Data Sheet

DATASHEET - PXF-40/4/003-B
Residual current circuit-breaker, all-current sensitive, 40 A, 4p, 30 mA,
type B
Part no. PXF-40/4/003-B
Catalog No. 300299
Delivery program
Basic function Residual current circuit-breakers
Number of poles 4 pole
Application Switchgear for residential and commercial applications
Rated current I
n
A 40
Rated short-circuit strength I
cn
kA 10
Rated fault current I
ΔN
A 0.03
Type Type B
Tripping s… Short time-delayed
Product range PXF
Sensitivity All current sensitive
Impulse withstand current Surge-proof, 3 kA
Technical data
Electrical
Current test marks As per inscription
Standards IEC/EN 61008
IEC/EN 62423
Rated operational voltage U
e
V
U
e
V AC
Rated operating voltage U
e
V AC 230/400
Rated frequency f Hz 50
Limit values of the operating voltage
Test circuit V AC 196 - 253
Sensitivity All current sensitive
Rated insulation voltage U
i
V 440
Rated impulse withstand voltage U
imp
kV 4
Rated short-circuit strength I
cn
kA 10
Rated making and breaking capacity / Rated residual making and breaking
capacity
I
m
/ I
Δm
A 500
lifespan
Electrical Operations ≧ 4000
Mechanical Operations ≧ 20000
References
Auxiliary switch for subsequent installation Z-HK 248432
Tripping signal contact for subsequent installation Z-NHK 248434
Remote control and automatic switching device Z-FW/LP 248296
Compact enclosure KLV-TC-4 276241
Switching interlock IS/SPE-1TE 101911
Sealing cover set Z-RC/AK-4MU 101062
Mechanical
Standard front dimension mm 45
Device height mm 80
Built-in width mm 70 (4TE)
Mounting Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Degree of Protection IP40, IP54 (with moisture-proof enclosure)
Terminals top and bottom Open mouthed/lift terminals
Terminal protection DGUV VS3, EN 50274
06/16/2021 Eaton Y7-300299 ED2021 V80.0 EN 1 / 3