Data Sheet

Ambient temperature
Operating ambient temperature min. °C -10
Operating ambient temperature max. °C + 50
operation (with 150 % overload)
Storage ϑ °C -40 - +60
Radio interference level
Radio interference class (EMC) C1 (for conducted emissions only), C2, C3, depending on the motor cable length, the
connected load, and ambient conditions. External radio interference suppression
filters (optional) may be necessary.
Environment (EMC) 1st and 2nd environments as per EN 61800-3
maximum motor cable length I m C1 ≤ 1 m
C2 ≤ 5 m
C3 ≤ 25 m
Mounting position Vertical
Altitude m 0 - 1000 m above sea level
Above 1000 m: 1% derating for every 100 m
max. 4000 m
Degree of Protection IP20/NEMA0
Protection against direct contact BGV A3 (VBG4, finger- and back-of-hand proof)
Main circuit
Supply
Rated operational voltage U
e
230 V AC, 1-phase
240 V AC, single-phase
Mains voltage (50/60Hz) U
LN
V 200 (-10%) - 240 (+10%)
Input current (150% overload) I
LN
A 8.6
System configuration AC supply systems with earthed center point
Supply frequency f
LN
Hz 50/60
Frequency range f
LN
Hz 48 - 62
Mains switch-on frequency Maximum of one time every 30 seconds
Power section
Function Variable frequency drive with internal DC link and IGBT inverter
Overload current (150% overload) I
L
A 6.45
max. starting current (High Overload) I
H
% 200
Note about max. starting current for 4 seconds every 40 seconds
Output voltage with V
e
U
2
230 V AC, 3-phase
240 V AC, 3-phase
Output Frequency f
2
Hz 0 - 50/60 (max. 500)
Switching frequency f
PWM
kHz 16
adjustable 4 - 32 (audible)
Operation Mode U/f control
Speed control with slip compensation
sensorless vector control (SLV)
optional: Vector control with feedback (CLV)
Frequency resolution (setpoint value) Δf Hz 0.1
Rated operational current
At 150% overload I
e
A 4.3
Note Rated operational current at an operating frequency of 16 kHz and an ambient air
temperature of +50°C
Power loss
Heat dissipation at rated operational current I
e
=150 % P
V
W 45.75
Efficiency η % 93.9
Heat dissipation at current/speed [%]
Current = 100%
Speed = 0 % P
V
W 42
Speed = 50 % P
V
W 53
Speed = 90 % P
V
W 64
Current = 50 %
Speed = 0 % P
V
W 38
Speed = 50 % P
V
W 38
Speed = 90 % P
V
W 42
06/18/2021 Eaton 169078 ED2021 V80.0 EN 2 / 6