Data Sheet

DATASHEET - PXF-100/4/003-A
Residual current circuit-breaker, 100A, 4pole, 30mA, type A
Part no. PXF-100/4/003-A
Catalog No. 102881
Similar to illustration
Delivery program
Basic function Residual current circuit-breakers
Number of poles 4 pole
Application Switchgear for residential and commercial applications
Rated current I
n
A 100
Rated short-circuit strength I
cn
kA 10
Rated fault current I
ΔN
A 0.03
Type Type A
Tripping s… non-delayed
Product range PXF
Sensitivity Pulse-current sensitive
Impulse withstand current Partly surge-proof 250 A
Technical data
Electrical
Standards IEC/EN 61008
Rated operational voltage U
e
V
U
e
V AC
Rated operating voltage U
e
V AC 230/400
Rated frequency f Hz 50
Limit values of the operating voltage
Test circuit V AC 184 - 440
Comment for range of the test button 3-phase application without N (400V AC Phase-Phase) not allowed
Sensitivity Pulse-current sensitive
Rated insulation voltage U
i
V 440
Rated impulse withstand voltage U
imp
kV 4
Rated short-circuit strength I
cn
kA 10
Rated making and breaking capacity / Rated residual making and breaking
capacity
I
m
/ I
Δm
A 1000
lifespan
Electrical Operations ≧ 4000
Mechanical Operations ≧ 20000
References
Auxiliary switch for subsequent installation Z-HK 248432
Tripping signal contact for subsequent installation Z-NHK 248434
Remote control and automatic switching device Z-FW/LP 248296
Compact enclosure KLV-TC-4 276241
Switching interlock IS/SPE-1TE 101911
Sealing cover set Z-RC/AK-4MU 101062
Mechanical
Standard front dimension mm 45
Device height mm 80
Built-in width mm 70 (4TE)
Mounting Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Degree of Protection IP20, IP40 with suitable enclosure
Terminals top and bottom Open mouthed/lift terminals
Terminal protection DGUV VS3, EN 50274
06/18/2021 Eaton 102881 ED2021 V80.0 EN 1 / 3