Datasheet

DATASHEET - DE11-121D4FN-N20N
Variable speed starters, Rated operational voltage 230 V AC, 1-phase, Ie
1.4 A, 0.25 kW, 0.33 HP, Radio interference suppression filter
Part no. DE11-121D4FN-N20N
Catalog No. 180650
Eaton Catalog No. DE11-121D4FN-N20N
Delivery program
Product range Variable speed starter
Part group reference (e.g. DIL) DE11
Rated operational voltage U
e
230 V AC, 1-phase
240 V AC, single-phase
Output voltage with V
e
U
2
230 V AC, 3-phase
240 V AC, 3-phase
Mains voltage (50/60Hz) U
LN
V 200 (-10%) - 240 (+10%)
Rated operational current
At 150% overload I
e
A 1.4
Note Rated operational current at an operating frequency of 16 kHz and an ambient air
temperature of +50°C
Assigned motor rating
Note for normal internally and externally ventilated 4 pole, three-phase asynchronous
motors with 1500 rpm
-1
at 50 Hz or 1800 min
-1
at 60 Hz
Note Overload cycle for 60 s every 600 s
Note at 230 V, 50 Hz
150 % Overload P kW 0.25
150 % Overload I
M
A 1.4
Note at 220 - 240 V, 60 Hz
150 % Overload P HP 0.33
150 % Overload I
M
A 1.4
Degree of Protection IP20/NEMA 0
Interface/field bus (built-in)
OP-Bus (RS485)/Modbus RTU, CANopen
®
Fitted with Radio interference suppression filter
Frame size FS1
Connection to SmartWire-DT yes
in conjunction with DX-NET-SWD3 SmartWire DT module
Technical data
General
Standards Specification for general requirements: IEC/EN 61800-2
EMC requirements: IEC/EN 61800-3
Safety requirements: IEC/EN 61800-5-1
Certifications CE, UL, cUL, RCM
Production quality RoHS, ISO 9001
Climatic proofing ρ
w
% < 95%, average relative humidity (RH), non-condensing, non-corrosive
Ambient temperature
operation (150 % overload) ϑ °C -10 - +60
Storage ϑ °C -40 - +70
Radio interference level
Radio interference class (EMC) C1 (for conducted emissions only), C2, C3, depending on the motor cable length, the
connected load, and ambient conditions. External radio interference suppression
filters (optional) may be necessary.
Environment (EMC) 1st and 2nd environments as per EN 61800-3
maximum motor cable length I m C1 ≤ 5 m
12/21/2018 Eaton 180650 ED2018 V51.0 EN 1 / 6

Summary of content (6 pages)