Installation Instructions

INSTALLATION
3525PRX / DFR / iCL
ELECTROMECHANICAL RACK HANDLE LOCK
WITH READER
© 2022 dormakaba Canada Inc
www.dormakaba.us • Phone: 1.800.265.6630 • Fax: 1.800.482.9795 • E-mail: sales_RCI@dormakaba.comIS3525PRX
PCN2105
R02-22GR
INSTALLATION
Specifications
Package Contents
3525 Electromechanical Rack Handle Lock with Reader
M3x25 Mounting Screws (qty 4)
M3x14 Mounting Screw
Rotation Limiter Standard
Rotation Limiter - Extended (for thicker panels)
Cam Bolt
Top Mounting Bracket
Bottom Mounting Bracket
Installation Instructions
• Keys (qty 3)
Actuator Module
Supply
Voltage
12VDC to 24VDC (NOTE: Status LED will blink red if
the supply voltage is out of range.)
Standby
Current
50mA maximum at 12VDC"
Operating
Current
see chart below
Stall Current 1A maximum at 12VDC (limited to 2 seconds)
Operating
Transit Time
1 second maximum (NOTE: Power must be present
during transit times. If power is removed while the lock
slide is in transit, it will complete it’s cycle when power
is restored.)
Electronic
Unlock Time
3 seconds minimum
Open
Collector
Outputs
Rated for supply voltage, maximum load
Alarm
Outputs
100mA/ output maximum
Fig. 1
Data Rack
Handle
Reader
Tri-Color Status
LED
Key Cylinder
Reader PRX DFR iCL
Voltage 12VDC ~ 24VDC
Operating
Current
20 mA
No External Load
125 mA
No External Load
60mA
No External Load
Transmit
Frequency
125 kHz FSK 13.56 MHz / 125 kHz 13.56 MHz
DATA Signal
Voltage
5VDC
DATA Pulse
Interval Time
40µs
DATA Signal
Delay
2ms
Output Format N/A
Reverse Byte Order (13.5MHz cards) Most Significant Bit First (125kHz
cards) Upper and Lower Parity Bit Included
Reverse Byte Order with
Upper and Lower Parity Bits
Overall
Dimensions
8-1/4” H x 1-1/2” W x 1” D
210mm x 37mm x 25mm (Depth from Cabinet Face)

Summary of content (4 pages)