Quick-Start-Guide PowerXL™ DE1 Quick-Start-Guide AP040092EN Title DE1 Quick-Start-Guide Product PowerXL™ DE1 Level 2 1 – Fundamental – No previous experience necessary 2 – Basic – Basic knowledge of Variable Speed Starter recommended 3 – Advanced – Basic knowledge of Variable Speed Starter required 4 – Expert – Good experience recommended 01/2015 AP040092EN
Content Danger! - Dangerous electrical voltage!........................................................................................................ 3 Disclaimer ...................................................................................................................................................... 4 General .......................................................................................................................................................... 5 Environmental conditions ....
Danger! - Dangerous electrical voltage! Disconnect the power supply of the device. Ensure that devices cannot be accidentally restarted. Verify isolation from the supply. Cover or enclose any adjacent live components. Follow the engineering instructions (AWA/IL) for the device concerned. Only suitably qualified personnel in accordance with EN 50110-1/-2 (VDE 0105 Part 100) may work on this device/system.
Disclaimer The information, recommendations, descriptions, and safety notations in this document are based on Eaton’s experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in the applicable Terms and Conditions for Sale of Eaton or other contractual agreement between Eaton and the purchaser.
General This Quick-Start-Guide gives a short introduction into the handling of the Variable Speed Starters DE1 (VSS). It is assumed that the measures described in the installation leaflet, which is supplied with the product, have been taken into account. Variable Speed Starter DE1 IL040005ZU Configuration module DXE-EXT-SET IL040020ZU Please see manual MN040011EN for more detailed information. Variable Speed Starters can be used for a plurality of applications as it comes out of the box.
Environmental conditions With the exception of DE1-34016…… all sizes of the Variable Speed Starter DE1 can be used in the temperature range between -10 °C and +60 °C without any derating. Derating for DE1-34016…. see manual MN040011EN. VSS can be mounted on a mounting plate or on a top hat rail (DIN rail). Please note that the devices DE1-121D4… and DE1-122D3 may have a max deviation of ± 5 ° from the vertical. For all other DE1 devices a deviation of up to 90 ° (= horizontal mounting) is permitted.
In default the Variable Speed Starter trips once a fault is detected and has to be reset. It is also possible to activate the function “Auto-Restart”, which resets the VSS automatically up to 9 times (number of Resets can be selected) and restarts the device. This function may only be activated when an automatic restart doesn’t lead to a dangerous situation for people and goods.
Status LEDs The LEDs on the front of the Variable Speed Starter indicate operating status and faults Run (green) o OFF = Fault or DE1 not supplied o Flash every 2 s = Ready, no start signal (FWD/REV) o ON = RUN Status (red) o OFF = DE1 OK o Flash every 0,5 s: Undervoltage e.g.
Configuration module DXE-EXT-SET DXE-EXT-SET is an optional module, which can be plugged onto the front of the Variable Speed Starter. It is used for simple modification of selected parameters without using a PC or keypad. All sizes of DE1 use the same module. It can be plugged and unplugged when live. The module is not necessary to operate DE1 after a parameter change. It can be removed after use. The settings are “stored mechanically” by the position of the switches and potentiometers.
Designation Settings Function Ramp Selection of ramp times. Values are equal for acceleration and deceleration ramp Fixed freq 0,1 s / 1 s / 3 s / 5 s / 10 s / 15 s / 30 s / 60 s / 120 s / 180 s 0 … 100 % f-max 50 Hz / 60 Hz 50 Hz / 60 Hz I motor 10 % … 100 % Mode 0…9 SET Status LED Setting of Fixed Frequency 1 with potentiometer (Default: 20 Hz). After pushing the SET button for a short time (< 2 s) the Fixed Frequency 1 can be adjusted while the motor is running.
Motor protection The internal motor protection protects the motor against overload. In default the motor protection is set to the device’s rated current. It can be set to values between 10 and 100 % of the rated current by using the potentiometer “I motor” on the configuration module. If a keypad or the PC software DrivesConnect is used, the motor protection is set with P08.
Functions of the signals at the control terminals FWD / REV o Selection of the direction of rotation with High signal o Both signals at the same time = motor coasts to stand still (XOR) FF1 o H = Selection of fixed frequency 1 o The speed changes from the analog reference (REF) to fixed frequency 1 REF o Analog input for reference 0…10 V EXTFLT o External fault.
Configuration of the control terminals In default Variable Speed Starters are configured for terminal mode (P-12 = 0). The following information refers to this mode only. Settings of P-12 different from zero may lead to other terminal configurations (see manual MN040011EN). There are 10 different terminal configurations which can be selected either with the selection switch Mode on the configuration module or with parameter P-15.
Mode 3 One direction 1 direction (FWD) Speed reference via potentiometer (0 … 10 V) Fixed frequency FF1. Details see Mode 0 External fault (EXTFLT). Details see Mode 1 Mode 4 Digital reference (1) 1 direction (FWD) Speed reference via fixed frequency 1 or the inputs for the digital reference (UP / DOWN). With UP the reference will be increased, with DOWN reduced. In case UP and DOWN are applied at the same time, DOWN gets priority.
Mode 7 Fixed frequencies (2) 1 direction (FWD) External fault (EXTFLT). Details see Mode 1 Selection of fixed frequencies via binary coded in0 1 puts (FF2 / FF2 ) Mode 8 Machine control (1) 2 directions, selected with DIR. (L = FWD, H = REV) Speed reference via potentiometer (0 … 10 V) Fixed frequency FF1.
Full parameter access In case access to additional parameters is needed, this can be achieved by using: the optional keypad DX-KEY-LED (V1.2 and above) the parameter software DrivesConnect. Free Download: http://www.drive-support-studio.com/OTS/Eaton/downloads/deploy/drivesConnect.htm the communication system SmartWire DT in connection with the option module DX-NET-SWD3 Modbus RTU The Variable Speed Starter can be accessed via the RJ45 socket on front of the device.
Configuration of the analog input In case an analog input is needed (P-15 = 0 / 1 / 3 / 8 / 9), this functionality is assigned to terminal 4.
DC braking Parameter P-25 defines the operation of the DC braking. In default DC braking is disabled. DC-Braking before Start can be activated, to bring spinning motors to stand still before the Variable Speed Starter starts. This is to prevent trips because of too high inrush currents (Fans). The duration of the braking is set with P-26 (t-DCBrake@Stop). This time applies for a braking before start as well as for one after a stop command.
Modbus Variable Speed Starters DE1 can be connected to a Modbus network. In this case the following parameter settings are necessary: P-12 = 3 (ProcessDataAccess) P-34 (PDP-Address) to be set to the DE1’s address in the Modbus network P-35 (RS485-0 Baudrate) Setting of the baudrate P-36 (Modbus RTU0 COM Timeout) Behavior at communication loss Terminal 1 is used as hardware enable and requires a High signal to operate DE1 via Modbus.
Parameter list PNU SWD Address Access RUN Designation f-max Range Default fmin…300.0 Hz 50/60 Hz 0…fmax 0 Hz P-01 20.1 - r/w P-02 20.0 - r/w P-03 111.0 Y r/w t-acc 0.1 … 300 s 5.0 s P-04 114.0 Y r/w t-dec 0.1 … 300 s 5.0 s P-05 620.1 Y r/w Stop Mode 0/1 1 P-06 626.1 - r/w Energy Optimizer 0/1 0 P-07* 211.0 - r/w Motor Nom Voltage 50…500 V 230 V / 400 V / 460 V P-08* 210.0 - r/w Motor Nom Current 0.1 Ie … Ie Ie P-09 216.
PNU SWD Address Access RUN Designation Range Default P-10 217.0 - r/w Motor Nom Speed 0/ 200…18000 rpm 0 rpm P-11 27.0 Y r/w V-Boost 0.0 … 40.0 % 0.0 % P-12 928.0 Y r/w ProcessDataAccess 0…13 0 P-13* 947.0 … 947.7 - r P-14 320.0 Y r/w P-15 423.0 - r/w Last Fault (Last Fault…….Last Fault7) Password DI Config Select … - 0…65535 0 0…9 0 Description The motor rated speed is set using this parameter.
PNU SWD Address Access RUN Designation Range Default Description Configures the Analog input 1 for the selected signal source type. P-16 260.0 - r/w AI1 Signal Range 0…3 0 P-17 261.0 Y r/w AI1 Gain 0.100 …2.500 1.000 P-18 267.0 - r/w AI1 Invert 0/1 0 P-19 650.2 - r/w DI3 Logic 0/1 0 P-20 5.1 - r/w f-Fix1 fmin … fmax 20 Hz P-21 5.2 - r/w f-Fix2 fmin … fmax 30 Hz P-22 5.3 - r/w f-Fix3 fmin … fmax 40 Hz P-23 5.
PNU SWD Address Access RUN Designation P-30 620.0 - r/w Start Mode P-31 626.3 Y r/w P-32 624.0 - P-33 682.0 P-34 P-35 Range Default 0…10 Auto-0 Overvoltage Control 0/1 0 r/w Auto Thermal Management 0/1 0 - r/w Switch Remanant Storage 0/1 0 918.0 Y r/w PDP-Address 1…63 1 3222.0 Y r/w RS485-0 Baudrate 0…4 4 Description Defines the behaviour of the VSS relating to the enable digital input and also configures the automatic restart function.
PNU SWD Address Access RUN Designation P-40 840.29952 Y r/w Action@Communication Loss P-41 927.0 Y r/w Parameter Access Range Default 0…4 0 0/1 0 Description VSS reaction after SWD master communication loss. Master communication loss delay time is set by P-36 0 = No reaction, continue work 1 = Set warning, continue work 2 = stop (if ramp enabled) 3 = coast stop 4 = Trip Parameter Access 0 = All parameters can be changed by any source.