Data Sheet

220 V 230 V P kW 1.5
240 V P kW 1.8
380 V 400 V P kW 3
415 V P kW 3.1
440 V P kW 3.3
500 V P kW 3
660 V 690 V P kW 3
DC
Rated operational current open
DC-1
12 V I
e
A 20
24 V I
e
A 20
60 V I
e
A 20
110 V I
e
A 20
220 V I
e
A 20
Magnet systems
Voltage tolerance
DC operated
Pick-up voltage 0.8 - 1.1
Power consumption
DC operation
Power consumption Pick-up = Sealing VA/W 2.3
Notes Smoothed DC voltage or three-phase bridge rectifier
Duty factor % DF 100
Switching times at 100 % U
c
Make contact ms
Closing delay ms
Closing delay min. ms 26
Closing delay max. ms 35
Opening delay ms
Opening delay min. ms 15
Opening delay max. ms 25
Closing delay with top mounting auxiliary contact ms 70
Reversing contactors
Changeover time at 110 % U
c
Changeover time min. ms 40
Changeover time max. ms 50
Arcing time at 690 V AC ms 12
Current heat losses (3- or 4-pole)
at I
th
, 50 °C W 4.4
at I
e
to AC-3/400 V W 0.9
Impedance per pole mΩ 7.86
Auxiliary contacts
Positive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact
module
Yes
Rated impulse withstand voltage U
imp
V AC 6000
Overvoltage category/pollution degree III/3
Rated insulation voltage U
i
V AC 690
Rated operational voltage U
e
V AC 600
Safe isolation to EN 61140
between coil and auxiliary contacts V AC 300
between the auxiliary contacts V AC 300
Rated operational current
AC-15
220 V 240 V I
e
A 6
06/16/2021 Eaton 079594 ED2021 V80.0 EN 4 / 11