design provides minimum fl ow requirements of boiler.
Note: Head Loss based on 110° F return temperature.
ELECTRIC SUPPLY
Model Volts Watts Amps kW Phase Btu/h CB
EB-C*-18-60 600 18,000 17 18 3-60 61,000 20
EB-C*-24-60 600 24,000 23 24 3-60 81,600 30
EB-C*-30-60 600 30,000 29 30 3-60 102,000 45
EB-C*-36-60 600 36,000 35 36 3-60 123,000 45
EB-C*-45-60 600 45,000 44 45 3-60 153,000 60
EB-C*-54-60 600 54,000 52 54 3-60 184,000 70
EB-C*-18-48 480 18,000 22 18 3-60 61,434 30
EB-C*-36-48 480 36,000 44 36 3-60 122,868 60
EB-C*-54-48 480 54,000 65 54 3-60 184,302 80
EB-C*-27-20 208 27,000 75 27 3-60 92,151 100
EB-C*-40-20 208 40,500 113 40.5 3-60 138,226 150
EB-C*-27-24 240 27,000 65 27 3-60 92,151 80
EB-C*-40-24 240 40,500 98 40.5 3-60 138,226 125
EB-C*-31 240 31,500 131 31.5 1-60 107,509 100 + 80
EB-C*-36 240 36,000 150 36 1-60 122,868 100 + 100
EB-C*-40 240 40,000 167 40 1-60 136,000 125 + 125
EB-C*-44 240 44,000 183 44 1-60 150,000 125 + 125
CLEARANCES
MINIMUM CLEARANCE FROM SUGGESTED MINIMUM
COMBUSTIBLE SURFACES SERVICE CLEARANCE
BACK 0 INCH 0 MM 0 INCH 0 MM
LEFT 1 INCH 25 MM 16 INCHES 406 MM
RIGHT 1 INCH 25 MM 6 INCHES 152 MM
FRONT 1 INCH 25 MM 24 INCHES 610 MM
TOP 1 INCH 25 MM 24 INCHES 610 MM
BOTTOM REQUIRED CLEARANCE - 16 INCHES/406 MM
SHIPPING WEIGHT
Model Weight
(lbs)
Model Weight
(lbs)
EB-C*-18-60 225 EB-C*-27-20 227
EB-C*-24-60 227 EB-C*-40-20 233
EB-C*-30-60 230 EB-C*-27-24 227
EB-C*-36-60 232 EB-C*-40-24 233
EB-C*-45-60 233 EB-C*-31 230
EB-C*-54-60 237 EB-C*-36 232
EB-C*-18-48 225 EB-C*-40 233
EB-C*-36-48 232 EB-C*-44 233
EB-C*-54-48 237

Summary of content (2 pages)