Data Sheet

Mechanical Ops./h 9000
electrical (Contactors without overload relay) Operations/h Page 05/070
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 - +50
Enclosed °C - 25 - 40
Storage °C
Min. ambient temperature, storage °C - 40
Ambient temperature, storage max. °C + 80
Mounting position As required, except vertical with terminals A1/A2 at the bottom
Mounting position
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Basic unit without auxiliary contact module
Main contacts, make contacts g 10
Main contacts Make/break contacts g
Make g 8
Basic unit with auxiliary contact module
Main contacts make contact g
Make g 10
Auxiliary contacts Make/break contacts g 20 / 20
Degree of Protection IP20
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Altitude m Max. 2000
Weight kg 0.206
Terminal capacity of auxiliary and main contacts
Screw terminals
Solid
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule
mm
2
1 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded AWG 18 - 14
Stripping length mm 8
Terminal screw M3.5
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.5
1 x 6
Max. tightening torque Nm 1.2
Main conducting paths
Rated impulse withstand voltage U
imp
V AC 6000
Overvoltage category/pollution degree III/3
Rated insulation voltage U
i
V AC 690
Rated operational voltage U
e
V AC 690
Safe isolation to EN 61140
between coil and contacts V AC 300
between the contacts V AC 300
Making capacity (cos ϕ to IEC/EN 60947) A 110
06/16/2021 Eaton 079594 ED2021 V80.0 EN 2 / 11