Installation Manual

Doc # INT-100109-001
Part No. 191132 Rev. 1
INSTALL INSTRUCTIONS
DTK-P Series
DITEK Technical Support Available 24/7
1-888-472-6100
www.ditekcorp.com
DITEK Corporation
ONE DITEK CENTER
1720 Starkey Road
Largo, FL 33771
This Surge Protection Device (SPD) is a high performance device, designed to provide protection
for sensitive electronic loads connected to service panels, fire panels, or where the SPD is
directly connected to the electronic device. Maximum protection will only be achieved if the SPD
is properly installed.
Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National
and Local Electrical Codes and the following instructions.
APPLICATION
Surge suppression for data circuits, isolated loops, or low voltage telecommunications using a
hardwired connection.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of
the unit. Improper installation voids the warranty.
This unit must be connected in parallel with the equipment to be connected.
1. Punch down the 22 AWG solid lead wires to a punch down block or make a parallel connection
to the screw terminal inside the RJ jack.
2. Always have one common ground per system to eliminate the possibility of a differential in
ground potentials.
Make sure your ground connection is shorter than the lead wires to the protected equipment.
Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum.
This cannot be an assumed value and must be measured to assure proper grounding.
3. For mounting, use double sided tape (supplied), or two (2) #8 screws (not supplied).
Drawn By: J.Ramirez 12-7-07
Approved By: R. Mitchell 12-7-07
INSTALLATION
130VRMS 95VRMS 75VRMS 52VRMS 27VRMS 15VRMS 7VRMS
RUV SGR SPK OPX LV X D