Specifications

D3000 and D4000 SERIES
COMPUTER TO ANALOG OUTPUT MODULES
D3000 and D4000 FEATURES
Analog output ranges: 0-1V, ±1V, 0-5V, ±5V, 0-10V,
±10V, 0-20mA, 4-20mA.
Communicates in ASCII with RS-232 or RS-485 serial
ports.
Programmable high/low output limits.
500Vrms output isolation.
12-bit output resolution.
Scaling in engineering units.
Baud rates: 300 to 38,400.
Nonvolatile digital calibration.
Output protection: 240VAC (current output).
±30V (voltage outputs).
Direct connection to ‘dumb’ terminals or modems.
Requires +10 to +30Vdc unregulated supply.
May be located up to 4,000 feet from host (RS-485).
Addressable: up to 124 units per serial port.
‘Bumpless’ manual control inputs.
D4000 PROGRAMMING FEATURES
Provides intelligent features not found in the D3000.
Fully programmable output slopes: 0.01V/s (mA/s)
to 10,000V/s (mA/s).
Programmable data scaling to any desired units.
True analog readback of output signal.
Programmable starting value.
Programmable watchdog timer provides orderly
shutdown in the event of host failure.
APPLICATIONS
Motion control
Motor speed control
Robotic welding control
Interfaces to modems
Programmable analog source for product test