REGO Instruction Manual Automatic Reactive Power Controller Revision-0 Firmware - 4.
DUCATI energia REGO POWER 1 2 3 5 4 REMOT NC2 5 NC1 3 4 2 C 1 DUCATI MAINS CONNECTION OPER.TYPE C.T.POST. x 10 REACTIVE POWER CONTROLLER L1 L2 L1 FF1 FF2 F-N 0 230V 400V L3 L1 N - ALARM RESET DATA energia REACTIVE POWER CONTROLLER REGO MADE IN TIALY L2 L2 L1 - CT.
MAINS -380-415V N T/23 S/L2R/L1 REGO K CT../5A L FF1 CONNECTION 400V (V2) 230V (V1) REGO K L CT../5A FF2 CONNECTION 400V (V2) 230V (V1) K CT../5A L F-n CONNECTION Only for single phase network 400V (V2) 230V (V1) USE 200mA FUSE FOR VOLTAGE INPUTS LOAD Fig.-3 - Mains Connection MAINS N T/23 S/L2R/L1 K L CT../5A REGO STEPS 12 REGO STEPS 7 SEE FIG.3 REGO STEPS 5 400V (V2) 230V (V1) DV USE 200mA FUSE FOR VOLTAGE INPUTS 2 1 3 6 8 7 C1 K4 K2 Fig.
Simplified Diagram relative to First Powering up 1 3 2 11 5 4 9 10 6 NO YES 12 YES 13 7 NO 14 SELFACQUISITION 15 8 MANUAL PROGRAMMING 16 17 18 19 20 1. POWER THE CONTROLLER 2. DISPLAYALTERNATELY SHOWS “IL” AND “- - -” 3. ENTER “IL” PARAMETER MAINS C.T. RATIO (e.g. w/ C.T. 200/5 enter 40) 4. “+” AND “-” TO CHANGE THE PARAMETER AND “DATA” KEY TO CONFIRM 5. “FAS” DISPLAYED IN TURN WITH “0” OR “1” 6.
CONTENTS (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) 12.1 12.2 12.3 12.4 12.5 12.6 12.7 12.8 12.9 (13) 13.1 13.2 13.3 13.4 13.5 13.6 13.7 (14) (15) (16) (17) SIMPLIFIED DIAGRAM RELATIVE TO FIRST POWERING UP SAFETY GENERAL DESCRIPTION HOW IT WORKS MAINS CONNECTION INSTRUCTIONS FOR INSTALLING THE. CT.
2) SAFETY NOTE: The front panel of REGO features a series of keys for accessing functions and programming; some functions are activated by pressing a combination of 2 keys: in this manual, when mention is made of a two-key combination (e.g. AUTO/MAN + ), it means that the user must press the first key and, without releasing it, then press the second one. (In fact the combination AUTO/MAN + activates a + AUTO/MAN.
MT TRANSFORMER ROOM L3 L1 L2 BT T.A. C.T. INSTALLATION CORRECT a MAIN SWITCH T.A. C.T. INSTALLATION CORRECT INSTALLATION INCORRECT b T.A. C.T. c T.A. C.T. d INSTALLATION INCORRECT L1 L2 L3 DEDICATED SWITCH FOR POWER FACTOR CORRECTION SYSTEM LOADS S2 S1 Fig.-5 - Positioning of C.T. (7) POWERING UP FOR THE FIRST TIME The REGO regulator behaves differently the first time it is started up since it will need the IL parameter (mains C.T.
NOTE: if the incoming current is insufficient (less than 200mA), REGO cannot determine its direction and will stand by in this status until current is supplied. At this point, the controller no longer requires any type of setting and will be ready for perfect operation: it will alternately display “COS” and the system power factor.
DO NOT CHANGE THIS PARAMETER IF THE CONTROLLER IS INSTALLED ON A DUCATI ENERGIA POWER FACTOR CORRECTION SYSTEM. AUt = a new automatic acquisition procedure will be carried out. Press DATA to go on to the next parameter 10.4 “IL” = Mains C.T. ratio. The “IL” parameter is displayed in turn with the value previously set by the user. The value can be changed using the or key. Setting examples: C.T. 300/5 IL =60; C.T. 350/5 IL=70; C.T. 400/5 IL=80 Ex. Press DATA to go on to the next parameter 10.
SEMI-GEOMETRIC LOGIC It is identified by the code 1:2:2 and the power of the first bank must be half that of the others, which must all be equal. The first bank is managed according to a geometric logic whereas all the others, which have equal powers, are managed according to a linear logic. Parameter Description Range (10.1) Fr Measured mains Freq. only an indication 50 or 60 Hz (10.2) COS Power factor to be 0.8IND ÷ achieved within the system 0.8CAP 0.95 400 (10.
press or to choose the status of the relay you want to set in the manual operating mode; press the DATA key to display the status of the subsequent relay. After viewing the status of the last relay, press the DATA key to exit this function. 12.2 DISPLAYING THE POWERS OF SINGLE STEPS Press DATA + to access the relevant menu (“CP” will appear on the display and will flash); when the key is pressed, REGO will alternately display “C1” and the value in kVAr associated with the first step. Ex. 12.
13.2 OVERVOLTAGE SIGNAL This signal is activated when the controller measures a supply voltage exceeding the maximum allowed by the transformer (230 +19%; 400 +19%) for longer than 30 seconds. To set the appropriate operating mode for correcting the power factor of generators, press the key: the word “On” will appear. If, on the contrary, you wish to enable the C.T.
After 30 minutes all these actions will be cleared and the controller will automatically resume operation (auto-reset status A.r.), though the incident will continue to be signaled via the display, which will show “A.L.A.” in turn with “t.h.d.” and the measured Crest Factor. To clear the display press ALARM/RESET. This protection is also active in the manual mode. 13.
Parameter Description Range Default Fan REGO7-12 Temperature threshold (°C) for tripping fan activation. 5...50 25 t1 Time (in seconds) of unavailability of a step for re-activation. Always wait for capacitors to discharge before switching them back on. 5...255 30 Delay time (in units: each unit corresponds to 500mS) between the activation of one step and the next. 1...600 2(=1S) HU Mains VT transformation ratio. 1...1000 1 StH Setting of trip time of t.h.d. harmonic distortion alarm. 12.
Measurement and control data Type of voltage and current true effective value ( true RMS) measurement Power factor control 0.80 inductive ÷ 0.80 capacitive Step re-connection time lag 5...255s Relay outputs Number of outputs Contact status Nominal contact capacity Voltage rating Alarm relay Nominal insulation voltage Max.