Datasheet

48
v1.3 / Modification rights reserved
EE431EE431
The EE431 temperature sensor is used for air temperature
measurement in heating, ventilation and air conditioning
systems. It can be installed either with mounting flange or via
external mounting holes at the enclosure (duct sensor).
For temperature measurement in liquids the temperature sen-
sor EE431 is mounted with an immersion well (immersion sen-
sor).
In addition to active outputs 0-10 V or 4-20 mA various types of
sensing elements such as Pt1000, NTC10k or Ni1000 are avai-
lable for passive temperature measurement.
The innovative IP65 housing and the mounting concept allow
for fast and easy installation.
The optional adapter EE-PCA and the free configuration software EE-PCS facilitate the adjustment and setup of the
active temperature sensors.
EE431
Duct / Immersion Temperature Sensor
EE431
EE431 +
Immersion Well
EE431 + Mounting Flange
Active Output
Operating temperature duct sensor (probe): -40 °C…+110 °C (-40 °F...+230 °F)
immersion sensor (probe): -40 °C…+150 °C (-40 °F...+302 °F)
electronics: -40 °C…+70 °C (-40 °F...+158 °F)
Sensing element Pt1000 (class A, DIN EN60751)
Output 0-10 V -1 mA < I
L
< 1 mA
4-20 mA (two-wire) R
L
< 500
Accuracy ±0.3 °C
(±0.54 °F) at 20 °C (68 °F)
Supply voltage (Class III)
for 0-10 V 15-35 V DC or 24 V AC ±20%
for 4-20 mA 10 V DC + R
L
x 20 mA < V+ < 35 V DC
Current demand DC: typ. 5 mA
AC: typ. 12 mA
eff
Electromagnetic compatibility EN61326-1, EN61326-2-3
industrial environment
Technical Data
Building automation
Process and climate control
Measurement in air and liquids
Typical Applications
Features
External mounting holes
» Mounting with closed cover
» Protection against construction
site pollution
Bayonet screws
» Open/closed with a ¼ rotation
Fixation via clamping
» No direct screwing onto probe
» Inclined screw for easy installation
Special sealing
» Foam gasket for good tightness
» No scratching of probe due to
alignment notch
Mounting flange
Immersion well
Innovative mounting spring
» For securing the probe inside the well
» No fastening screw, no tools required