Submittal Sheet

The Series GSTA and GSTC Carbon Monoxide/Nitrogen Dioxide
Transmitter monitors gas concentration in underground parking garages
and loading docks. The carbon monoxide transmitter is used to measure
the exhaust of gasoline engines, while the nitrogen dioxide transmitter
is used for diesel engines. The Series GSTA has eld selectable current
and voltage output, and the Series GSTC is compatible with either
BACnet or Modbus
®
communication protocol, allowing the transmitters
to be used with almost any building management controller. To maximize
the accuracy of the transmitters, the sensors can be eld-calibrated
using the A-449 remote LCD display. When the sensor reaches the end
of its life, the display will indicate that the sensor needs to be replaced.
Industrial grade electrochemical sensor means longer sensor life and less frequent sensor replacements
Field replaceable sensors extend transmitter’s working life
Remote LCD display makes select models more cost effective by only needing one display for multiple transmitters
Field selectable current and voltage outputs on GSTA and BACnet or Modbus
®
communication protocol on GSTC allow for
gas sensing solutions to be used with almost any building management controller
Parking garages
Loading docks
Automobile service bays
Boiler or mechanical rooms
FEATURES/BENEFITS
DESCRIPTIONAPPLICATIONS
SERIES GSTA & GSTC | CARBON MONOXIDE/NITROGEN DIOXIDE
GAS TRANSMITTER
®
Wall mount with LCD Wall mount without LCD Duct mount
SPECIFICATIONS
Sensor Field replaceable electrochemical, 4 years typical lifespan.
Range NO2: 10 PPM; GSTA CO: Switch selectable 200 or 500 PPM; GSTC CO: 500 PPM.
Output Drift <5% per year in air.
Coverage Area 5000 to 7500 ft2 typical.
Accuracy CO: 2% FS; NO2: 3% FS, at the time of calibration.
Resolution CO: 1 PPM; NO2: 0.1 PPM.
Temperature Limits -4 to 122°F (-20 to 50°C).
Storage Temperature For best sensor life 32 to 68°F (0 to 20°C).
Humidity Limits 15 to 90% RH constant; 0 to 99% RH intermittent.
Response Time <45 s to 90% CO; <25 s to 90% NO2.
Span and Zero Adjustments Via pushbutton, using optional A-449 display.
Housing UV resistant glass lled polycarbonate
Output
GSTA: Switch selectable 4-20 mA, 0-5 V or 0-10 V; GSTC: BACnet MS/TP or Modbus
®
RTU (switch selectable)
communication protocol.
Power Supply
GSTA: Current output: 10-35 VDC, Voltage output: 15-35 VDC or 15-29 VAC; GSTC: 10-36 VDC or isolated 21.6-
33 VAC.
Electrical Connection Removable terminal block, knock outs for conduit tting.
Calibration Via pushbuttons using A-449 display. Span gas concentration is eld selectable on CO units.
Weight 1 lb (0.45 kg).
Agency Approvals CE.