Switching Devices
Safety Switches
Dimensions
Approximate Dimensions in Inches (mm)
Mounting Dimension Requirements in Inches (mm)
Mounting Dimension Requirements Line Lug Data
Dimension A = The required wire bending spacing selected
from Article 430.10 of the National Electrical Code.
Dimension B = Minimum or maximum depth from inside of
flange holding operating handle to panel where disconnect
switch is mounted (variable 7 to 16 inches).
Disconnect Switch Type A B C D E F G
30A and 60A non-fusible See dimensions
below
See dimensions
below
1.56 (39.6) 0.96 (24.4) 4.00 (101.6) 3.50 (88.9) 7.12 (180.8)
30A and 60A fusible 1.56 (39.6) 0.96 (24.4) 4.00 (101.6) 3.50 (88.9) 9.75 (247.7)
100A non-fusible 1.75 (44.5) 1.10 (27.9) 5.50 (139.7) 3.38 (85.9) 7.12 (180.8)
100A fusible 1.75 (44.5) 1.10 (27.9) 5.50 (139.7) 3.38 (85.9) 11.88 (301.8)
200A non-fusible and fusible 3.34 (84.8) 0.63 (16.0) 8.50 (215.9) 1.84 (46.7) 15.50 (393.7)
Disconnect Switch Size Wire Size
30A #2–14 Cu/Al
60A #2–14 Cu/Al
100A 1/0–14 Cu/Al
200A 250 kcmil–#6 Cu/Al