Data Sheet

DATASHEET - EC4P-222-MRAX1
Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), 1AO, ethernet, CAN
Part no. EC4P-222-MRAX1
Catalog No. 106406
EL-Nummer
(Norway)
4519739
Delivery program
Expandable: Inputs/outputs and bus systems
individual laser inscription possible with EC4-COMBINATION-*
Description easyNet/CANopen® and Ethernet on board
Inputs
Digital 12
of which can be used as analog 4
Outputs
Relay 10 A (UL) 6
Analog 1
Supply voltage 24 V DC
Technical data
General
Dimensions (W x H x D) mm 107.5 x 90 x 72 without/79 with adapter for MCC (6 SU)
Weight kg 0.3
Mounting Top-hat rail IEC/EN 60715, 35 mm or screw fixing using 3 fixing brackets ZB4-101-
GF1 (accessories)
Terminal capacities
Solid
mm
2
0.2/4 (AWG 22 - 12)
Flexible with ferrule
mm
2
0.2/2.5 (AWG 22 - 12)
Standard screwdriver mm 0.8 x 3.5
Max. tightening torque Nm 0.6
Climatic environmental conditions
Operating ambient temperature °C -25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2
Condensation Take appropriate measures to prevent condensation
LCD display (clearly legible) °C 0 - 55
Storage ϑ °C -40 - +70
Relative humidity, non-condensing (IEC/EN 60068-2-30) % 5 - 95
Air pressure (operation) hPa 1080 - 1080
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20
Vibrations (IEC/EN 60068-2-6) Hz
Constant amplitude 0.15 mm Hz 10 - 57
Constant acceleration 2 g Hz 57 - 150
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms Impacts 18
Drop to IEC/EN 60068-2-31 Drop height mm 50
Free fall, packaged (IEC/EN 60068-2-32) m 1
Mounting position Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree II/2
Electrostatic discharge (ESD)
applied standard IEC/EN 61000-4-2, Level 3
Air discharge kV 8
Contact discharge kV 6
Electromagnetic fields (RFI) to IEC EN 61000-4-3 V/m 10
Radio interference suppression EN 55011 Class B, EN 55022 Class B
Burst kV IEC/EN 61000-4-4, level 3
06/18/2021 Eaton 106406 ED2021 V80.0 EN 1 / 6