Data Sheet

DATASHEET - EMT6-DB
Thermistor overload relay for machine protection, 24-240V50/60HZ/DC
Part no. EMT6-DB
Catalog No. 066167
Alternate Catalog
No.
EMT6-DB
EL-Nummer
(Norway)
0004110420
Delivery program
Product range EMT6 thermistor overload relay for machine protection
Function Selector switch with/without manual reset
For manual or remote resetting
Test button
Mains and fault LED display
Rated operational current
AC-15
240 V I
e
A 3
AC--14
300 V I
e
A 3
400 V I
e
A 3
Value applies starting with release 001.
conventional thermal current I
th
A 6
Rated control voltage U
s
V 24 - 240 V 50 - 400 Hz
24 - 240 V DC
Notes
Observe manual MN03407006Z-DE/EN.
Can be snap fitted on a top-hat rail to IEC/EN 60715.
Technical data
General
Standards IEC/EN 60947, VDE 0660, EN 55011
Climatic proofing Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 - +60
Enclosed °C - 25 - 45
Storage °C - 45 - 85
Mounting position As required
Weight kg 0.15
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 g 10
Degree of Protection IP20
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Safe isolation to EN 61140
between the contacts V AC 250
between contacts and power supply V AC 250
Auxiliary and control circuits
Rated impulse withstand voltage U
imp
V AC 4000
Rated impulse withstand voltage U
imp
V AC 6000
Value applies starting with release 001.
Overvoltage category/pollution degree III/3
Terminal capacities Auxiliary and control circuits
Solid
mm
2
1 x (0.5 - 2.5)
2 x (0.5 - 1.5)
Flexible with ferrule
mm
2
1 x (0.5 - 2.5)
2 x (0.5 - 1.5)
Solid or stranded AWG 20 - 14
Terminal screw M3.5
06/16/2021 Eaton 066167 ED2021 V80.0 EN 1 / 5

Summary of content (5 pages)