Data Sheet

Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top
of the enclosure, calculated as per IEC 60890
Individual enclosure for wall mounting P
V
W 13
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top
of the enclosure, calculated as per IEC 60890
Individual enclosure for wall mounting P
V
W 25
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
650 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Not relevant to indoor installations.
10.2.5 Lifting Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact IK08
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES IP65
10.4 Clearances and creepage distances Is the panel builder's responsibility.
10.5 Protection against electric shock Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength U
i
= 1000 V AC
10.9.3 Impulse withstand voltage 3.3kV
10.9.4 Testing of enclosures made of insulating material Meets the product standard's requirements.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility.
10.12 Electromagnetic compatibility Is the panel builder's responsibility.
10.13 Mechanical function Meets the product standard's requirements.
Technical data ETIM 7.0
Distribution boards (EG000023) / Small distribution board (EC000214)
Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (incl. small distribution board) / Small distribution board
(ecl@ss10.0.1-27-14-24-09 [ACN387011])
Mounting method Surface mounted (plaster)
Number of rows 1
Width in number of modular spacings 6
Type of cover Door
Cover model With notch
Transparent cover/door Yes
Material housing Plastic
Height mm 231
Width mm 202
Depth mm 110
Built-in depth mm 70
Internal depth mm 60
DIN-rail Yes
With mounting plate No
Extension possible Yes
EMC-version No
Colour Grey
RAL-number 7035
Degree of protection (IP) IP65
With lock No