Datasheet

03/24/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 3
Trip�block�Standard�8-32A
Part�no. PKE-XTU-32
Article�no. 121726
Program
Accessories Trip blocks
Setting range of overload releases I
r
A 8–32
Expansions without communication capability
Function With overload release
Rated uninterrupted current I
u
A 32
Motor rating
AC-3
220/230 V P kW 7.5
400 V P kW 15
440 V P kW 15
500 V P kW 22
690 V P kW 30
For use with PKE32 basic device
Motor output/rated motor current
Motor
power
AC-3
rated
motor
current
220, 230
240 V
380, 400,
415 V
440 V 500 V 660, 690 V
P [kW] I [A] I [A] I [A] I [A] I [A]
2.2 8.7
3 11.5
4 14.8 8.5
5.5 19.6 11.3 10.2 9
7.5 26.4 15.2 13.8 12.1 8.8
11 21.7 19.8 17.4 12.6
15 29.3 26.6 23.4 17
18.5 28.9 20.9
22 23.8
30 32
Approbationen
UL approval Yes
CSA approval Yes
Product Standards UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
NA Certification Request filed for UL and CSA
Specially designed for NA No
General
Standards IEC/EN 60947, VDE 0660, UL 508, CSA C 22.2 No. 14
Climatic proofing Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature °C
Storage °C -20 - +80
Open °C -20 - +55
Enclosed °C -20 - +40
Direction of incoming supply as required
Degree of protection
Device IP20
Main�conducting�paths
Rated impulse withstand voltage U
imp
V
AC
6000
Overvoltage category/pollution degree III/3
Rated operational voltage U
e
V
AC
690
Rated uninterrupted current = rated operational current I
u
= I
e
A 32
Rated frequency f Hz 40 - 60
Current heat loss (3 pole at operating temperature) W 6
Motor switching capacity kA
rms

Summary of content (3 pages)