Standalone Wireless Communicator Compatible with all PowerSeries keypads Installation & Programming Guide R D T F A WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. Read the entire manual carefully.
Skyroute CL3050 Quick Start: Note: Before you start, you must be enrolled with CONNECT 24 as an authorized installer to activate a Skyroute transceiver. Enrollment is Free! If you are not already enrolled, call 1-888955-5583 in Canada or 1-888-251-7458 in the U.S. at least 24 hours before your first activation. STEP 1 - SELECT BEST LOCATION (See Section 2.1) Connect the Skyroute transceiver to a 7 Ah battery, as described in Section 2.1. Determine the best location for signal strength.
For Your Records Location Test Time & Day Additional Notes CONNECT 24TM Enrollment Information Note: Only authorized dealers can enroll a wireless system to Connect 24. Dealer application forms and additional information on the Connect 24 Voice Response Unit can be found at the Connect 24 web site. http://www.connect24.com/dealer.htm The information required for activation is listed below. Ensure that all information is available before calling the Connect 24 Voice Response Unit.
FCC COMPLIANCE STATEMENT CAUTION: Changes or modifications not expressly approved by Digital Security Controls Ltd. could void your authority to use this equipment. This equipment generates and uses radio frequency energy and if not installed and used properly, in strict accordance with the manufacturer’s instructions, may cause interference to radio and television reception.
Table of Contents Section 1: Introduction ...................................................................... 1 1.1 Specifications .......................................................................................................2 1.2 Unpacking ...........................................................................................................2 Section 2: Installation, Testing & Factory Defaults .......................... 3 2.1 Installation ...............................................
ii
1 Introduction 1 Introduction The Skyroute CL3050 is a standalone wireless communicator that sends alarm system information to Connect 24. Connect 24 then forwards this information to the central station. The Skyroute CL3050 automatically configures itself on power up to one of three operational modes or; if it is connected to a keypad, in the programming mode. The Skyroute CL3050 is pre programmed with the most commonly used settings for quick installation.
Skyroute CL3050 Standalone Wireless Communicator 1.1 Specifications • • • • • • • • • • Power Supply Voltage ...................................................................................... 9-12 VAC or VDC Current .........................................................................................500 mA (Max) Low DC Trouble ...................................................................................... 8.8 VDC Low DC Restore ...........................................................
2 Installation, Testing & Factory Defaults 2 Installation, Testing & Factory Defaults 2.1 Installation 1 Determine The Operating mode required (see section [03]) The operating mode (modes 1, 2, or 3) will determine how the unit is to be wired up. Refer to section 6, Programming Descriptions, section [10] for available options and for programming defaults. 2 Determine the Mounting Location Select a mounting location in a dry, protected area.
Skyroute CL3050 Standalone Wireless Communicator 5 Mount Unit • • • • Remove the front cover if required Disconnect flying leads from battery and power leads from the RED and BLK terminals (if connected). Remove two screws securing battery clamp. Remove battery Mount backplate of unit to wall or over electrical junction box using the four screws provided. Note: 6 DO NOT connect the battery to the flying leads and AC or DC power to the terminal strip until all other wiring connections are completed.
3 Controls and Indicators 3 Controls and Indicators Figure 2 Antenna Mounting Holes Green LED Yellow LED Red LED Battery (6 VDC) Enroll Button Wire Access Tamper Switch 3.1 LED Indicators (see figure 2) Yellow LED During normal operation, the yellow LED will indicate the system status with a series of flashes as indicated below. No.
Skyroute CL3050 Standalone Wireless Communicator Note: Multiple trouble conditions are displayed (flashed) in sequence. Red LED The red LED will flash to provide event transmission status for the following events: 1 Flash 1 Flash 2 Flashes Enroll button held down for 2 seconds Event transmitted to cellular network Event acknowledged by Connect 24. Green LED The green LED will light continuously if the (RSSI) signal is acceptable. If signal strength is not acceptable the LED will turn OFF.
4 Power up Sequence PGM - The PGM output is dedicated for Skyroute CL3050 trouble indications. If a control panel is not monitoring the Skyroute CL3050, an LED or a buzzer can be connected between this terminal and the RED terminal for trouble indication. The PGM terminal switches low from an open-collector state. Connect to the control panel using a Single EOL configuration as shown Note: The PGM output can sink 50 mA (maximum).
Skyroute CL3050 Standalone Wireless Communicator 5 System Programming The Skyroute CL3050 is programmed using a PowerSeries keypad. Refer to Section 1.1 Specifications. Note: 1. Power down the Skyroute CL3050 when connecting or removing other Keybus modules from the system. If the Skyroute CL3050 is connected to a control panel (mode 1), the control panel must also be powered down. Connect keypad Keybus connections to the RED, BLK, YEL and GRN terminals of the Skyroute CL3050.
6 Programming Descriptions 6 Programming Descriptions Modes 2, 3 [01] Zone 1, 2 Definitions When the Skyroute CL3050 is in Mode 2 or 3, there are 14 options that can be programmed as zone types. All of the zone types with the exception of 00 (null zone) and 13 (TLM monitor) are straightforward. Since all the zones are 24-hour type zones, selecting any listed zone type will simply select which identifier should be used for reporting the alarm.
Skyroute CL3050 Standalone Wireless Communicator [02] Mode 2 - (2) 24-Hour Zones In this mode, both the YEL and RED BLK YEL GRN COM PGM GRN terminals on the Skyroute CL3050 will be used as zone inputs. These zones will support Input Voltage the DSC standard EOL configura- 9-12VAC or VDC Zone 1 Input tion and loop response. ProZone 2 Input gramming sections will allow the Zone Common installer to change the default Trouble Output zone types and attributes.
6 Programming Descriptions Single EOL resistors allows the use of N/C and/or Normally Open contacts. C Zx C Zx C Zx Double EOL resistors allows the zone to be monitored for fault, tamper, secure and violated conditions. Only Normally Closed contacts can be used in this configuration C 5.6KΩ 5.6KΩ Zx Tamper Contact 5.6KΩ C Zx 5.6KΩ 5.6KΩ 5.6KΩ 5.6KΩ Note: Option 2 must be set to OFF to enable these options.
Skyroute CL3050 Standalone Wireless Communicator . Control Panel Skyroute CL3050 Zx COM RED BLK YEL GRN COM PGM 5.6KΩ Note: A relay may be required for proper operation in other configurations. See paragraph 3.3 Terminal Connections. Option 1 - Low battery All Modes If the battery voltage drops below 5.72VDC a trouble will be indicated until the battery voltage rises to 5.87VDC. Default - ON Option 2 - Input Supply Failure All Modes If AC power is absent or if DC power drops below 8.
6 Programming Descriptions All Modes [15] System Time When the time and day have been programmed, the values are saved and are used as the current time and day whenever the Skyroute CL3050 does a power up. Time and day programming is only required if the installer desires the Skyroute CL3050 to test transmit at a specific time and/or day. There is no "loss of time" trouble on the Skyroute CL3050.
Skyroute CL3050 Standalone Wireless Communicator Options 3, 4 - Zone Fault, Zone Fault Restores Modes 2, 3 When the system sees a short circuit across any zone, a zone fault is generated. DEOL resistors are required for zone fault reporting. In Section [11], Option [2] must be set to OFF and Option [3] must be set to ON; In Section [13], Option 3 must be set to ON and the Skyroute CL3050 must be operating in mode 2 or 3. Option 3. Default - OFF, Option 4.
6 Programming Descriptions The generic identifier will be sent with 98 as it's zone number, this is a special combination recognized by Connect 24 as a generic event. When the generic zone reporting toggle is disabled, each zone alarm for each zone type will then send it's own identifier. Default - ON. [21] System Event Communication Options NOTE: Section [20], Option [7] must be enabled for these events to be communicated.
Skyroute CL3050 Standalone Wireless Communicator 7 Programming Worksheets Zone Definitions (For Sections [01] -[02]) 00 Null Zone (Not Used) 01 Burglary 02 Fire 03 Panic 04 Technical 05 Gas 06 Heat 07 Medical 08 Emergency 09 Water 10 Freeze 11 Sprinkler 12 Hold-up 13 TLM Monitor (1 zone max.
7 Programming Worksheets [13] Skyroute CL3050 Trouble Mask Default Option On Option Off ON I___I Opt 1 Low Battery Disabled ON I___I 2 Input Supply Failure Disabled OFF I___I 3 Zone Fault/Tamper (DEOL only) Disabled ON I___I 4 No Service Available Disabled ON I___I 5 Radio Failure Disabled ON I___I 6 PC5108 Failure Disabled ON I___I 7 Failure to Communicate Disabled OFF I___I 8 Skyroute CL3050 Tamper Disabled [15] System Time Default Range 0000 I___I___I___I___I
7 Programming Worksheets [20] Transmission Options Default Option On Option Off ON I___I Opt 1 Zone Alarms Disabled OFF I___I 2 Zone Alarm Restores Disabled OFF I___I 3 Zone Fault Disabled OFF I___I 4 Zone Fault Restores Disabled OFF I___I 5 Zone Tamper Disabled OFF I___I 6 Zone Tamper Restores Disabled ON I___I 7 System Maintenance Events Disabled ON I___I 8 Generic Zone Reporting Detailed Zone Reporting [21] System Event Communication Options Default Option On
Glossary of Terms Glossary of Terms Cellemetry A network allowing short data packets to be sent on cellular control channels. Connect 24 Connect 24 is the service provider that provides the Skyroute service to the security industry and links the Skyroute cellemetry communicator to the central station. RSSI Radio Signal Strength Indication - This value is transmitted to Connect 24 during the periodic test transmission and can be viewed after power up by pressing the enroll button.
Skyroute CL3050 Standalone Wireless Communicator Appendix A: Reporting Codes Events Reporting Codes SIA Events Reporting Codes Contact SIA ID Contact ID Zone Alarms Zone Restores Burglary Zone BAXX E130 Burglary Zone BHXX R130 Fire Zone FAXX E110 Fire Zone FHXX R110 Panic Zone PAXX E120 Panic Zone PHXX R120 Technical Zone UAXX E140 Technical Zone UHXX R140 Gas Zone GAXX E151 Gas Zone GHXX R151 Heat Zone KAXX E158 Heat Zone KHXX R158 Medical Zone MAXX E100 M
Appendix A: Reporting Codes Event Reporting Code SIA Event Reporting Code SIA Contact ID Contact ID Zone Tamper Alarms Zone Tamper Restores Burglary Zone TAXX E137 Burglary Zone TRXX R137 Fire Zone FTXX E373 Fire Zone FJXX R373 Panic Zone TAXX E137 Panic Zone TRXX R137 Technical Zone TAXX E137 Technical Zone TRXX R137 Gas Zone TAXX E137 Gas Zone TRXX R137 Heat Zone TAXX E137 Heat Zone TRXX R137 Medical Zone TAXX E137 Medical Zone TRXX R137 Emergency Zone
©2002 Digital Security Controls Ltd. Toronto • Canada • 1-800-387-3630 www.dsc.com Printed in Canada 29034531r001 Forward comments about this manual to: pubs@dsc.