1.1
Switching Devices
Safety Switches
Product Selection
Fusible
Non-Fusible 277/480–600V
Notes
1
Contact the Safety Switch Flex Center (1-888-329-9272 or FlexSwitches@eaton.com) for copper neutrals.
2
NEMA 12 enclosures (30–600A) can be field modified to meet NEMA 3R rainproof requirements when a factory provided drain hole is opened.
3
Contact the Safety Switch Flex Center (1-888-329-9272 or FlexSwitches@eaton.com) for availability of this product.
4
Use three-pole catalog numbers below for 600 Vac, 250 Vdc maximum applications. For 600 Vdc, see note
3
.
5
DC rating for 400–600A switches is 250V.
6
For two-pole applications, use outside poles of three-pole switch.
System
Ampere
Rating
Fuse
Class
Provision
Maximum Horsepower Ratings with Time Delay Fuses
NEMA 12 Enclosure
Industrial, Dust-Tight
Catalog Number
NEMA 4X Enclosure
Corrosion-Resistant,
Stainless Steel
Catalog Number
AC
DCStandard Fuse Time Delay
Single-
Phase
Three-
Phase
Single-
Phase
Three-
Phase 250V 600V
Three-Pole—240 Vac, 250 Vdc (Suitable for Service Entrance Use with a Neutral Kit Installed)
1
30 H 1-1/2 3 — 7-1/2 — — DH321FDK-GCL
2
DH321FWK-GCL
60 H 3 7-1/2 — 15 — — DH322FDK-GCL
2
DH322FWK-GCL
100 H 7-1/2 15 — 30 20 — DH323FDK-GCL
23
200 H 15 25 — 60 40 — DH324FDK-GCL
2
DH324FWK-GCL
400 H — 50 — 125 50 — DH325FDK-GCL
2
DH325FWK-GCL
600 H — 75 — 200 — — DH326FDK-GCL
2
DH326FWK-GCL
Two-Pole—480 Vac—600 Vac or DC
5
(Suitable for Service Entrance Use with a Neutral Kit Installed)
1
30 H 7-1/2 10 — — — 15 DH261FDK-GCL
2
DH261FWK-GCL
60 H 20 25 — — — 25 DH262FDK-GCL
23
or
4
100 H 30 40 — — — 25 DH263FDK-GCL
23
or
4
200 H 50 50 — — — 50 DH264FDK-GCL
2
DH264FWK-GCL
Three-Pole—480 Vac—600 Vac, 250 Vdc (Suitable for Service Entrance Use with a Neutral Kit Installed)
1
30 H 7-1/2 10 15 20 — — DH361FDK-GCL
2
DH361FWK-GCL
60 H 20 25 30 50 — — DH362FDK-GCL
2
DH362FWK-GCL
100 H 30 40 60 75 — — DH363FDK-GCL
2
DH363FWK-GCL
200 H 50 50 125 150 — — DH364FDK-GCL
2
DH364FWK-GCL
400 H — — 250 350 — — DH365FDK-GCL
2
DH365FWK-GCL
600 H — — 400 500 — — DH366FDK-GCL
2
DH366FWK-GCL
System
Ampere
Rating
Fuse
Class
Provision
Maximum Horsepower Ratings
NEMA 12 Enclosure
Industrial, Dust-Tight
Catalog Number
NEMA 4X Enclosure
Corrosion-Resistant,
Stainless Steel
Catalog Number
AC
DCStandard Fuse Time Delay
Single-
Phase
Three-
Phase
Single-
Phase
Three-
Phase 250V 600V
Three-Pole—480 Vac—600 Vac, 250 Vdc
6
(Suitable for Service Entrance use with a Neutral Kit Installed)
1
30 — 7-1/2 10 20 30 5 — DH361UDK-GCL
2
DH361UWK-GCL
60—2025506010—DH362UDK-GCL
2
DH362UWK-GCL
100 — 40 50 75 100 20 — DH363UDK-GCL
2
DH363UWK-GCL
200 — 50 50 125 150 40 — DH364UDK-GCL
2
DH364UWK-GCL
400 — — — 250 350 50 — DH365UDK-GCL
2
DH365UWK-GCL
600 — — — 400 500 — — DH366UDK-GCL
2
DH366UWK-GCL
DH361FWK-GCL