Counters, Panel Meters, Tachometers and Timers
Digital Panel Meters
General Specifications, continued
Description Specification
Signal Input, continued
5 A AC models (5770X-44X)
Range 5 A AC, true rms
Frequency 40 to 1000 Hz
Impedance 0.02 ohm (shunt output capacitive coupled)
Overrange 10 A maximum
Accuracy ±0.4% of reading, ±0.13% FS, ±0.5 digit, and ±200 PPM/°C for crest factor = 1; plus ±0.7% for crest
factor = 1 to 3; and ±2.5% for crest factor = 5
Process models (5770X-45X)
Range 4–20 mA DC, 0–10 Vdc, 1–5 Vdc; separate input terminals for voltage and current signals
Impedance 100 ohms (current input) and 1.27 Mohms (voltage input)
Overrange 50 mA maximum (current input) and 100 V maximum (voltage input)
Power output 24 Vdc ±10%, 90 mA max, short-circuit protected
Accuracy ±0.1% of reading, ±0.03% FS, ±0.5 digit, and ±80 PPM/°C
Optional Outputs
Relay board
Dual relay 1 set of Form C contacts each
Contact rating 5 A, 250 Vac or 30 Vdc
Isolation dielectric strength 2300 Vac
Analog retransmission
Output signals 4–20 mA (<750 ohms) and 0–10 V (>2500 ohms)
Accuracy 0.13% FS, 100 PPM/°C, 0.07% FS change with 4–20 mA load, ±0.3% FS for 4–20 mA output, only
after exposure to 85% relative humidity
Isolation dielectric strength 2300 Vac to signal inputs, relays and AC power input; 500 Vac to RS-485 and DC power inputs
RS-485 serial communication
Baud rate 1200, 2400, 4800, 9600 or 19,200, programmable
Parity Even, odd or no parity
Address range 00 to 99 decimal
Protocol Opto 22
®
compatible
Isolation dielectric strength 2300 Vac to signal inputs, relays, and AC power input; 500 Vac to analog outputs and
DC power inputs
Environmental
Operating environment Indoor use to 2000 meters
Temperature
Operating 32 to 122 °F (0 to 50 °C)
Storage –4 to 158 °F (–20 to 70 °C)
Humidity 0 to 85% RH, noncondensing
Vibration 2.5 Gs, 30 to 200 Hz
Shock 30 Gs, 11 ms half sinewave
EMC/EMI Per EN 61326-1 industrial
Front panel NEMA 4X when mounted with gasket provided
Agency approval CE EMC immunity and emissions requirements were met using shielded wiring on the RS-485,
analog output and signal input lines. The shields were connected to earth ground at the Eclipse
end of the shields.
Conducted emissions requirements were met assuming that the AC signal input would not be
connected directly to the AC mains.
The measurement error during RF immunity testing was less than ±5% of full scale.
In addition, models with an AC signal input had measurement error of less than +25% of full scale
during RF immunity testing of the RS-485 at frequencies below 1 MHz.
Pollution degree 2 Overvoltage Category II