Installation Manual

www.eaton.com IM02601001E 10-5
Setup on the Web Server Pages
Alarm Triggers - Out of Limits
You can use the Out of Limits Triggers page to set high and low cautionary and critical
alarms for a wide range of electrical parameters (see page “Triggers” on page 9-12 for a
complete list of parameters). For a detailed discussion of triggers, see page “Triggers” on
page 9-12. Triggers can cause the following actions:
An event is added to the event log, and can be seen in the Events page.
The event indicator at the top of each meter page ashes.
The event information is sent via SNMP as a trap. SNMP is a standard protocol used
to monitor and manage devices on a network. The trap protocol allows a node (such
as the meter) to send a message to SNMP monitoring/management software without
being queried.
The event information is sent as an RSS (Atom) feed. You can subscribe to the me-
ter’s Atom feed by clicking the RSS icon at the top, right side of the page. In the RSS
feeds page that appears click the Subscribe to this feed link. In the dialog box that
appears, click the Subscribe button.
RSS Feeds Page, Showing Subscription Dialog Box
The RSS feed subscription appears in Internet Explorer under Favorites in the Feeds
tab. Each event is shown as an individual feed. Clicking a feed launches the RSS
feeds page, from which you can view event details. Clicking an event on the RSS
feeds page launches the meter’s Home web page.
The event information can be sent to one or more recipients as an email message.
RSS Icon