Counters, Panel Meters, Tachometers and Timers
Tem p e ra t u re Con t rol s
General Specifications, continued
Special Control Function Inputs
Input Characteristics
Description Specification
Alarm
Alarm relay Form C rating; 2 A/240 Vac; 200,000 life cycles for resistive load
Alarm functions Dwell timer, deviation high/low alarm, deviation band high/low alarm, PV high/low alarm
Alarm mode Normal, latching, hold, latching/hold
Dwell timer 0.1 to 4553.6 minutes
Environmental and Physical
Operating temperature 14 to 122 °F (–10 to 50 °C)
Storage temperature –40 to 140 °F (–40 to 60 °C)
Humidity 0–90% RH (noncondensing)
Altitude 2000 m max.
Pollution Degree 2
Insulation resistance 20 Mohms min. (at 500 Vdc)
Dielectric strength 2000 Vac, 50/60 Hz for 1 minute
Vibration resistance 10–55 Hz, 10 m/s
2
for 1 minute
Moldings Flame resistant polycarbonate
Dimensions TC96 = 1.88 in (48 mm) (W) x 3.77 in (96 mm) (H) x 3.15 in (80 mm) (D)
TC48 = 1.88 in (48 mm) (W) x 1.88 in (48 mm) (H) x 4.56 in (116 mm) (D)
TC24 = 1.96 in (50 mm) (W) x 1.04 in (26.5 mm) (H) x 4.35 (110.5 mm) (D)
Type Range Accuracy at 25 °C Input Impedance
J –120 to 1000 °C (–184 to 1832 °F) ±2 °C 2.2 Mohms
K –200 to 1370 °C (–328 to 2498 °F) ±2 °C 2.2 Mohms
T –250 to 400 °C (–418 to 752 °F) ±2 °C 2.2 Mohms
E –100 to 900 °C (–148 to 1652 °F) ±2 °C 2.2 Mohms
B 0 to 1800 °C (32 to 3272 °F) ±2 °C (–200 to 1800 °C) 2.2 Mohms
R 0 to 1767.8 °C (32 to 3214 °F) ±2 °C 2.2 Mohms
S 0 to 1767.8 °C (32 to 3214 °F) ±2 °C 2.2 Mohms
N –250 to 1300 °C (–418 to 2372 °F) ±2 °C 2.2 Mohms
L –200 to 900 °C (–328 to 1652 °F) ±2 °C 2.2 Mohms
PT100 (DIN) –210 to 700 °C (–346 to 1292 °F) ±0.4 °C 1.3 Kohms
PT100 (JIS) –200 to 600 °C (–328 to 1112 °F) ±0.4 °C 1.3 Kohms
mV –8 mV to 70 mV ±0.05% 2.2 Mohms
mA –3 mA to 27 mA ±0.05% 70.5 ohms
V –1.3 V to 11.5 V ±0.05% 650 Kohms