Installation Manual

www.eaton.com IM02601001E 10-19
Setup on the Web Server Pages
Relay Output Setup Edit Page
Pulse Output (Solid State Relay Contacts) / Digital Input Card
This option card has:
Four pulse outputs via solid state contacts.
Four wet/dry contact sensing digital inputs.
Accumulators in the software count the pulses of the Inputs and Outputs (the accumula-
tors are shown on the I/O page. Typically, this card is used in a sub-metering application
where a pulse output is needed. The Input Accumulators (which perform the same func-
tion as the inputs on the relay card) allow you to count the pulses from another device, for
example, a KYZ module or another meter. The Output Accumulators allow you to count
the pulses being output by the card.
For inputs, you can congure up to four inputs for your card, and assign a Label, Open
State Label, and Closed State Label for each. You can also set labels and other in-
formation for Accumulators for the Inputs. Triggers can be set as Disabled, Open to
Close, Close to Open, or on Any Transition.
Accumulators have both a compression factor and a device output ration setting. The
divisor is a compression factor for the accumulator, and you can select 1, 10, 100, 1000,
10000, and 100000. For example, if you choose a Divisor of 10, each time 10 state
changes occur, the accumulator count will increment by 1. The Accumulator Kt is the
output ratio from the device that is being input into the meter. For example, if you have a
KYZ module that is outputting a pulse every 1.8 kWh, you would set the Accumulator Kt
to be the value of the KYZ; in this case either 1.8 or a ratio of that number.